- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- Motor Soft Starters
- HMI Displays
- Pneumatic Cylinders
- Isolator & Barrier
- Automation Software
- Machine Vision
- Robotics
Brand: Extech
Extech PQ3450 3-Phase Power Analyzer and Datalogger
Description
PQ3450 is the Extech portable three-phase power analyzer and datalogger. It measures voltage up to 600 V, current through user-selectable clamp inputs, and up to 35 parameters including kW, kVA, kVAR, power factor, frequency, phase angle and energy, and it saves readings to an SD card in spreadsheet-ready format. Current clamps are sold separately.
A portable power survey tool for panels and feeders
Energy audits and load studies need a meter that can be clamped onto a live feeder without opening cables. The PQ3450 supports 1P/2W, 1P/3W, 3P/3W and 3P/4W configurations, shows phase and system values on a 320 x 240 pixel backlit dot-matrix display, and lets the CT ratio (1 to 600) and PT ratio (1 to 1000) be entered so that readings can refer to the primary side of larger distribution systems.
The datalogger stores up to 30,000 readings per file on a removable SD card at a sampling rate from 2 seconds to 2 hours (7200 seconds in the manual). A built-in clock and calendar time-stamp the data, and the manual describes an RS232 port for connection to a PC.
Features stated in the datasheet and manual
- Voltage 10 to 600 V AC auto-ranging; true RMS; safety rating IEC1010 CAT III 600 V.
- Universal clamp input: 200 mV to 3 V output clamps, user-selectable, with current ranges from 20 A to 6000 A as listed in the manual.
- Active, apparent and reactive power and energy (MWH, MVAH, MVARH) readouts.
- Complete with four voltage leads with alligator clips, eight AA batteries, SD card, universal AC adaptor (100 to 240 V) and case.
Technical specification
Electrical specification (datasheet and manual)
| Parameter | Specification |
|---|---|
| AC voltage | 10.0 to 600.0 V, 0.1 V resolution; ± (0.5 % + 0.5 V + 5 digits); input impedance 10 Mohm |
| AC current (meter only) | 20.0 A: ± (0.5 % + 0.1 A + 5 digits); 20.01 to 200.0 A: ± (0.5 % + 0.5 A + 5 digits); above 200.0 A: ± (0.5 % + 5 A + 5 digits); add the clamp accuracy |
| Power factor | 0.00 to 1.00; ± 0.04 |
| Phase angle | -180 to 180 degrees; ± 1 degree |
| Frequency | 45 to 65 Hz; ± 0.1 Hz |
| Power (kW, kVA, kVAR) | 0.0 to 3.6 MW range in the manual (datasheet 9.999 MW); ± (1 % + 8 digits) |
| Energy (MWH, MVAH, MVARH) | 0.0 to 3.6 MWH in the manual; ± (1 % + 8 digits); datasheet quotes ± 2 % of reading |
| Overload protection | 720 V AC RMS on the voltage input |
General specification
| Parameter | Specification |
|---|---|
| Display | 3.2 x 2.4 in (81.4 x 61 mm) backlit dot-matrix LCD, 320 x 240 pixels |
| Clamp frequency response | 40 Hz to 1 kHz |
| Data recording | SD card up to 2 GB (SDHC up to 16 GB per manual); 30,000 records maximum per file |
| Sampling rate | 2 to 7200 seconds |
| Power supply | Eight AA 1.5 V batteries or 9 V AC adaptor; 250 mA consumption |
| Operating conditions | 0 to 50 C (32 to 122 F); 80 % RH maximum |
| Dimensions and weight | 225 x 125 x 64 mm (8.86 x 4.92 x 2.52 in); 1010 g with batteries |
| Available kits | PQ3450-2 (200 A clamps), PQ3450-12 (1200 A clamps), PQ3450-30 (3000 A flexible probes) |
Choosing the clamp set
The meter is ordered as PQ3450; clamp sets are PQ34-2 (200 A current clamp probes, set of 3), PQ34-12 (1200 A clamps, set of 3) and PQ34-30 (3000 A flexible current probes, 24 in / 600 mm, set of 3), and PQ1000 is a set of four voltage test leads. Kits PQ3450-2, PQ3450-12 and PQ3450-30 combine the meter with each clamp set.
Choose the clamp rating from the feeder current: the 200 A and 1200 A jaws open 0.8 in (19 mm) and 2 in (50 mm), while the flexible probe wraps around busbars. Add the clamp accuracy to the meter accuracy to estimate system accuracy.
