Accuenergy Acuvim 3 Class A Power Quality Meter
Description
Acuvim 3 is the Accuenergy flagship power quality and revenue meter. It is compliant with IEC 61000-4-30 class A (third-party certified by NMi, per the datasheet), measures active energy to IEC 62053-22 class 0.1s and ANSI C12.20 class 0.1, samples at 1024 samples per cycle and detects harmonics up to the 127th order.
Class A analysis, synchrophasors and billing in one device
Voltage and current RMS are updated every half cycle. The meter captures waveforms of up to 512 samples per cycle in COMTRADE format with up to 60 cycles before and 300 cycles after an event, analyses transient voltage at 32,000 samples per second, and produces EN 50160, IEEE 519 and ITIC/CBEMA reports.
It also provides IEEE C37.118 synchrophasor output with configurable frame rates, frequency and ROCOF detection, and time synchronisation from IRIG-B, NTP, SNTP and PTP. Time-of-use metering supports 8 tariffs and 12 previous billing periods.
Features stated in the datasheet
- 32 GB data logger with up to 15 configurable data loggers and data post by HTTP/FTP.
- IEC 61000-4-15 class F1 flicker; frequency 40 to 70 Hz at 1 mHz.
- Dual Ethernet port, RS485, IRIG-B, four digital I/O and USB-C; optional Wi-Fi (2.4 GHz), NW non-Wi-Fi model available.
- Optional 7-inch colour touch-screen remote display (ACUVIM-3-REM-DISP).
Technical specification
Metering (datasheet)
| Parameter | Specification |
|---|---|
| Voltage | 0.1 %; 0.001 V; VLN 10 – 400 V, VLL 17.3 – 690 V; half-cycle update |
| Current | 0.1 %; 0.001 A; 1 A: 10 mA – 2 A, 5 A: 50 mA – 10 A, 333 mV and Rogowski: 3 – 400 mV |
| Power | 0.1 %; 1 W; class 0.1 IEC 61557-12 |
| Frequency | 0.001 %; 0.001 Hz; 40 – 70 Hz; class 0.02 IEC 61557-12 |
| Energy | 0.1 %; 0.001 Wh; class 0.1s IEC 62053-22, 0.1 ANSI C12.20; reactive class 0.5s |
| Harmonics, unbalance | 0.15 %; harmonics to 127th; flicker Pst 5 % |
| Power quality standard | IEC 61000-4-30 class A; flicker IEC 61000-4-15 F1 |
Inputs, communication and environment
| Parameter | Specification |
|---|---|
| Current inputs | 5 A, 1 A, 333 mV, Rogowski coil; withstand 20 A continuous, 50 A for 10 s per hour, 500 A for 1 s per hour; burden 0.05 VA at 5 A |
| Voltage inputs | 400 Vac L-N, 690 Vac L-L (+20 %); 2 Mohm per phase; withstand 1500 Vac continuous |
| Control power | P1: 100 – 415 Vac 50/60 Hz or 100 – 300 Vdc, 15 W / 25 VA; P2: 20 – 60 Vdc |
| Communication protocols | Modbus RTU 9600 – 115200 bps; Modbus TCP/IP; DNP3 over IP; IEC 61850 1st and 2nd Ed.; PMU C37.118; SNMP V2c/V3; BACnet/IP; EtherNet/IP; MQTT; HTTP/HTTPS, FTP, sFTP, SMTP |
| Time synchronisation | NTP, SNTP, IRIG-B, PTP |
| I/O modules | AXM-IO1 to IO4: digital in, relay, photo-MOS out, analogue in/out, residual current (RCM) and RTD inputs; up to three external modules |
| Operating / storage temperature | -25 to 70 C / -40 to 70 C; humidity 5 – 95 %; altitude below 3000 m; indoor use |
| Protection | IP54 panel front and touchscreen; IP30 rear, DIN rail and I/O modules |
| Safety and standards | IEC/UL 61010-1 and 61010-2-030, CAT III; CISPR 32 class B; IEC 61000-6-5; BTL listed for B-SA |
Order code
Order as Meter Model – Mounting Option – Current Input – Power Supply – Canada Application – NW. Mounting D is panel mount with LCD, M is DIN rail without LCD; current input is 5A (5 A / 1 A) or mV (333 mV and Rogowski); power supply P1 (AC/DC) or P2 (20 – 60 Vdc); MC marks Measurement Canada and NW the non-Wi-Fi version. Examples: Acuvim-3-M-5A-P1-NW and Acuvim-3-D-5A-P2-MC.
Per the datasheet note, Measurement Canada certified meters do not support the millivolt current input option.
Installation notes
The meter mounts on a DIN rail or in a panel. Up to three external AXM I/O modules can be attached, with no more than two of the same kind, each given a different logic number in the meter configuration.
