Brand:

Eaton DILMC80 Contactor 80 A, 37 kW

Description

Eaton DILMC80(230V50HZ,240V60HZ) contactor for 37 kW at 400 V AC-3

The Eaton DILMC80(230V50HZ,240V60HZ) is a three-pole AC contactor from the Moeller DILM range, built to switch motors up to 37 kW at 400 V and 63 kW at 690 V in AC-3 duty. The DILMC80 has spring-loaded control terminals, which suit panels exposed to vibration from nearby compressors and fans. Seven Star LLC supplies the DILMC80(230V50HZ,240V60HZ) in Oman and the GCC.

With 80 A of AC-3 current and 110 A of AC-1 current it sits in the upper part of the DILM line. The housing measures 160 × 170 × 90 mm (length/depth × height × width) and weighs 2.154 kg, so panel space can be planned from the catalog entry before the order is placed.

How to read the model code DILMC80(230V50HZ,240V60HZ)

The code splits into three parts. DILMC80 is the contactor series and size: the number 80 is the rated AC-3 operational current in amperes at 400 V, here 80 A. The letter C after DILM marks the version with spring-loaded (cage-clamp style) control-circuit terminals; the main terminals remain screw type. There is no auxiliary-contact suffix, so the contactor itself carries three main poles only and any auxiliary contacts are added as snap-on modules. The bracket gives the coil: 230V50HZ,240V60HZ means the coil is designed for 230 V 50 Hz / 240 V 60 Hz AC coil.

DILMC80(230V50HZ,240V60HZ) technical specifications

Parameter Specification
Manufacturer / part number Eaton DILMC80(230V50HZ,240V60HZ) (catalog number 239618)
Series Eaton Moeller DILM contactor, Contactors for motors, spring-loaded control terminals
Number of main poles 3 (three N/O main contacts)
Auxiliary contacts None fitted; snap-on modules available
AC-3 rated current, 380/400/415 V 80 A
AC-3 rated power at 380/400 V, 50 Hz 37 kW
AC-3 rated power at 240 V, 50 Hz 27.5 kW
AC-3 rated current at 500 V 80 A
AC-3 rated current at 660/690 V 65 A (63 kW at 690 V)
AC-1 rated current, 380/400/415 V 110 A
AC-4 rated current at 380 to 415 V 40 A
Rated operational voltage Ue, AC, max 690 V
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 8000 V AC
Coil 230 V 50 Hz / 240 V 60 Hz AC coil
Pick-up / drop-out voltage 0.8 to 1.1 × Uc (pick-up); 0.6 to 0.3 × Uc (drop-out), of the coil rated voltage
Coil consumption, pick-up (50 Hz / 60 Hz) 310 VA / 345 VA
Coil consumption, sealed (50 Hz) 5.8 W / 26 VA
Closing / opening delay (main contacts) 14 to 20 ms / 9 to 14 ms
Mechanical lifespan 10,000,000 operations
Operating frequency 3600 operations per hour (mechanical)
Main terminals, stranded 1 x (16 – 70) mm² or 2 x (16 – 50) mm²
Main terminals, flexible with ferrule 1 x (10 – 70) mm² or 2 x (10 – 50) mm²
Control terminals, flexible with ferrule 1 x (0.75 – 1.5) mm² or 2 x (0.75 – 1.5) mm²
Copper band 2 x (6 x 16 x 0.8) mm
Tightening torque 14 Nm (main circuit)
Control terminals Spring-loaded
Short-circuit protection, type 2 coordination, 400 V / 690 V 160 A gG/gL / 160 A gG/gL
Ambient temperature, open -25 °C to 60 °C
Ambient temperature, enclosed (max) 40 °C
Heat dissipation (current-dependent / static) 9 W / 5.8 W
Degree of protection IP00
Dimensions 160 × 170 × 90 mm (length/depth × height × width)
Weight 2.154 kg

What the DILMC80(230V50HZ,240V60HZ) switches and how the coil behaves

Utilisation categories matter more than the headline ampere figure. In AC-3 the contactor starts squirrel-cage motors and breaks the current while the motor is running, which is the normal case for pumps, fans and compressors; the 80 A rating is for that duty. In AC-4, plugging and inching, the permitted current is much lower (40 A at 380 to 415 V), so a drive that is reversed or jogged often needs a larger contactor than its nameplate kilowatts suggest. In AC-1, for resistive loads such as heaters, the contactor carries 110 A.

