Brand:

Rotork CVL-5000 Heavy-Duty Electric Linear Actuator

Description

When a control valve needs more than 6,672 N, the CVA linear range stops at one model: Rotork CVL-5000. It is rated at 5,000 lbf (22,241 N), has a maximum stroke of 4.5 in (114.3 mm), and weighs 51 kg without or 53 kg with the reserve powerpack. Everything about it is scaled up, from the M12 mounting bolts to the lifting requirements, so it deserves separate attention from its smaller CVL cousins.

Rotork CVL-5000 main data

Rated thrust 5,000 lbf / 22,241 N
Minimum settable thrust 2,000 lbf / 8,869 N
Maximum stroke 4.5 in / 114.3 mm
Speed 0.1 in/s / 2.54 mm/s
Full-stroke time 45 s
Weight 51 kg without powerpack, 53 kg with powerpack
Valve interface MSS SP-102 FA12 / ISO 5210 F12; 4 x M12 x 1.75 holes, 24 mm deep, on a 125 mm PCD (1/2 in UNC on 4.95 in PCD alternative)
Fixing torque M12 at 46 Nm (34 lbf.ft)
Supply 100 to 240 VAC 50/60 Hz only; no 24 VDC version
Powerpack charge time 300 s
Design life 5 million 1 percent strokes at 75 percent load; 2.5 million 10 percent strokes at 100 percent load
Enclosure IP66/IP68, Type 4 and 6
Flamepath top cover 0.20 mm maximum gap, 40 mm minimum length

Handling and mounting the CVL-5000

The user manual calls out that the CVL-5000 requires additional lifting provision compared with the smaller units; do not attempt to hang it by the output shaft. The output shaft carries a protective cap that is removed during fit-up, and there is an extra cap screw on this size that does not appear on the CVL-500 to CVL-1500. The four M12 fixings must be tightened to 46 Nm (34 lbf.ft), and the alignment between the actuator shaft and valve stem should be verified before the bolts are pulled down, because misalignment raises mechanical wear.

Electrical demand of CVL-5000

Only AC supply is offered. At 240 VAC the CVL-5000 draws 9.54 W (0.15 A) at standstill, 37.63 W (0.24 A) running free, 74.31 W (0.37 A) at half load, and 116.8 W (0.55 A) at full load, with a 127.82 W (0.59 A) peak while the super capacitors charge. A continuous modulation test at 0.5 Hz and 2 percent cycling averages 43.79 W (0.28 A). The reserve capacitor pack needs 200 mA, 4.8 W after charging, larger than the 20 mA used by smaller models, and takes 300 s to charge before the actuator will move.

How CVL-5000 differs from other CVA variants

The CVL-5000 has 3.3 times the force of CVL-1500, 10 times the force of CVL-500, and more than twice the stroke of CVL-1000 and CVL-1500. It is the slowest at 45 s, has the lowest design-life count (5 million small strokes against 40 million for the CVL-500) and is the only CVA linear model with no 24 VDC supply. It is also the only linear size mounted on an F12 / FA12 pattern. On the rotary side, CVQ-2400 provides 271 Nm and is intended for quarter-turn valves.

Where a CVL-5000 belongs

Large globe and cage control valves in boiler feedwater, turbine bypass, anti-surge recycle trims at compressor stations, desuperheater spray control and high-differential water injection are classic uses. The big stroke fits valves of 8 in and above with long travel, and 22,241 N reduces the need for hydraulic power units on remote sites without compressed air. Back-drive resistance is 125 percent of rated force, so the CVL-5000 holds the valve steady against 27,801 N of reverse load without a brake.

At the same time, a 45 s full stroke makes it unsuitable for fast anti-surge duty; there, a pneumatic or hydraulic actuator is still the conventional choice. Always compare your required stroking time with the datasheet.

Control, set-up and diagnostics for CVL-5000

4 to 20 mA is standard; HART, Pakscan, Profibus, Foundation Fieldbus and Modbus cards are options. Bluetooth set-up uses Enlight, and the quick set-up routine drives to both ends, stores the thrust reference, and then supports tuning of speed from 5 to 100 percent. Data logging allows comparison of friction against the reference stroke.

