- Automation & ControlView all 3,063 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- Encoders
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Bürkert
Bürkert 436473 Type 8032 SE32 Dual Output Flow Detector
Description
Overview
With two independently configurable transistor outputs and a freely positionable 5-pin M12 male connector, Bürkert 436473 is the flexible version of the Type 8032 threshold detector. The SE32 electronics monitor liquid flow with a paddle wheel, show it on an 8-digit backlit display and drive two outputs, NPN or PNP according to wiring, so one device can issue a low-flow alarm and a high-flow alarm at once. Seven Star LLC is an independent supplier serving Oman and the GCC.
Two outputs, many functions
- Output 1 and output 2 each operate as hysteresis or window functions.
- Either transistor works as NPN or PNP depending on how it is wired, up to 700 mA in total and 500 mA each when both are used.
- Frequency output up to 300 Hz is available for pulse signals.
- The 5-pin M12 male connector can be turned to align with the cable route.
- Short-circuit protection on both transistors.
Specification of Bürkert 436473
| Parameter | Value |
|---|---|
| Article | 436473, SE32 threshold detector, 2 transistors, no UL |
| Outputs | 2 x transistor, NPN and/or PNP, open collector |
| Output current | 700 mA max.; 500 mA per transistor if both wired |
| Electrical connection | Free positionable 5-pin M12 male connector |
| UL approval | No (UL Recognized version is 553431) |
| Principle | Paddle wheel with 8-digit backlit LCD |
| Supply | 12 to 36 V DC plus or minus 10 percent, SELV and LPS, reverse-polarity protected |
| Current consumption | 80 mA or less with no load |
| Flow range | 0.5 to 1000 l/min, 0.3 to 10 m/s with Type S030 fitting |
| Deviation | teach-in plus or minus 1 percent; standard K factor plus or minus 3 percent |
| Linearity and repeatability | 0.5 percent of full scale; 0.4 percent of reading |
| Operating mode | threshold with window or hysteresis |
| Pipe size | DN 06 to DN 65 |
| Viscosity and solids | 300 cSt max.; up to 1 percent solids, 0.5 mm |
| Fluid temperature with S030 | PVC 0 to 50; PP 0 to 80; PVDF, steel or brass minus 15 to plus 100 degrees C |
| Fluid pressure | plastic PN 10, metal PN 16 |
| Housing | glass fibre reinforced PC, polyester front film |
How Bürkert 436473 differs from the single-output articles
Articles 436474 and 434871 each provide one transistor and use the DIN cable plug. 436473 doubles the output count and exchanges the cable plug for an M12 connector, which is faster to mount and is common in machine builds with pre-moulded cables. Relay article 436475 adds a 250 V AC rated contact when mains switching is needed, and the transmitters add 4 to 20 mA. The M12 connector requires a female cable connector that is not part of the delivery.
Wiring, supply and protection
Use a shielded supply cable up to 100 m long. The supplied female cable plug takes wire with 6 to 7 mm outside diameter and 0.25 to 1.5 mm2 cores, while 5-pin and 8-pin M12 female connectors, which are not supplied, take thinner cable. Power must come from a limited power source, and in damp or outdoor installations the voltage is limited to 35 V DC. Fasten the cable plug fully so that the enclosure keeps its rating, and loop the cable downward before the entry to form a drip loop.
Ordering and related items
The electronics, the Inline fitting and the connector are different items, so a complete measuring point needs at least two or three articles. List the pipe size, material and connection of the fitting, and the connector style for the electronics. Cable connectors for M12 versions are accessories and are not included in the scope of delivery. If you have a standard for spares, keep one electronics module per critical line, because they are interchangeable on the same fittings.
Alarm strategy with two outputs
Use output 1 as a minimum-flow alarm with hysteresis and output 2 as a window that confirms flow inside the normal band. The PLC can then distinguish no flow, low flow, normal flow and excessive flow. In dosing and cooling services, wire the first output to a pump interlock and the second to an alarm annunciator.
Why a display on the sensor still helps
The 8-digit backlit LCD on the module shows flow rate or total, and three keys allow the operator to change thresholds and units on site. This saves a trip to the control room during commissioning and gives operators a local indication when the PLC link is lost. A teach-in routine lets you fill a known volume and correct the K factor, improving accuracy from plus or minus 3 percent with the default factor to plus or minus 1 percent at the teach-in flow.
Wiring the M12 connector of Bürkert 436473
The five-pin M12 male connector carries supply positive, supply negative, the two outputs and the fifth pin as defined in the data sheet pin assignment. Use a shielded female M12 connector with moulded cable of the right length, or a field-wireable female connector with a cable of 3 to 6.5 mm diameter. Take care to match the pin colours with the data sheet because connectors from different makers use different colour codes. Check each output with a multimeter before connecting to the PLC.
The free positionable connector can be rotated, which lets the cable leave the device towards the cable tray without sharp bending.
Quotation notes for Bürkert 436473
Please give the article number, the number of units, the pipe size, the fitting material and connection, and any M12 cable lengths needed. The female M12 connector is not included. State the PLC input type so the correct output wiring can be confirmed. Delivery to Oman and the wider GCC region will be planned from this information.
Where two outputs help
Two outputs allow a low flow alarm and a high flow alarm, a pump trip and a warning, or a flow window around a setpoint. They also let a single sensor serve a PLC and a local indicator lamp at the same time, which saves wiring and parts.
Related items you may also need: Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Bürkert Type 8681 Control Head for Hygienic Process Valves | Veeder-Root EMR4 Electronic Meter Register | All Bürkert products.
Documents and quotation
The Type 8032 data sheet containing Bürkert 436473 is attached with ordering charts and dimensions. Send an RFQ with part number 436473, quantity and delivery location in Oman or the GCC, and mention pipe size and material for the Inline fitting.
Other Models in the 8032 Range
Seven Star LLC supplies models from the 8032 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Bürkert 434871 Type 8032 SE32 PNP Flow Threshold Detector | Turbine & Positive Displacement Flowmeters | View details |
| Bürkert 436473 Type 8032 SE32 Dual Output Flow Detector | Turbine & Positive Displacement Flowmeters | You are viewing this model |
Datasheets & Documents
- Datasheet Bürkert 436473 Type 8032 SE32 Dual Output Flow Detector Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.
Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.
Bürkert company profile
| Founded | 1946, by Christian Bürkert |
|---|---|
| Headquarters | Ingelfingen, Germany |
| Ownership | Family-owned |
| Product families | Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers |
Bürkert types listed on this page
Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.
Ordering Bürkert valves: what we need
The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.
Facts checked against Bürkert's published company history, October 2026.
Browse Bürkert products by category: Solenoid Valve, Control Valves.
FAQ
Questions about the Bürkert 436473 Type 8032 SE32 Dual Output Flow
Answers from our engineering team on installation, compatibility and integration.
01How many outputs does Bürkert 436473 have?
It has two transistor outputs, each wired as NPN or PNP, with a total rating of 700 mA and 500 mA each when both are used.
02What connector has 436473?
It has a free positionable 5-pin M12 male connector; the matching female connector is not part of the delivery.
03Can Bürkert 436473 give a flow window alarm?
Yes. Operation can be parameterised as threshold with either hysteresis or window functions on the outputs.
04What is the UL version of 436473?
The UL Recognized equivalent is listed as article 553431 in the Type 8032 ordering chart, while 436473 has no UL approval.
05What pipe sizes suit 436473?
With a Type S030 Inline sensor-fitting, pipes from DN 06 to DN 65 are covered, with flow from 0.5 to 1000 l/min.


















Reviews