Omron G9SA-501 Safety Relay 5-pole emergency-stop
Description
G9SA-501 safety relay unit: what it is and how the code reads
The Omron Omron G9SA-501 is a emergency-stop safety relay unit with five poles from the G9SA series, with 5 safety contacts (5PST-NO) plus 1 auxiliary NC contact. A master unit with five safety outputs, for machines that need to disconnect more than three power circuits from one stop signal. Seven Star LLC supplies the Omron G9SA-501 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
Reading the code:
- G9SA is the safety relay unit family.
- 501 identifies the function and contact arrangement: 5 safety contacts (5PST-NO) plus 1 auxiliary NC contact.
- The power supply voltage must be specified when ordering: 24 VAC/VDC or 100 to 240 VAC.
- A T suffix, where present, gives the maximum OFF-delay time.
It carries five safety poles in the same 45 mm wide housing, which saves an expansion unit when a machine has several contactors to drop out.
Omron G9SA-501 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Omron / G9SA-501 |
| Type | emergency-stop safety relay unit with five poles |
| Contacts | 5 safety contacts (5PST-NO) plus 1 auxiliary NC contact |
| Supply options | 24 VAC/VDC or 100 to 240 VAC (specify on order) |
| Operating voltage range | 85% to 110% of rated supply |
| Power consumption (24 VAC/VDC) | 7.4 VA/2.6 W max. |
| Power consumption (100 to 240 VAC) | 11 VA max. |
| Input current | 60 mA max. |
| Contact rating | 250 VAC, 5 A or 30 VDC, 5 A resistive; carry current 5 A |
| Operating time | 30 ms max. |
| Response time | 10 ms max. |
| Mechanical life | 5,000,000 operations min. |
| Electrical life | 100,000 operations min. |
| Ambient operating temperature | −25 to 55°C, no icing or condensation |
| Humidity | 35% to 85% |
| Terminal tightening torque | 0.6 N·m |
| Weight | Approx. 270 g (24 VAC/VDC) |
Values are from the manufacturer G9SA datasheet; for 100 to 240 VAC types add about 20 g to the weight. Where the datasheet gives a combined column for several models, the figure shown applies to this model.
How the G9SA-501 works
A safety relay unit monitors the stop circuit with redundant channels. Internally there are two forced-guided relays, and the control circuit only allows the outputs to turn on when both channels agree and the reset condition is met. If either relay welds or a wire shorts, the unit does not re-enable the outputs.
Reset mode is set on terminals A and B: open gives manual reset, and closed gives auto-reset. Inputs may be one-channel or two-channel on the emergency-stop types, and two-channel on the two-hand controller. The datasheet notes that G9SA units can be used to PLe and category 4 depending on the circuit, but the actual performance level must be evaluated for each application by the system designer.
Contacts are positive-guided, so you can monitor them with the auxiliary NC output or feed the contactor feedback into the reset circuit.
Where the G9SA-501 fits and related part numbers
The G9SA family combines masters and expansion units: masters are G9SA-301 (3 poles), G9SA-501 (5 poles), G9SA-321-T (3 poles plus 2 delayed) and G9SA-TH301 (two-hand), and expansion units are G9SA-EX301 and G9SA-EX031-T. Neighbours of the G9SA-501 are G9SA-301, G9SA-321-T15, G9SA-EX301.
Typical companions include emergency-stop pushbuttons, safety limit switches such as the D4N series, light curtains with relay outputs, and external contactors with positively guided contacts. The unit mounts on DIN rail or by screws.
Selection and ordering checklist for G9SA-501
- Confirm the function: emergency-stop safety relay unit with five poles.
- Count the safety outputs you need and whether a delay is required.
- Specify 24 VAC/VDC or 100 to 240 VAC supply.
- Check the 5 A, 250 VAC contact rating against the contactor coil or load.
- Decide on manual or auto reset.
- Confirm the required performance level and check that the application circuit meets it.
- Plan expansion units if outputs may increase later.
Installation, commissioning and maintenance of the G9SA-501
Mount on a DIN rail inside a control panel with spacing as the datasheet advises when several units are placed side by side. Wire the supply to A1 and A2; with 24 VAC/VDC types A2 is the negative pole. Tighten terminals to 0.6 N·m and connect PE to protective ground on 100 to 240 VAC types.
Test the full safety function before release: operate each stop device in turn, verify outputs drop out within the response time, and confirm that the unit does not restart after a reset unless the inputs are healthy. Record the results in the machine validation file.
Maintenance consists of periodic functional tests according to the machine risk assessment, checking terminals and contactor feedback wiring, and replacing the unit after the contacts reach their rated life.
Typical applications in Oman and the GCC
Safety relays are found in the control panels of pump stations, compressor skids, packaging lines and fabrication machinery across Oman and the GCC. Panels are often in hot and dusty environments, so ventilate enclosures to keep the internal temperature within the 55°C operating limit of the G9SA-501.
- Emergency-stop with several contactors, for example motors and heaters on a processing line.
