Brand: ABB
ABB Uvisor SF810 Safe Flame Scanner
Description
Overview
The ABB Uvisor SF810 is a Safe Flame Scanner, not a stack gas analyzer, that detects burner flame presence and quality by sensing UV, visible, and infrared radiation from the flame. It feeds this signal into a burner management system (BMS) for combustion safety interlocks on industrial and utility boilers, distinct from the related SF810i model, which adds an integrated Combustion Index function.
Seven Star LLC supplies the ABB Uvisor SF810 and the wider Uvisor flame scanner range to power generation and industrial combustion facilities across Oman and the GCC, with application guidance for burner management system integration.
Detection Principle
The SF810 pairs a burner-mounted detector head with a separate remote flame amplifier unit (FAU810), using dual-wavelength UV/IR detection to distinguish real flame from background radiation across gas, oil, coal, lignite, and biomass fuels. This multi-wavelength approach lets the scanner reliably confirm flame presence across very different fuel combustion characteristics, rather than being tuned to only one fuel type’s typical radiation signature.
Flame-failure response is programmable from 0.2 to 4 seconds, and the system is built on a fail-to-safe philosophy, so a scanner or signal fault drives the BMS toward a safe fuel-shutoff state rather than leaving the burner in an undefined condition during a detection failure.
Engineering Design of the SF810
The scanner carries an explosion-proof ATEX II 2GD T6 rating with an IP66/IP67 enclosure for direct mounting on burner fronts in classified hazardous areas, reflecting the reality that flame scanners are mounted directly on or near the combustion equipment they are monitoring rather than in a remote safe area. It communicates via 4-20 mA analog outputs and relays, with optional Modbus RTU or Profibus DP for integration into digital burner management architectures.
Separating the detector head from the remote flame amplifier unit (FAU810) allows the sensitive amplification electronics to be mounted away from the highest-temperature zone directly at the burner front, while the detector head itself is built to withstand that harsher thermal environment.
Key Features
- Dual-wavelength UV/IR flame detection
- Compatible with gas, oil, coal, lignite, and biomass fuels
- Programmable flame-failure response, 0.2 to 4 seconds
- Fail-to-safe design philosophy
- ATEX II 2GD T6 explosion-proof rating
- IP66/IP67 enclosure for burner-front mounting
- 4-20 mA analog output plus relay outputs
- Optional Modbus RTU or Profibus DP communication
Industrial Applications
The SF810 is used on industrial and utility boilers and furnaces to provide reliable flame-proving for combustion safety, supporting precise air-fuel control and helping plants avoid unsafe fuel-rich conditions across multiple fuel types. It is a standard component of burner management systems on power generation and heavy industrial combustion equipment where flame-out detection speed and reliability are safety-critical.
Across Oman, Muscat, Sohar, Salalah, and the GCC, Seven Star LLC supports power generation and industrial combustion operators as a trusted supplier of ABB Uvisor flame scanners, helping plants maintain reliable burner management and combustion safety systems.
Technical Specifications
| Model | ABB Uvisor SF810 |
| Type | Safe Flame Scanner |
| Detection Method | Dual-wavelength UV/IR |
| Fuel Compatibility | Gas, oil, coal, lignite, biomass |
| Flame-Failure Response | Programmable, 0.2 to 4 seconds |
| Hazardous Area Rating | ATEX II 2GD T6, IP66/IP67 |
| Communication | 4-20 mA, relays, optional Modbus RTU/Profibus DP |
Request a Quote for ABB Uvisor SF810 Safe Flame Scanner
Contact Seven Star LLC for a quotation, lead time, and technical support on the ABB Uvisor SF810 Safe Flame Scanner and the full Uvisor flame detection range across Oman and the GCC.
Installing and Aligning the SF810
A flame scanner is only as good as its sight line. On a single-burner boiler the scanner looks at one flame, but on a multi-burner furnace it must be positioned so it sees the root of its own burner’s flame and not the fireball or the neighbouring burners. Poor discrimination is the most common reason a scanner keeps proving flame after its burner has tripped.
- Aim the sight tube at the primary combustion zone near the burner throat, where the flame is most stable and its signal is strongest.
- Provide clean, dry purge air to the sight tube so soot, ash and oil vapour do not build up on the lens and so the head stays cool.
- Use a swivel mount during commissioning to find the best viewing angle, then lock it.