The coil is a dual-frequency AC coil. Pick-up is specified at 0.8 to 1.1 × Uc of the rated control voltage and drop-out at 0.6 to 0.3 × Uc, so a control supply that sags during the start of a large motor in the same panel should still be checked against the lower limit. At pick-up the coil draws 310 VA at 50 Hz, falling to 5.8 W / 26 VA once the armature is sealed. That inrush matters when a PLC relay output or a small control transformer has to drive several contactors at once.

Closing takes 14 to 20 ms and opening 9 to 14 ms at the main contacts, which is useful when contactor timing is part of an interlocking or star-delta sequence. The catalog lists a mechanical life of 10,000,000 operations and an operating frequency of 3600 operations per hour (mechanical).

Where the DILMC80(230V50HZ,240V60HZ) fits in the DILM range

The DILM contactors from DILM40 to DILM95 form a continuous ladder of ratings, and the DILMC80(230V50HZ,240V60HZ) is one rung of it. Neighbouring catalog entries are the DILM40-22, DILM50, DILM65, DILM80 and DILM95; the DILMC variants carry the same power ratings with spring-loaded control terminals. For motor protection the usual companion devices are ZB overload relays and PKZM4 motor-protective circuit-breakers from the same manufacturer, and for control the auxiliary contact modules in the same series. Always confirm mechanical fit of an overload relay to the exact contactor before ordering.

Model AC-3, 400 V AC-3 power AC-1, 400 V Auxiliary contacts
DILM40-22 40 A 18.5 kW 60 A 2 N/O + 2 N/C
DILM50 50 A 22 kW 80 A none
DILM65 65 A 30 kW 98 A none
DILM80 80 A 37 kW 110 A none
DILM95 95 A 45 kW 130 A none

Selection checklist for the DILMC80(230V50HZ,240V60HZ)

  • Motor full-load current at the actual voltage: the 80 A AC-3 rating must exceed it with margin for the duty cycle.
  • Duty category: AC-3 for normal starting, AC-4 for plugging or jogging, AC-1 for heaters; for AC-4 use the 40 A figure.
  • Control voltage and frequency: this entry is for 230 V 50 Hz / 240 V 60 Hz AC coil; a different coil needs a different catalog entry.
  • Auxiliary contacts: none are included, so decide how many N/O and N/C contacts the control scheme needs.
  • Terminals: spring-loaded on the control side, screw main terminals taking 1 x (16 – 70) mm² or 2 x (16 – 50) mm² stranded.
  • Short-circuit protection: the catalog gives 160 A gG/gL for type 2 coordination at 400 V.
  • Ambient temperature: open mounting up to 60 °C, enclosed up to 40 °C.

Installation, commissioning and maintenance of the DILMC80(230V50HZ,240V60HZ)

Mount the contactor on a flat plate or on a suitable rail as shown in its instruction sheet and leave the clearances recommended for this size (FS4). Tighten the terminal screws to 14 Nm (main circuit) and keep conductor stripping lengths as specified. Use ferrules on flexible cable; the main terminal accepts 1 x (10 – 70) mm² or 2 x (10 – 50) mm² with ferrule.

During commissioning, measure the coil voltage at the terminals while the motor starts, not only at no load. A contactor that chatters or drops out during a start is almost always a voltage-drop problem in the control circuit. Check that the interlock between forward and reverse contactors is wired correctly before the first run. In service, inspect the contacts at planned shutdowns for pitting and blackening, check that the terminals are still tight after thermal cycling, and keep dust out of the armature area.

Typical applications in Oman and the GCC

Contactors of this size start the pumps, compressors and ventilation fans that run the large utility systems of Omani industrial sites: seawater and process-water booster pumps in desalination and water-treatment plants, cooling-tower fans, and compressors in gas processing. In the Gulf climate, switchgear rooms run warm and panels are often dusty, so the -25 °C to 60 °C ambient range, with the lower enclosed limit of 40 °C, should be compared with the real panel temperature rather than the room temperature. Where several contactors share a cabinet, use the heat-dissipation figure of 9 W per device when sizing air conditioning or ventilation. Typical uses are direct-on-line starters, the line and delta contactors of star-delta starters, soft starter bypass contactors and heater switching.

Information to send with an RFQ for DILMC80(230V50HZ,240V60HZ)

  • Exact part number DILMC80(230V50HZ,240V60HZ) and the quantity required.
  • Control voltage and frequency available in the panel.
  • Motor power, voltage and duty (normal starting, jogging or reversing).
  • Whether auxiliary contact modules or a mechanical interlock are required.
  • Delivery location and required date.

