Raychem 5BTV2-CR Self-Regulating Heating Cable, 200-277 V
Description
5BTV2-CR is the 5 W/ft class, 200-277 Vac version of the Raychem BTV self-regulating heating cable with the flame-retardant modified polyolefin outer jacket (-CR). It is a cut-to-length parallel heating cable for low-temperature process maintenance and freeze protection on metal and plastic pipes, and the datasheet lists it under part number 414809-000.
A cut-to-length heating cable for maintaining pipes up to 65 C
Reading the code from the datasheet: 5 is the nominal power rating class, BTV is the cable family, 2 is the supply-voltage group (BTV1 100-130 Vac, BTV2 200-277 Vac) and -CR is the flame-retardant modified polyolefin outer jacket. The -CT alternative has a fluoropolymer jacket for organic chemicals and corrosives.
Inside, a self-regulating conductive core sits between two nickel-plated copper bus wires. As the pipe warms, the core raises its electrical resistance and the cable output falls; as the pipe cools, output rises again. A tinned-copper braid under the outer jacket provides the grounded metallic covering.
Features stated in the datasheet
- Maintain or continuous exposure up to 150 F (65 C) power on or off; intermittent exposure to 185 F (85 C) with a 1000 hour cumulative limit.
- Configured for nonhazardous and hazardous locations, including corrosive atmospheres when the correct jacket is used.
- Suitable for metal and plastic traced surfaces.
Technical specification
Specification of 5BTV2-CR
| Parameter | Specification |
|---|---|
| Cable family and code | BTV, 5 W class, BTV2 voltage group, -CR jacket (5BTV2-CR) |
| Part number (datasheet) | 414809-000; the -CT version 5BTV2-CT is 487509-000 |
| Supply voltage | 200-277 Vac (BTV2 group) |
| Maximum maintain or continuous exposure temperature | 150 F (65 C), power on or off |
| Maximum intermittent exposure temperature | 185 F (85 C), power on or off; maximum cumulative exposure 1000 hours |
| Temperature classification | T6: 185 F (85 C) |
| Minimum installation temperature | -76 F (-60 C) |
| Bus wire size | 16 AWG |
| Outer jacket | Modified polyolefin (-CR), colour black |
| Dimensions (3BTV and 5BTV) | 0.413 x 0.217 in (10.5 x 5.5 mm), width x thickness, nominal |
| Weight (3BTV and 5BTV) | 74 lbs per 1000 ft (110 g/m) |
| Power output adjustment factors for 5BTV2 | At 208 V: power 0.91, circuit length 0.94; at 277 V: power 1.08, circuit length 1.09 |
| IECEx / ATEX type marking, -CR | IECEx BAS 20.0011X: Ex 60079-30-1 eb IIC T6 Gb, also eb mb IIC T6 Gb; IEx 09.0004X (as printed) |
| Class and division, -CR | Class I Div. 2 Groups A, B, C, D; Class II Div. 2 Groups F, G; Class III (as printed) |
Maximum circuit length of 5BTV-CR at 240 V, 20 A breaker (metres derived, feet divided by 3.28)
| Parameter | Specification |
|---|---|
| Start-up 50 F / 0 F / -20 F / -40 F | 540 / 380 / 330 / 295 ft (about 165 / 116 / 101 / 90 m) |
Choosing between the BTV ratings, voltages and jackets
The datasheet offers 3, 5, 8 and 10 W classes at both 120 V and 240 V in both jackets, which gives eight 240 V orderable codes: 3BTV2-CR 914279-000, 5BTV2-CR 414809-000, 8BTV2-CR 479821-000, 10BTV2-CR 677245-000, and the same four with -CT (469145-000, 487509-000, 008633-000, 567513-000). Pick the rating from a heat-loss calculation with TraceCalc Pro or Design Guide H56882.
Note how the circuit length shrinks as the output class rises: at 240 V and a 20 A breaker, 3BTV runs 530 ft at start-up of 0 F while 5BTV runs 380 ft and 10BTV only 215 ft (datasheet values).
Installation and commissioning points from the maintenance manual
The installation manual H57274 asks for the cable to be strapped with GT-66 or GS-54 glass tape (or AT-180 aluminium tape on plastic pipes) at about every foot, ideally at the 4 and 8 o clock positions, with extra cable looped at valves, flanges and supports. Metal pipe straps and tie wire are not allowed; minimum bend radius is half an inch.