Service planning for Rotork CVL-5000

The geartrain is lubricated for life and the motor is brushless. Plan work around the valve packing, stem coupling and conduit seals. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Certification notes for CVL-5000: hazardous-area enclosures in ATEX, UKEx and IECEx form (Ex db h [ia IIC Ga] IIB T4 Gb, with IIC and increased-safety variants) are offered across the CVA family, with ambient limits of -20 to +60 C or -40 to +60 C for the low-temperature option. For the CVL-5000 specifically, the manual gives the top cover flamepath as 0.20 mm maximum gap and 40 mm minimum length, wider than the 0.15 mm and 25 mm values of the smaller CVL models, and the output shaft bush as a negative 0.018 mm interference fit with at least 25.5 mm length. These details matter when site inspectors check flameproof joints.

Environmental limits are the same as for other CVA units: IP66/IP68 (7 m for 72 hours), Type 4 and 6, vibration to 1 g RMS from 10 to 1,000 Hz, shock to 5 g peak and under 61 dB(A) at 1 m. Because the unit is heavy, vibration-prone pipework should be checked before mounting on a long stem yoke.

Documents and quotation

The attached datasheet is the Rotork CVA range brochure covering CVL-5000. Send an RFQ naming CVL-5000, quantity, AC supply, stem or coupling detail and hazardous-area requirement.

Selection Notes for the Rotork CVL-5000

When comparing the Rotork CVL-5000 with alternatives, start from the duty it must perform: the measured or controlled variable, the range and accuracy you need, the environment at the mounting point and the interface to your control system. Check the electrical and mechanical connections against the installed equipment, and confirm any hazardous-area or ingress-protection requirements for the location. If any point is unclear, send a photo of the nameplate and a short description of the application, and we will compare it with the Rotork electric actuators range and confirm the correct order code before you commit.

Documentation and Compliance

Industrial buyers often need more than the hardware. When you order the Rotork CVL-5000, tell us which documents your project or quality team requires, such as certificates of origin, conformity declarations, calibration or test records, or hazardous-area certificates where the variant carries them. Mentioning these at the enquiry stage avoids delays at customs and at goods receipt on site. For tenders and project packages, we can also align the quotation with your line-item format so that Rotork electric actuators items can be checked against the bill of materials quickly.

Other Models in the Rotork Cva Range

Seven Star LLC supplies models from the Rotork Cva range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Rotork CVQ-1200 Quarter-Turn Electric Control ActuatorElectric ActuatorsView details
Rotork CVL-1500 Electric Linear Actuator 6,672 NElectric ActuatorsView details
Rotork CVL-5000 Heavy-Duty Electric Linear ActuatorElectric ActuatorsYou are viewing this model
Rotork CVQ-2400 Quarter-Turn Electric Actuator 271 NmElectric ActuatorsView details
Rotork CVL-1000 Linear Electric Actuator 4,448 NElectric ActuatorsView details
Rotork CVL-500 Linear Electric Control Valve ActuatorElectric ActuatorsView details
Datasheets & Documents
  • PDF Datasheet Rotork CVL-5000 Heavy-Duty Electric Linear Actuator Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Rotork is a British flow control company best known for electric valve actuators. Jeremy Fry founded Rotork Engineering Company in Bath in 1957, the year its first actuator, the 100A, went on sale, and the group is still headquartered in Bath and listed on the London Stock Exchange. Today Rotork makes electric, pneumatic, hydraulic and electro-hydraulic actuators, gearboxes, precision regulators and valve positioners.

Seven Star LLC is an independent supplier listing Rotork actuators, Rotork Fairchild regulators, YTC positioners and spare parts for buyers in Oman and the GCC. Replacement units are matched from the actuator nameplate and wiring diagram number.

Rotork company profile

Origin Founded by Jeremy Fry in 1957 in Bath, England; first product the 100A valve actuator
Headquarters Brassmill Lane, Bath, United Kingdom
Ownership Rotork plc, a public company listed on the London Stock Exchange
Acquired brands Fairchild precision pneumatic controls (2011, Winston-Salem, USA), YTC valve positioners (Young Tech Co., Seoul, 2014), Mastergear gearboxes (2016)
Product families Intelligent electric actuators, control valve actuators, electro-hydraulic and fluid power actuators, gearboxes, precision regulators, positioners and network control systems

Milestones

  • 1957: Jeremy Fry founds Rotork in Bath, England; the first product is the 100A valve actuator.
  • 2011: Fairchild precision pneumatic controls (Winston-Salem, USA) is acquired.
  • 2014: YTC valve positioners (Young Tech Co., Seoul) is acquired.
  • 2016: Mastergear gearboxes is acquired.

