Brand: Eaton
Eaton DILM38-10(RDC240) Contactor 38 A 200-240 V DC
Description
Eaton DILM38-10(RDC240) contactor, 38 A AC-3, 200-240 V DC coil
The Eaton DILM38-10(RDC240) (catalog number 112445) is a three-pole DILM contactor from the Moeller range, built for motors up to 18.5 kW at 380/400 V. It is rated 38 A in AC-3 up to 500 V and 45 A in AC-1, and it carries one built-in normally open auxiliary contact. The coil is specified for 200 to 240 V DC (RDC 240), which makes this version the match for control circuits on a 220 V DC battery or rectified supply, found in older power stations and industrial plants with a high-voltage DC auxiliary system. The housing is the FS2 frame, 45 mm wide, 85 mm high and 97 mm deep. Seven Star LLC supplies the DILM38-10(RDC240) in Oman and the GCC.
How to read the model code DILM38-10(RDC240)
The prefix DILM names the contactor series, 38 stands for the 38 A AC-3 rating and 10 for one N/O auxiliary contact with no N/C contact. The bracket defines the coil: RDC marks a DC-operated electronic coil and the number is the nominal voltage band, here 200 to 240 V DC (RDC 240). The power section is identical to the AC-operated DILM38-10 versions, so the bracket is the only part of the code that separates DILM38-10(RDC240) from DILM38-10(RDC60) and DILM38-10(RDC130). The manufacturer sheet describes the unit as a three-pole contactor with screw terminals, DC operation and a 380/400 V motor rating of 18.5 kW.
DILM38-10(RDC240) technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Eaton DILM38-10(RDC240) (catalog number 112445) |
| Series | Eaton Moeller DILM contactor |
| Poles / contacts | 3 main contacts (N/O), 1 N/O auxiliary contact built in |
| Coil / control voltage | 200 to 240 V DC (RDC 240) |
| Pick-up / drop-out voltage | 0.7 – 1.2 × Uc / 0.6 – 0.15 × Uc (DC operated) |
| Coil power at pick-up / sealed | 12 W / 0.9 W |
| Switching time, closing delay (max.) | 47 ms |
| Switching time, opening delay (max.) | 30 ms |
| Rectifier requirement | At least a smoothed two-phase bridge rectifier or a three-phase rectifier |
| Rated operational current AC-3, 220–500 V | 38 A |
| Rated operational current AC-3, 660/690 V | 22.5 A |
| Rated operational power AC-3 at 380/400 V, 50 Hz | 18.5 kW |
| Rated operational power AC-3 at 240 V / 415 V / 440 V / 500 V / 690 V | 12 kW / 20 kW / 21 kW / 24 kW / 21 kW |
| Rated operational current AC-1, 380–415 V | 45 A |
| Rated operational current AC-4, 220–500 V / 660–690 V | 15 A / 12 A |
| Rated breaking capacity at 220–500 V / 660–690 V | 320 A / 180 A |
| Rated making capacity up to 690 V | 384 A |
| Rated insulation voltage Ui / impulse withstand Uimp | 690 V / 8000 V AC |
| Short-circuit protection, type 1 coordination, 400 V / 690 V | 125 A gG/gL / 63 A gG/gL |
| Short-circuit protection, type 2 coordination, 400 V / 690 V | 63 A gG/gL / 35 A gG/gL |
| Heat dissipation per pole (current dependent) / static | 3.1 W / 0.9 W |
| Contact resistance per pole | 2.7 mΩ |
| Frame size / degree of protection | FS2 / IP00 (finger and back-of-hand proof from the front) |
| Ambient temperature, open / enclosed | -25 to 60 °C / -25 to 40 °C |
| Dimensions (depth x height x width) | 97 x 85 x 45 mm |
| Weight | 0.534 kg |
The values above follow the manufacturer specification sheet for catalog number 112445. The sheet lists CE marking and conformity to IEC/EN 60947-4-1, together with UL and CSA recognition data for the DILM38 power section.
What the DILM38-10(RDC240) can switch
In utilisation category AC-3 the sheet gives 38 A at every voltage from 220 V to 500 V and 22.5 A at 660/690 V. The corresponding motor powers are 12 kW at 240 V, 18.5 kW at 380/400 V, 20 kW at 415 V, 21 kW at 440 V, 24 kW at 500 V and 21 kW at 690 V. For heavy starting duty in AC-4 the sheet lists 15 A up to 500 V and 12 A at 660/690 V, equal to 8 kW at 440 V. In AC-1 the contactor carries 45 A at 380 to 415 V, and in DC-1 it is listed at 40 A at 60 V, 110 V and 220 V.