- Run the signal cable between the detector head and the FAU810 amplifier away from ignition transformers and power cables.
Commissioning checks
With the burner firing across its turndown range, record the flame signal at minimum and maximum load. Then shut the burner down while adjacent burners keep firing and confirm the signal falls clearly below the flame-off threshold. Set the flame-on and flame-off thresholds with a comfortable margin between them and set the flame-failure response time to suit the BMS and the relevant combustion safety standard. Finally, prove the complete trip path from scanner to fuel shut-off valves.
Maintenance and Troubleshooting
- Weak signal at high load: dirty lens, insufficient purge air or a sight tube partly blocked by deposits.
- Nuisance trips at low fire: the scanner is looking at the outer, unstable part of the flame; re-aim toward the root.
- Signal remains after the burner stops: the scanner sees adjacent flames or glowing refractory; improve the sight angle and review the thresholds.
- Intermittent faults: check cable screening, terminations and the temperature at the detector head.
Include lens cleaning and a purge-air check in each planned outage, and log flame signal levels so a slow decline is spotted before it causes a trip.
Applications in Oman and the GCC
Across the region the SF810 fits utility and process boilers at power and water plants, fired heaters in refineries and petrochemical complexes, and package boilers in industry. Many of these units fire natural gas with liquid fuel as a backup, which makes a multi-fuel scanner useful. Summer heat and airborne dust make purge-air quality and head temperature especially important at outdoor burner fronts.
Sourcing from Seven Star LLC
For a replacement, send us the model and order code from the scanner label, the amplifier model, the fuel types fired and the communication option in use. Seven Star LLC checks the configuration against your existing BMS interface and confirms lead time and delivery.
Related Products
Datasheets & Documents
- Datasheet ABB Uvisor SF810 Safe Flame Scanner Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB, formed in 1988 and headquartered in Zurich, covers an unusually long stretch of a plant's equipment list, from the flowmeter and analyzer in the field to the drive, breaker and protection relay in the electrical room.
Seven Star LLC is an independent supplier serving Oman and the GCC. Our ABB listing concentrates on measurement and analytics: ABB flowmeters, liquid analysis sensors and systems, level and pressure instruments. It also includes valve actuators, low voltage circuit breakers, ABB drives, soft starters and protection relays.
ABB product families on this page
Flow measurement includes ABB electromagnetic, Coriolis, vortex and swirl meters, sold under names such as ProcessMaster, AquaMaster, CoriolisMaster and SwirlMaster. Liquid analysis covers pH, conductivity and dissolved oxygen sensors with their transmitters. SensyTemp TSP sensors handle temperature. On the electrical side the listing has ACS355 machinery drives, the ACS550 general purpose drive, the ACQ580 for water and wastewater and the ACS880-01 industrial drive, with fieldbus adapters such as the FPBA-01 for PROFIBUS DP. Protection and switching products include SACE Tmax XT molded case breakers, SACE Emax 2 air circuit breakers, PSR soft starters and the REM615 and RET615 relays.
Where ABB instruments and drives are used
Water and wastewater plants use the electromagnetic flowmeters, analyzers and ACQ580 drives together. Oil and gas, power and chemical plants specify the Coriolis and vortex meters, pressure and level transmitters and the 615 series relays for motor and transformer feeders. The drives run pumps, fans, conveyors and compressors in almost every industry.
Ordering ABB parts: what we need
For drives send the full type code from the rating label, for example ACS355-03E-05A6-4, plus the serial number if it is a replacement. For instruments send the complete order code, measuring span, process connection, wetted materials, output or protocol and the hazardous area approval. For breakers give frame size, rated current, breaking capacity, number of poles, trip unit and fixed or withdrawable version.
Related products
Frequently Asked Questions
No, it is a Safe Flame Scanner that detects burner flame presence and quality, feeding a signal to the burner management system.
The SF810i adds an integrated Combustion Index function; the standard SF810 provides core flame detection without that added feature.
It is compatible with gas, oil, coal, lignite, and biomass fuels through its dual-wavelength UV/IR detection.
Yes, it carries an explosion-proof ATEX II 2GD T6 rating with an IP66/IP67 enclosure for burner-front mounting.
Yes, Seven Star LLC supplies genuine ABB Uvisor flame scanners across Oman and the GCC, with application guidance for BMS integration.