Rotork actuators, regulators and positioners

Series Type Typical use
IQ3 Intelligent multi-turn electric actuator Gate and globe valves, penstocks and sluice gates; non-intrusive setup with a Bluetooth setting tool, double-sealed enclosure, data logging
IQT3 Intelligent part-turn electric actuator Ball, butterfly and plug valves and dampers, with the same setup and diagnostics as IQ3
CVA Precision control valve electric actuator Continuous modulating control of linear and part-turn control valves where instrument air is not available
CMA Compact modulating electric actuator Small control valves, chemical injection and metering pumps
Skilmatic SI3 Self-contained electro-hydraulic actuator Spring-return fail-safe and ESD duty with partial stroke testing, needing only an electrical supply
GP / GH Scotch yoke pneumatic (GP) and hydraulic (GH) actuators Large quarter-turn valves on pipelines and ESD service; spring-return or double-acting
CP Compact pneumatic quarter-turn actuator Smaller on-off ball and butterfly valves on plant air
Fairchild 10, 30, 55, 66, M11, 81 Precision pressure regulators Instrument air to positioners and actuators, test benches; Model 66 in stainless steel for corrosive and offshore sites
Fairchild 1000 No-bleed precision regulator Saves instrument air or gas where continuous bleed is not acceptable
Fairchild 10BP, 4000ABP Back pressure regulators Holding upstream pressure in process and test systems
YTC YT-1000, YT-3300 Valve positioners Electro-pneumatic (YT-1000) and smart HART (YT-3300) positioning of linear and rotary pneumatic actuators

Where Rotork equipment is used

Rotork actuators are common on oil and gas pipelines and terminals, refineries and gas plants, water and wastewater networks, desalination plants and power stations. Electric IQ actuators handle isolation valves on long pipelines and water mains, often networked over Rotork Pakscan, Modbus or another fieldbus. Skilmatic and scotch yoke actuators cover emergency shutdown valves, and Fairchild regulators and YTC positioners sit on pneumatic control valves throughout process plants.

Ordering Rotork actuators and spare parts: what we need

Send photos of the actuator nameplate with the model, serial number and wiring diagram number; the wiring diagram is usually inside the terminal cover. Rotork can identify the original build, including options and control interface, from the serial number. For a new application add the valve type and size, required torque or thrust, operating time, mounting flange (ISO 5210 or ISO 5211), power supply, control signal or network protocol, fail-safe requirement and hazardous-area marking. For regulators and positioners send the full model code and the pressure or signal ranges.

Facts checked against Rotork plc company information and product data, October 2026.

FAQ

Questions about the Rotork CVL-5000 Heavy-Duty Electric Linear Actuator

Answers from our engineering team on installation, compatibility and integration.

01What force does the Rotork CVL-5000 produce?
Its rated thrust is 5,000 lbf (22,241 N) with a settable minimum of 2,000 lbf (8,869 N), measured with plus or minus 5 percent accuracy by the built-in thrust sensor.
02How long is the stroke of the CVL-5000?
The maximum stroke is 4.5 in (114.3 mm) and the full-stroke time at 100 percent speed is 45 seconds, a speed of 0.1 in/s (2.54 mm/s).
03Can the CVL-5000 run from 24 VDC?
No. The brochure states that the 24 VDC supply option is not available for the CVL-5000; it runs on 100 to 240 VAC, 50 or 60 Hz only.
04What is the weight of the CVL-5000?
The drawing note gives 51 kg without the reserve powerpack and 53 kg with it, so additional lifting provisions are required during installation.
05What bolting does the CVL-5000 use?
The valve interface is MSS SP-102 FA12 and ISO 5210 F12, with four M12 x 1.75 holes 24 mm deep on a 125 mm PCD, tightened to 46 Nm (34 lbf.ft).