Connection and safety notes
Connect the four voltage leads and the three clamps according to the selected wiring system, and set the clamp ratio in the menu to match the probe in use. The manual states that voltage inputs are limited to 600 V CAT III and that overloads above 720 V AC RMS are shown as OL.
Only trained personnel should connect to live panels, and the meter should be used with insulating gloves, rated probes and a lock-out procedure as required by site rules.
Typical uses in industrial and building plants
General engineering note: a portable analyzer is used to check motor loads before and after maintenance, balance single-phase loads, verify power factor correction and run week-long load profiles on chiller, pump and compressor feeders before a retrofit or a capacity study. The SD card data opens directly in a spreadsheet for charting.
Related Extech items
For clamp-on current and voltage spot checks see the MA445 AC/DC clamp meter, and for insulation condition the MG500. See the portable test and measurement category.
Field use and calibration notes
Select the current clamps to match the conductor sizes and current ranges in the panels to be surveyed. Follow the safety instructions and wear suitable protective equipment when connecting to live panels. Arrange calibration at regular intervals.
Information to send with an enquiry
- Current clamps needed
- Quantity
Frequently asked questions
Are current clamps included with the PQ3450?
No. The datasheet states that clamp probes are sold separately; PQ3450 kits with 200 A, 1200 A or 3000 A probes are also listed.
What parameters does it measure?
Up to 35 parameters including phase and system kW, kVA, kVAR, power factor, kWh, kVAh, kVARh, frequency, phase angle, voltage and current.
How does it log data?
Readings are saved to an SD card in a spreadsheet format at sampling intervals from 2 seconds upward, with up to 30,000 records per file.
What wiring systems are supported?
1P/2W, 1P/3W, 3P/3W and 3P/4W, with adjustable CT (1 to 600) and PT (1 to 1000) ratios.
Is Seven Star LLC an Extech distributor?
No, we are an independent supplier in Muscat and supply Extech items on request rather than acting for Extech.
Documents and quotation
For quotation, send your required quantity and destination. The Extech datasheet and user manual for PQ3450 are provided below the description on this page. Seven Star LLC works as an independent supplier from Muscat. Please compare code, ratings and options with the documents before you place an order; see also the category listing.
Datasheets & Documents
Reviews (0)
How would you rate this product? Cancel reply
About brand
Extech Instruments is an American brand of handheld test and measurement instruments, founded in the early 1970s in Waltham, Massachusetts. FLIR Systems acquired Extech in 2007 for about $40 million, and FLIR itself became part of Teledyne in 2021. Extech is based in Nashua, New Hampshire, and makes meters for electrical, environmental and HVAC testing.
Extech company profile
| Founded | Early 1970s, Waltham, Massachusetts |
|---|---|
| Headquarters | Nashua, New Hampshire (since 2011) |
| Ownership | Teledyne FLIR |
| Acquired by FLIR | 2007 |
| Product families | True RMS clamp meters and multimeters, insulation testers, power analysers, IR thermometers, light meters, vibration meters, sound, humidity and air quality meters |
Milestones
- 2007: FLIR Systems acquires Extech.
- 2011: Extech moves to Nashua.
- 2021: FLIR becomes part of Teledyne.
Meters, testers and inspection tools
The Extech range includes multimeters and clamp meters, insulation and resistance testers, power analyzers, thermometers, light and sound level meters, anemometers, tachometers, vibration meters, moisture meters, borescopes and water quality meters. Each datasheet and user manual lists ranges, accuracy, safety category and ordering codes, and many models are listed with NIST-traceable calibration versions ordered by adding -NIST to the part number.
Supply through Seven Star LLC
Seven Star LLC is an independent supplier in Muscat that quotes Extech products for projects in Oman and the GCC, with the official Extech datasheet and user manual attached to each product page.
Extech products we list
Facts checked against FLIR's 2007 announcement and published Extech histories, October 2026.
Related products
Frequently Asked Questions
No. The datasheet states that clamp probes are sold separately; PQ3450 kits with 200 A, 1200 A or 3000 A probes are also listed.
Up to 35 parameters including phase and system kW, kVA, kVAR, power factor, kWh, kVAh, kVARh, frequency, phase angle, voltage and current.
Readings are saved to an SD card in a spreadsheet format at sampling intervals from 2 seconds upward, with up to 30,000 records per file.
1P/2W, 1P/3W, 3P/3W and 3P/4W, with adjustable CT (1 to 600) and PT (1 to 1000) ratios.
No, we are an independent supplier in Muscat and supply Extech items on request rather than acting for Extech.