Because class A compliance depends on correct CT and VT settings, record the CT ratio, connection type and nominal frequency at commissioning.
Applications
The datasheet lists SCADA, industrial automation, power quality, UPS systems, critical infrastructure, data centres, telecom, manufacturing, substations, healthcare, DER and microgrids, auxiliary frequency response services and EPSS testing. General engineering note: for Gulf utilities and large industrial sites, the EN 50160 and IEEE 519 reports can support power quality acceptance checks.
Related Accuenergy items
The Acuvim II offers class 0.1s metering with modular expansion at a simpler level, and the AcuRev 1320 is a class S DIN-rail alternative. See the power meters category.
Commissioning and enquiry notes
Class A power quality meters are installed in the region at substations, utility supply points of large plants, data centres and hospitals, and on feeders to large drive loads, where harmonics, voltage dips and transients must be recorded to a recognised method. Set the wiring mode, CT and PT ratios and the nominal values at commissioning, and synchronise the time source so events can be compared with protection relay and utility records. Oman’s networks run at 50 Hz. Check the panel’s internal temperature in summer.
Information to send with an enquiry
- Nominal voltage, CT and PT ratios
- Options and communication required
- Quantity and software needs
Related Accuenergy products: Accuenergy Acuvim II Advanced Power and Energy Meter, Accuenergy AcuRev 1320 Class 0.1S DIN Rail Energy Meter, Accuenergy AcuRev 1310 DIN Rail Power and Energy Meter, Accuenergy AcuDC 243 DC Power and Energy Meter, 1000 Vdc, Accuenergy AcuDC-262 Dual-Channel DC Power and Energy Meter and Accuenergy AcuDC-301 EV Charging DC Energy Meter, 650 A.
Documents and quotation
This page carries the official Accuenergy datasheet and manual for Acuvim 3. Seven Star LLC is an independent supplier in Muscat and sources Accuenergy products on request; tell us the quantity and delivery point to receive a quotation. Always confirm the order code and technical values in the documents first. See more in the product category.
Datasheets & Documents
- Datasheet Accuenergy Acuvim 3 Advanced Power Quality Meter datasheet, version 1.0.14 (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Accuenergy is a Canadian manufacturer of power and energy meters, founded in 1998 and headquartered in Toronto, with offices in Los Angeles, Beijing and Pretoria. Its first multifunction meter line, Acuvim, reached the global market in 2003. Accuenergy makes AC and DC power meters, multi-circuit submeters, current sensors and communication gateways.
Accuenergy company profile
| Founded | 1998, Toronto, Canada |
|---|---|
| Headquarters | Toronto, Canada |
| Offices | Los Angeles, Beijing and Pretoria |
| First product line | Acuvim multifunction meters, 2003 |
| Product families | Acuvim power meters, AcuRev DIN-rail and multi-circuit submeters, AcuDC DC power and energy meters, split-core and Rope CTs, AcuLink gateways |
Milestones
- 1998: Accuenergy is founded in Toronto.
- 2003: Acuvim meters reach the global market.
Power meters, DC meters and submeters
The Accuenergy range covers Acuvim multifunction and power quality meters, AcuRev DIN rail meters and multi-circuit submeters, AcuDC meters for DC systems and EV charging, plus current transformers, Rogowski coils and communication modules. Each datasheet lists accuracy classes, inputs, communication options and ordering codes. Accuenergy states that its operations hold ISO 9001, ISO 14001 and ISO 45001 certification and that its management systems are certified to ISO 27001 and ISO 50001.
Supply through Seven Star LLC
Seven Star LLC is an independent supplier in Muscat that quotes Accuenergy products for projects in Oman and the GCC, with the official Accuenergy datasheet attached to each product page.
Accuenergy products we list
Facts checked against Accuenergy's own about page (accuenergy.com), October 2026.
FAQ
Questions about the Accuenergy Acuvim 3 Class A Power Quality Meter
Answers from our engineering team on installation, compatibility and integration.
01Is Acuvim 3 a class A power quality meter?
Yes. The datasheet states compliance to IEC 61000-4-30 class A, third-party certified by NMi.
02How high are harmonics measured?
Up to the 127th harmonic, with inter-harmonics, and the meter also gives TDD, K factor and flicker.
03What time synchronisation is supported?
IRIG-B, NTP, SNTP and PTP.
04Can it output synchrophasors?
Yes, IEEE C37.118 synchrophasors at 10 to 60 frames per second depending on 50 or 60 Hz.
05Is Seven Star LLC an Accuenergy distributor?
No. Seven Star LLC is not an Accuenergy distributor; it is an independent Muscat-based supplier that quotes Accuenergy products on request.