Rated breaking capacity is 320 A up to 500 V and 180 A at 660/690 V, with a making capacity of 384 A. For North American ratings the sheet assigns 10 HP at 200/208 V and 230/240 V three-phase, 20 HP at 460/480 V and 25 HP at 575/600 V.
How the DILM38-10(RDC240) coil works
The DILM38-10(RDC240) is DC operated with an electronic coil for 200 to 240 V DC (RDC 240). It pulls in at 0.7 to 1.2 times the rated control voltage and drops out between 0.6 and 0.15 times, which gives a wide hold range on battery supplies. Pick-up power is 12 W and sealed consumption falls to 0.9 W, so the auxiliary battery is hardly loaded once the contactor is closed. Closing takes up to 47 ms and opening up to 30 ms, slower than the AC versions, which is worth remembering in interlocked reversing circuits.
The sheet states that the DC coil needs at least a smoothed two-phase bridge rectifier or a three-phase rectifier if it is fed from AC. The DILM38-10(RDC240) is intended for control circuits on a 220 V DC battery or rectified supply, found in older power stations and industrial plants with a high-voltage DC auxiliary system. Keep the supply inside the band given for this version and do not mix it up with the other DC bands, since each coil is wound for its own range.
Selection checklist for the DILM38-10(RDC240)
- Confirm the motor nameplate current is 38 A or less at the operating voltage, and 22.5 A or less at 660/690 V.
- Check that the control supply matches 200 to 240 V DC (RDC 240) and, for DC, that the supply type is smooth enough.
- Choose back-up protection: 63 A gG/gL for type 2 coordination and 125 A gG/gL for type 1 at 400 V.
- Plan an overload relay or a motor protective breaker for the 38 A band; a ZB65 type or a PKZM4 breaker are the usual companions.
- Allow for 3.1 W loss per pole at 38 A, plus coil loss, when you calculate the enclosure temperature rise.
Wiring, mounting and service of the DILM38-10(RDC240)
The contactor measures 97 mm deep, 85 mm high and 45 mm wide and weighs 0.534 kg. Main terminals take M5 screws with a tightening torque of 3.2 Nm and accept 1 x 0.75 to 16 mm² or 2 x 0.75 to 10 mm² conductors. The control terminals take M3.5 screws at 1.2 Nm with 0.75 to 4 mm² solid or 0.75 to 2.5 mm² flexible conductors with ferrule, stripped by 10 mm. Use a Pozidriv size 2 or a 1 x 6 mm slotted driver. Wire the coil to A1 and A2, observing polarity on the DC coil.
During service, check that the armature closes cleanly, that terminal screws stay tight after thermal cycling and that the contact faces show no deep pitting. If a unit is replaced, copy the full model code including the coil bracket from the old nameplate so the new part has the same control voltage.
Where the DILM38-10(RDC240) is used in Oman and the GCC
In Oman and the wider Gulf the DILM38-10(RDC240) typically ends up in motor control centres and skid panels for water injection, firewater and transfer pumps, compressors, ventilation fans and crushers in oil and gas, desalination, power and petrochemical sites. It operates at up to 40 °C enclosed and 60 °C in open air, with damp-heat proofing to IEC 60068-2-30 and IEC 60068-2-78, which gives some margin in warm and humid coastal plants. For dusty sites the contactor belongs inside a sealed enclosure because the housing itself is IP00.
DILM38-10 coil variants compared
| Model | Catalog number | Coil |
|---|---|---|
| DILM38-10(42V50HZ,48V60HZ) | 112424 | 42 V 50 Hz / 48 V 60 Hz AC |
| DILM38-10(110V50HZ,120V60HZ) | 112425 | 110 V 50 Hz / 120 V 60 Hz AC |
| DILM38-10(400V50HZ,440V60HZ) | 112430 | 400 V 50 Hz / 440 V 60 Hz AC |
| DILM38-10(RDC60) | 112443 | 48-60 V DC |
| DILM38-10(RDC130) | 112444 | 110-130 V DC |
| DILM38-10(RDC240) | 112445 | 200-240 V DC |
Within the DILM38-10 group the coil is the only difference: the AC versions cover 42/48 V, 110/120 V and 400/440 V, and the RDC versions cover 48-60 V, 110-130 V and 200-240 V DC. The DILM38-10(RDC240) is the 200-240 V DC member.