Run an insulation resistance test with a megohmmeter at 500, 1000 and 2500 Vdc between bus wires and braid and between braid and pipe; every reading should exceed 1000 megohms. Each branch circuit needs ground-fault equipment protection, and every power connection, splice and end seal must use Raychem connection kits.
Where a 65 C maintain cable fits in Gulf plants and buildings
General engineering note: in Oman and the wider Gulf, freeze protection is limited to cold stores, chilled and refrigerated lines and high-altitude or desert-night exposure, so most BTV demand is process temperature maintenance. Typical uses are keeping caustic, glycol and water-based chemical lines above the temperature at which they thicken or crystallise.
The 65 C ceiling is a hard design limit: hotter lines belong with QTVR, XTVR, HTV or VPL cables.
Related Raychem items
Cable families that take over above 65 C are the QTVR (110 C maintain), XTVR (150 C) and HTV (205 C) self-regulating cables and the VPL power-limiting cable. Control can be done with an Elexant 4010i, Elexant 3500i or a Raystat controller, and the heating-cable compatibility list on the 3500i datasheet names BTV-CR and BTV-CT.
Frequently asked questions
What does the 5 in 5BTV2-CR mean?
It is the nominal power rating class of the cable; 3, 5, 8 and 10 classes are listed in the datasheet. The actual output depends on pipe temperature and voltage.
What voltage does 5BTV2-CR run on?
It belongs to the BTV2 group for 200-277 Vac. BTV1 is the 100-130 Vac group. Output and circuit length change at 208 V and 277 V by the adjustment factors printed.
What is the maximum maintain temperature?
150 F (65 C) with power on or off, and intermittent exposure to 185 F (85 C) for up to 1000 cumulative hours.
Can the cable be used on plastic pipes?
The datasheet lists metal and plastic traced surfaces. For aluminium tape and design details on plastic, follow the installation manual and TraceCalc Pro.
Is Seven Star LLC a Raychem distributor?
No. Seven Star LLC is an independent supplier in Muscat that sources Raychem products on request.
Documents and quotation
The official Raychem datasheet and user manual for 5BTV2-CR are hosted on this page for download. Seven Star LLC is an independent supplier in Muscat; send your quantity and delivery location through the quotation form and we will quote this item. Please confirm the exact order code, supply voltage and output options against the documents before ordering. More related products: product category.
Datasheets & Documents
- Datasheet Raychem BTV self-regulating heating cables datasheet RAYCHEM-DS-H51086-BTV-EN-2504 (EN, PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Raychem is the electric heat-tracing brand of Chemelex, a company that describes itself as a global leader in electric thermal and sensing solutions with over 50 years of innovation. Raychem heat-tracing solutions cover industrial, commercial and residential applications, from frost protection of water pipes to maintenance of high temperatures in energy transition applications.
Heating cables, controllers and skin-effect systems
The industrial range includes BTV, QTVR, XTVR and HTV self-regulating heating cables, VPL power-limiting cable, STS skin-effect tracing wire for long pipelines, hot water temperature maintenance cable (HWAT) and the Elexant and RAYSTAT controllers for control, monitoring and ground-fault protection. Each datasheet lists the maximum maintain temperature, circuit lengths, approvals and ordering codes.
Supply through Seven Star LLC
Seven Star LLC is an independent supplier in Muscat that quotes Raychem products for projects in Oman and the GCC, with the official Raychem datasheet attached to each product page.
Related products
Frequently Asked Questions
It is the nominal power rating class of the cable; 3, 5, 8 and 10 classes are listed in the datasheet. The actual output depends on pipe temperature and voltage.
It belongs to the BTV2 group for 200-277 Vac. BTV1 is the 100-130 Vac group. Output and circuit length change at 208 V and 277 V by the adjustment factors printed.
150 F (65 C) with power on or off, and intermittent exposure to 185 F (85 C) for up to 1000 cumulative hours.
The datasheet lists metal and plastic traced surfaces. For aluminium tape and design details on plastic, follow the installation manual and TraceCalc Pro.
No. Seven Star LLC is an independent supplier in Muscat that sources Raychem products on request.