Brand: Lovato Electric
Lovato DCRG8F Dynamic Power Factor Controller, 8 Static Steps
Description
Power factor control for capacitor banks
The DCRG8F is a dynamic power factor controller from Lovato Electric with 8 static steps and a graphic display. Static switching means the capacitor steps are switched by thyristor modules (the DCTL series) instead of contactors, so the bank can follow rapidly changing loads such as welders, cranes and presses without the delay of contactor switching.
Compared with the contactor-based DCRG8 it has three current inputs, master-slave operation, four-quadrant operation, analog outputs and many communication options listed in the table (USB, RS232, RS485, Ethernet, Profibus-DP, GSM/GPRS modem).
Technical specifications
| Parameter | Specification |
|---|---|
| Order code | DCRG8F |
| Product designation | Automatic dynamic power factor controller, 8 static steps, graphic display |
| Product type designation | DCRG8F |
| AC (min) | 100 VAC |
| AC (max) | 415 VAC |
| DC (min) | 110 VDC |
| DC (max) | 250 VDC |
| Auxiliary operating range | 90-484VAC / 93.5-300VDC |
| Auxiliary rated frequency | 50/60 ±10% Hz |
| Power consumption Max | 27 (with 4 EXP modules) VA |
| Power dissipation Max | 10.5 (with 4 EXP modules), 2.5 (with no EXP modules) W |
| Immunity time for microbreakings | ≥35ms (110VAC); ≥80ms (220-415VAC) |
| Rated voltage (Ue) | 600VAC L-L (rated max) |
| Operating range | 50-720VAC L-L (415VAC L-N) |
| Frequency range | 45-65 Hz / 360-440 Hz |
| Type of measure | True RMS value |
| No-voltage release | ≥8 ms |
| Measurement input impedance | above 1.10MΩ L-L, above 0.55MΩ L-N kΩ |
| Type of connection | Single phase, two phase, three phase with or without neutral or balanced three phase system |
| Number of current input | 3 |
| Type of input | Shunt supplied by external current transformer (low voltage). Max 5A |
| Measurement range | 0.025-6A~ for 5A scale; 0.025-1.2A~ for 1A scale |
| Measurement method | True RMS value |
| Constant overload | 1.2 Ie |
| Overload peak | 50A for 1s |
| Type of voltage and current measurement | True RMS value |
| Power factor adjustment | 0.5ind-0.5cap. |
| Type of temperature sensor | Internal + PT100 with EXP1004 |
| Temperature measurement range | 0-+212 °C |
| Number of relay output | 0 (up to 10 with EXP10 06 – EXP10 07) |
| UL/CSA and IEC/EN 60947-5-1 designation | B300 |
| Number of static output | 8 (up to 24 with EXP1001) |
| Rated current | 120mA max 40VDC/30VAC |
| Rated insulation voltage Ui IEC/EN | 600 V |
| Rated impulse withstand voltage Uimp | 9.5 kV |
| Operating frequency withstand voltage | 5.2 kV |
| Functions and protections provided | Automatic recognition of current flow direction, 4-quadrant operation, Master-Slave function, Independent auxiliary supply input, Three-phase voltage control, Dynamic (FAST) power factor correction, Power factor correction by single phase, Possibility of use in medium voltage, Possibility of phase-neutral insertion on a three-phase system, Analog outputs, Input programmable as function or external temperature sensor, USB communication interface, RS232 communication interface, Opto-isolated RS485 communication interface, Ethernet communication interface, Opto-isolated Profibus-DP interface, GPRS/GSM modem, Optical port on front for the connection of USB devices, Optical port on front for the connection of Wi-Fi devices, Fast setting of current transformer, Compatible with Xpress configuration and remote control software, Compatible with Synergy and Synergy Cloud,supervision and energy management software, Compatible with Sam1 App, Calendar-clock with backup reserve power, Data logging memory, Event logging: alarms, setup changes, etc., Customisable internal counters |
| Current inputs | 3 |
| Type of terminal | Plug-in, removable |
| Operating temperature (min) | -20 °C |
| Operating temperature (max) | +70 °C |
| Storage temperature (min) | -30 °C |
| Storage temperature (max) | +80 °C |
| Maximum Pollution degree | 2 |
| Overvoltage category | 3 |
| Climatic sequence | Z/ABDM (IEC/EN 60068-2-61) |
| Shock resistance | 15g (IEC/EN 60068-2-27) |
| Vibration resistance | 0.7g (IEC/EN 60068-2-6) |
| Execution | Flush mount |
| Material | Polycarbonate |
| Mounting | Flush-mount 144x144mm (5.67×5.67”) |
| Degree of protection | IP65 on front, IP20 terminals |
| Dimensions (W x H x D) | 144 x 144 x 53.2 mm |
| Weight | 980 g |
Selecting the controller
Choose the dynamic version when the load changes faster than a contactor bank can respond. For stable loads the standard DCRG8 controller is simpler and cheaper.
Static switching needs matching thyristor modules, such as the DCTLA series; the module ratings (kvar at the bank voltage) must match the capacitor steps.
Applications and installation
Typical use is a plant cubicle with an incomer current transformer, capacitor contactors and detuning reactors where required. Set the target power factor, step sizes and CT ratio during commissioning; the controller then adapts the number of active steps to the load.
The controller mounts in a panel cut-out; relay or static outputs drive the step contactors or thyristor modules.
Related Lovato Electric products: Lovato DCRL8 8-Step Automatic Power Factor Controller, Lovato ATL600 Automatic Transfer Switch Controller 2 Sources, Lovato LVM20A240 LVM20 Level Control Relay, Lovato LVM40A240 LVM40 Level Control Relay, Lovato PMIB1A230 Insulation Monitoring Relay for IT Networks and Lovato PMV45NA480 PMV45N Three-Phase Voltage Monitoring Relay.
Documents and quotation
Download the attached datasheet for DCRG8F from the Lovato Electric online catalogue (English) to see every parameter in full. Ordering checklist: the capacitor bank layout, the number of steps, the current transformer ratio and the supply voltage. Data in the datasheet is subject to change by the manufacturer. For related parts browse controllers & data acquisition. Send the order code DCRG8F, the quantity and the delivery location through the quotation form and Seven Star LLC, an independent supplier in Muscat, will reply with availability.
Datasheets & Documents
- Datasheet Lovato Electric DCRG8F datasheet (EN, catalogue export) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
Related products
Frequently Asked Questions
8.
100 to 415 VAC.
A current transformer with a 5 A or 1 A secondary, measured from 0.025 A to 6 A.
Up to 600 VAC line-to-line.
Static switching (thyristor modules).