Brand: Bürkert
Bürkert 444007 Type 8035 SE35 Inline Flow Transmitter
Description
Overview
Where a process needs both a flow signal and local switching, Bürkert 444007 fits well. It is the Type SE35 compact flow transmitter of the Bürkert Type 8035 inline flowmeter family, in the 12 to 36 V DC version with a Hall sensor, a 4 to 20 mA three-wire output, a pulse output and two relay outputs, with two cable glands. Seven Star LLC is an independent supplier serving Oman and the GCC.
The Type 8035 is an inline paddle-wheel meter. The transmitter bayonets onto a Type S030 inline sensor-fitting which is welded, threaded, flanged or glued into the pipe, and the fitting material (brass, stainless steel, PVC, PP or PVDF) is chosen to suit the medium. The pair covers pipes from DN 6 to DN 65.
Why Bürkert 444007 is useful
- Combined analogue, pulse and relay outputs let one device feed the PLC and switch a pump or alarm locally.
- Flow rate range of 0.5 to 1000 l/min (0.13 to 265 gpm) and velocity range of 0.3 to 10 m/s.
- Paddle wheel in PVDF on an Al2O3 ceramic axis.
- Alphanumeric 8-digit display, 15 by 60 mm, with 9 mm characters.
- Bayonet connection to the fitting for quick removal during service.
- UL Recognized options exist for the family under other article numbers.
Technical data of Bürkert 444007
| Parameter | Value |
|---|---|
| Article number | 444007 |
| Device | Type SE35 flow transmitter for Type 8035 |
| Supply | 12 to 36 V DC |
| Sensor | Hall |
| Outputs | 4 to 20 mA (3-wire), pulse, 2 relays |
| Electrical connection | 2 cable glands |
| Pipe range | DN 6 to DN 65 with Type S030 fitting |
| Flow range | 0.5 to 1000 l/min |
| Deviation, teach-in | plus or minus 1 percent of reading |
| Deviation, standard K factor | plus or minus 2.5 percent of reading |
| Linearity | plus or minus 0.5 percent of full scale |
| Repeatability | plus or minus 0.4 percent of reading |
| Fluid pressure | plastic fittings max. PN 10; metal max. PN 16 |
| Fluid temperature | PVC 0 to 50, PP 0 to 80, metal or PVDF minus 15 to plus 100 degrees C |
| Viscosity and solids | max. 300 cSt; max. 1 percent solids, 0.5 mm |
| Air humidity, altitude | up to 80 percent without condensation; max. 2000 m |
How 444007 differs from other 8035 variants
The 8035 list offers nine compact flowmeter articles. The plain 2-wire 4 to 20 mA plus pulse model with a female cable plug is 444005 and with two cable glands 444006, whereas Bürkert 444007 adds a third wire and two relays. On AC supply the equivalents are 423922 for 2-wire and 423924 for three-wire with relays, and the battery indicator is 423921. UL Recognized versions of this exact device carry the number 553433.
The batch controller versions, such as 443360 on DC, add four digital inputs and relay and transistor outputs for dosing. If you only need a signal to a PLC, choose the 2-wire model; if you need a local high or low flow alarm without extra relays, this is the right article.
Where it is used
In Oman and the GCC this meter appears on water treatment skids, cooling circuits for compressors and chillers, reverse osmosis permeate lines, chemical dosing loops and boiler make-up. The relays can trip a pump on low flow, protecting equipment that must not run dry.
Selection and compatibility notes
Pick the Type S030 fitting first: its material fixes the allowed temperature and pressure. PVC limits fluid to 50 degrees C, PP to 80 degrees C, and metals or PVDF to 100 degrees C. Particles above 0.5 mm or more than 1 percent solids will damage the paddle wheel. Provide a limited power source meeting EN 62368-1 or a limited-energy circuit under EN 61010-1, and use shielded cable up to 50 m with a temperature rating above 80 degrees C.
Wiring and output planning
The ordering chart separates the 2-wire and 3-wire current outputs into different articles, so the wiring of a replacement must match the original: a loop-powered 2-wire device is not a drop-in for a 3-wire device with relays. Plan the pulse output and the two relay contacts together with the PLC input cards, and note the supply limit described above. The detailed parameter menu, relay behaviour and teach-in steps are described in the device operating instructions, which should be kept with the commissioning records for Bürkert 444007.
Environmental limits from the datasheet are worth checking at the design stage: relative humidity up to 80 percent without condensation, altitude up to 2000 m, indoor or outdoor use with protection from direct sunlight, and continuous operation. In a hot outdoor skid in the Gulf, a shade or enclosure is advisable to keep the polycarbonate housing and display within comfortable limits.
Installation and commissioning
Install the fitting with at least the straight pipe runs specified for paddle wheel meters, with the pipe always full. Click Bürkert 444007 onto the bayonet, route cables through the two glands and close the lid. Run the teach-in procedure at a known flow or enter the K factor of the fitting.
Maintenance
Take the transmitter off the bayonet, rinse the paddle wheel and check that it spins freely. Replace seals when changing fittings, and keep the lid and glands tight so that the PC housing remains dry.
Ordering notes for Bürkert 444007
Quote 444007 in your RFQ together with the pipe size and material, and we will help identify the S030 fitting. Tell us if you need the UL Recognized equivalent.
Related items you may also need: Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Bürkert Type 8681 Control Head for Hygienic Process Valves | Elster TRZ2 Turbine Gas Meter DN50 to DN150 | All Bürkert products.
Documents and quotation
The Type 8035 datasheet is attached to this listing. To request pricing, send part number 444007, the quantity and your delivery location in Oman or the GCC through the RFQ form and we will confirm availability and lead time.
Datasheets & Documents
- Datasheet Bürkert 444007 Type 8035 SE35 Inline Flow Transmitter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.
Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.
Bürkert company profile
| Founded | 1946, by Christian Bürkert |
|---|---|
| Headquarters | Ingelfingen, Germany |
| Ownership | Family-owned |
| Product families | Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers |
Bürkert types listed on this page
Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.
Ordering Bürkert valves: what we need
The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.
Facts checked against Bürkert's published company history, October 2026.
Browse Bürkert products by category: Solenoid Valve, Control Valves.
FAQ
Questions about the Bürkert 444007 Type 8035 SE35 Inline Flow
Answers from our engineering team on installation, compatibility and integration.
01What is Bürkert 444007?
It is the Type SE35 compact flow transmitter for the Type 8035 inline flowmeter, 12 to 36 V DC, Hall sensor, 4 to 20 mA 3-wire plus pulse and two relays.
02Which pipes does the 8035 cover?
With a Type S030 inline sensor-fitting it covers pipes from DN 6 to DN 65.
03What flow range does 444007 measure?
The datasheet lists 0.5 to 1000 l/min and a flow velocity of 0.3 to 10 m/s.
04What pressure and temperature limits apply?
They depend on the S030 fitting: plastic up to PN 10, metal up to PN 16, with fluid temperatures from minus 15 to plus 100 degrees C for metal or PVDF.
05Does 444007 have relay outputs?
Yes, the ordering chart lists 4 to 20 mA three-wire plus pulse plus two relays for this article.