- Guarding of a robotic or packaging cell where several actuators must be isolated.
- Replacing a G9SA-301 plus expansion with a single housing.
G9SA family comparison
| Model | Function | Contacts | OFF-delay | Weight (24 V) |
|---|---|---|---|---|
| G9SA-301 | Master | 3 NO + 1 NC | None | 210 g |
| G9SA-501 | Master | 5 NO + 1 NC | None | 270 g |
| G9SA-321-T15 | Master with OFF-delay | 3 NO + 2 NO delayed + 1 NC | 1 to 15 s | 270 g |
| G9SA-EX301 | Expansion | 3 NO + 1 NC | None | 130 g |
| G9SA-TH301 | Two-hand controller | 3 NO + 1 NC | None | 210 g |
The G9SA-501 row shows how it compares with the rest of the series.
Information to send with an RFQ for G9SA-501
- Full part number G9SA-501, supply voltage and quantity.
- Number and type of stop devices.
- Required performance level and stopping category.
- Loads to be switched and their ratings.
- Reset mode requirements.
- Any expansion units required.
Documents and quotation
The manufacturer datasheet for the G9SA series is attached on this page, including wiring diagrams and application examples for G9SA-501.
Send the part number, supply voltage, quantity and delivery location and Seven Star LLC will confirm availability. We are an independent supplier and not affiliated with the manufacturer.
Other Models in the Omron G9sa Safety Relays Range
Seven Star LLC supplies models from the Omron G9sa Safety Relays range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Omron G9SA-301 Safety Relay 3-pole emergency-stop | Safety Switches & Guard Locking | View details |
| Omron G9SA-501 Safety Relay 5-pole emergency-stop | Safety Switches & Guard Locking | You are viewing this model |
Datasheets & Documents
- Datasheet Omron G9SA-501 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Omron is a Japanese electronics and automation company, founded in 1933 in Osaka by Kazuma Tateisi and now headquartered in Kyoto. Its industrial automation business makes PLCs, I/O, sensors, relays, safety components, motion control and robots. Omron's CJ and NX series controllers and I/O units are widely used in machine building.
Seven Star LLC lists Omron PLC input and output units from the CJ and NX series and supplies them to panel builders and maintenance teams in Oman.
Omron company profile
| Founded | 1933, Osaka, Japan |
|---|---|
| Founder | Kazuma Tateisi |
| Headquarters | Kyoto, Japan |
| Business | Industrial automation, healthcare, electronic components |
| Product families | CJ1/CJ2 PLCs and I/O units, NX and NJ controllers, NX I/O, E2E proximity sensors, G2R and MY relays |
Omron CJ-series and NX-series units listed here
Three I/O units are on this page. The CJ1W-ID211 is a CJ-series 16-point 24 VDC input unit and the CJ1W-OC211 is a CJ-series 16-point relay output unit. The NX-ID5442 is an NX-series 16-point 24 VDC digital input unit for PNP wiring, 12 mm wide with push-in terminals. CJ and NX units belong to different hardware platforms and do not plug into each other's racks.
Omron products we list
| Family | Examples |
|---|---|
| PLC & I/O Cards | CJ1W-ID211 CJ-Series 16-Point 24 VDC Inp…, CJ1W-OC211 CJ-Series 16-Point Relay Outp…, NX-ID5442 NX-Series 16-Point Digital Inp… |
Ordering Omron PLC modules: what we need
Send the complete model number from the front or side label of the unit, including every suffix. If you are replacing a failed card, add the CPU or coupler model it is mounted with, and tell us if the terminal block or connector is needed as well. For obsolete Omron PLC parts we check which successor the manufacturer documents. Requests from other GCC countries are handled the same way.
Facts checked against Omron's published company history, October 2026.
FAQ
Questions about the Omron G9SA-501 Safety Relay 5-pole emergency-stop
Answers from our engineering team on installation, compatibility and integration.
01What contacts does the G9SA-501 provide?
It provides 5 safety contacts (5PST-NO) plus 1 auxiliary NC contact. Contacts are rated 250 VAC 5 A or 30 VDC 5 A on a resistive load, with a carry current of 5 A.
02Which supply voltages are available for the G9SA-501?
The datasheet lists 24 VAC/VDC and 100 to 240 VAC versions, and the supply voltage must be specified when ordering. The operating range is 85% to 110% of the rated supply.
03How fast does the G9SA-501 switch off?
The datasheet response time is 10 ms maximum from input off to main contact opening, and the operating time is 30 ms maximum. OFF-delay models add the delay set on their switch.
04How is manual or auto reset selected on the G9SA-501?
Reset is chosen on terminals A and B: open gives manual reset and closed gives auto-reset. Use manual reset wherever a restart must be a deliberate operator action.
05Can the G9SA-501 be used for PLe, category 4?
The datasheet states that G9SA units can be applied to PLe and category 4 with the appropriate circuit, with some model exceptions. The performance level must be assessed for your specific application and wiring.