Documents and quotation

The official Eaton Moeller series contactor datasheet for the DILM80 frame, shown as DILM80(110V50HZ,120V60HZ) (English) is attached on this page as a PDF for the Eaton DILMC80. It lists the AC-1, AC-3 and AC-4 operational currents, the motor ratings from 220 V to 690 V, the coil pick-up and sealing power, the short-circuit coordination, the conductor cross-sections, the dimensions and the IEC/EN 60947, UL and CSA approvals. The DILMC80 is the spring-loaded terminal version of the same 37 kW DILM80 contactor, so the main-circuit ratings apply unchanged. Check the coil voltage, the auxiliary contact arrangement and the terminal type against your panel, then send us the quantity and the delivery location for a quotation.

Seven Star LLC supplies Eaton industrial control products in Oman and the GCC, quoting against the exact catalog number.

Other Models in the Eaton Dilm Contactor Large Range

Seven Star LLC supplies models from the Eaton Dilm Contactor Large range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Eaton DILM40-22 Contactor 40 A, 18.5 kWContactors & Overload RelaysView details
Eaton DILM50 Contactor 50 A, 22 kWContactors & Overload RelaysView details
Eaton DILM65 Contactor 65 A, 30 kWContactors & Overload RelaysView details
Eaton DILM80-22 Contactor 80 A, 37 kWContactors & Overload RelaysView details
Eaton DILM95-22 Contactor 95 A, 45 kWContactors & Overload RelaysView details
Eaton DILMC80 Contactor 80 A, 37 kWContactors & Overload RelaysYou are viewing this model
Eaton DILMC95 Contactor 95 A, 45 kWContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Eaton DILM80 Contactor Datasheet (PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.

Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.

Eaton company profile

Founded 1911, New York, USA, by Joseph O. Eaton
Early move Cleveland, Ohio, 1914
Headquarters Dublin, Ireland, since the 2012 Cooper Industries acquisition
Listing New York Stock Exchange (ETN)
Brands Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC
Product families FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling

Milestones

  • 1911: Joseph O. Eaton starts an axle business in New York.
  • 1914: The business moves to Cleveland.
  • 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.

Eaton circuit protection listed here

The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.

Where Eaton breakers and fuses are used

Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.

Eaton products we list

Family Examples
Circuit Breakers LPJ-35SP Class J Time-Delay Fuse, NZMN1-A80 Molded Case Circuit Breaker, NZMN2-A250 Molded Case Circuit Breaker, NZMN3-AE400 Molded Case Circuit Breaker, PKZM0-1
AC Drives DA1-342D2FB-A20C AC Drive, PowerXL DG1-34140FN-C21C Variable Freque…

Ordering Eaton parts: what we need

Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.

Facts checked against Eaton's corporate history and investor materials, October 2026.

FAQ

Questions about the Eaton DILMC80 Contactor 80 A, 37 kW

Answers from our engineering team on installation, compatibility and integration.

01What is the AC-3 rating of the DILMC80(230V50HZ,240V60HZ)?
The catalog entry lists 80 A at 380/400/415 V AC-3, which corresponds to 37 kW at 400 V and 27.5 kW at 240 V, 50 Hz. At 690 V the AC-3 current is 65 A.
02What coil does the DILMC80(230V50HZ,240V60HZ) use?
The coil is specified as 230 V 50 Hz / 240 V 60 Hz AC coil. The coil draws 310 VA at pick-up at 50 Hz and 5.8 W / 26 VA when sealed, so the control supply must cope with the inrush.
03Does the DILMC80(230V50HZ,240V60HZ) include auxiliary contacts?
No auxiliary contacts are listed on the contactor itself. Snap-on auxiliary contact modules are added separately where the control scheme needs them. Count the contacts needed before ordering.
04Which terminals does the DILMC80(230V50HZ,240V60HZ) have?
Main terminals are screw type and take 1 x (16 – 70) mm² or 2 x (16 – 50) mm² stranded; the control terminals are spring-loaded. The catalog gives a tightening torque of 14 Nm (main circuit).
05Can the DILMC80(230V50HZ,240V60HZ) be used for jogging or reversing duty?
Reversing and jogging are AC-4 duty, where the permitted current is lower: 40 A at 380 to 415 V for this contactor. Size it from the AC-4 value, not from the AC-3 kilowatt rating.