Information to send with an RFQ for DILM38-10(RDC240)
- Full model code including the coil bracket, or the catalog number from the nameplate.
- Quantity and required delivery point in Oman or the GCC.
- Control voltage, frequency and whether the supply is AC or DC.
- Motor power and voltage, and the starting duty (normal, heavy, reversing).
- Any matching overload relay, auxiliary contact module or mechanical interlock needed.
Documents and quotation
A datasheet for the DILM38-10(RDC240) is attached on this page. It reproduces the manufacturer specification data for catalog number 112445.
Send the model code and quantity and we will reply with availability and lead time for the DILM38-10(RDC240).
Other Models in the Eaton Dilm Contactor Range
Seven Star LLC supplies models from the Eaton Dilm Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
Datasheets & Documents
- Datasheet Eaton DILM38-10(RDC240) Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Eaton is a power management company that began in 1911, when Joseph O. Eaton started a truck axle business in New York and moved it to Cleveland, Ohio, in 1914. It grew from vehicle components into electrical equipment, hydraulics and aerospace systems. Since buying Cooper Industries in 2012, Eaton has been incorporated in Ireland with its head office in Dublin, and it is listed on the New York Stock Exchange.
Seven Star LLC lists Eaton NZM molded case circuit breakers, PKZM0 motor-protective circuit breakers and Bussmann series Class J fuses, and supplies them to panel builders and maintenance teams in Oman and the GCC.
Eaton company profile
| Founded | 1911, New York, USA, by Joseph O. Eaton |
|---|---|
| Early move | Cleveland, Ohio, 1914 |
| Headquarters | Dublin, Ireland, since the 2012 Cooper Industries acquisition |
| Listing | New York Stock Exchange (ETN) |
| Brands | Eaton, Moeller, Bussmann, Crouse-Hinds, MTL and MEDC |
| Product families | FAZ and PL miniature circuit breakers, NZM moulded-case breakers, DILM contactors, PowerXL variable frequency drives, 9PX and 93PM UPS, Bussmann fuses, hazardous-area enclosures and signalling |
Milestones
- 1911: Joseph O. Eaton starts an axle business in New York.
- 1914: The business moves to Cleveland.
- 2012: Eaton acquires Cooper Industries and redomiciles in Ireland.
Eaton circuit protection listed here
The NZMN1-A80 is a frame size 1 molded case circuit breaker rated 80 A with a thermomagnetic release for cable and system protection. The PKZM0-1,6 is a motor-protective circuit breaker whose overload release is adjustable from 1 to 1.6 A, used as a manual motor starter. The LPJ-35SP is a Bussmann series Low-Peak Class J time-delay fuse rated 35 A at 600 V AC. Older NZM and PKZ devices carry the Moeller name on the nameplate, and the type designations are the same.
Where Eaton breakers and fuses are used
Motor control centers, feeder panels, machine control cabinets and UL-style fused disconnects.
Eaton products we list
Ordering Eaton parts: what we need
Send the full type and article number, the number of poles, the current rating or setting range, and any accessories such as auxiliary contacts, trip releases or rotary handles.
Facts checked against Eaton's corporate history and investor materials, October 2026.
Browse Eaton products by category: Circuit Breaker.
FAQ
Questions about the Eaton DILM38-10(RDC240) Contactor 38 A 200-240 V DC
Answers from our engineering team on installation, compatibility and integration.
01What is the AC-3 rating of the DILM38-10(RDC240)?
The sheet lists 38 A at 220 to 500 V and 22.5 A at 660/690 V, which equals 18.5 kW at 380/400 V and 24 kW at 500 V.
02Which coil is fitted to the DILM38-10(RDC240)?
A coil for 200 to 240 V DC (RDC 240). It pulls in at 0.7 to 1.2 times the rated voltage and drops out between 0.6 and 0.15 times.
03How much power does the DILM38-10(RDC240) coil draw?
The sheet gives 12 W at pick-up and 0.9 W sealed, and it requires a smoothed bridge or three-phase rectifier when fed from AC.
04What breaking capacity does the DILM38-10(RDC240) have?
Rated breaking capacity is 320 A up to 500 V and 180 A at 660/690 V, with a rated making capacity of 384 A up to 690 V.
05Which fuse is recommended with the DILM38-10(RDC240)?
At 400 V the sheet gives 63 A gG/gL for type 2 coordination and 125 A gG/gL for type 1. At 690 V the values are 35 A and 63 A gG/gL respectively.