Brand:

Danfoss 148B5200 SVA-S 15 Shut-off Valve, 15 mm Butt Weld

Description

SVA-S 15: a small steel angle stop valve with handwheel for industrial refrigeration lines

Danfoss 148B5200 is an SVA-S 15 shut-off (stop) valve from the SVL Flexline range. The body is steel with 15 mm (1/2 in) butt-weld connections to EN 10220, an angleway flow path and a standard neck. This code carries a handwheel, which makes the valve quick to operate by hand on small branch lines and instrument take-offs.

The printed ratings are a maximum working pressure of 52 bar (754 psig), a temperature range of -60 to 150 C and a Kv value of 7 m3/h. The flow is bi-flow, so the valve can be fitted with either side as the inlet, and the body is painted reddish brown. The approvals listed are EAC and UA.

Technical specifications

Parameter Specification
Danfoss code number 148B5200
Type SVA-S 15
Approvals as listed EAC; UA
Body material Steel
Connection standard EN 10220
Inlet connection size 1/2 in / 15 mm
Inlet connection type Butt weld
Kv value 7 m3/h
Maximum working pressure 52 bar
Outlet connection size 1/2 in / 15 mm
Outlet connection type Butt weld
Refrigerants R113; R114; R1234yf; R1234ze(E); R125; R1270; R1336mzz(Z); R134a; R152a; R22; and others listed in the data sheet
Temperature range -60 C to 150 C
Net weight 1.559 kg
EAN 5702428466943

Where the SVA-S 15 is used

SVA-S valves isolate sections of ammonia, CO2 and HFC plant for service, and are placed at evaporator inlets and outlets, on oil drains and on gauge or purge branches. The size 15 is the smallest in the SVA-S line, so it is common on pilot lines, sample points and compact heat exchanger connections.

The refrigerant list on the product page is long and includes R717 (ammonia), R744 (CO2), R134a, R404A, R407C, R410A, R32 and several low-GWP mixtures. The data sheet gives the complete list; use it to confirm your refrigerant and oil before ordering.

Installation, spares and checks

Weld the body into the line with the bonnet removed or the cone protected, as the SVA-S/L installation guide describes; the top works on the SVL Flexline spare-parts program, so bonnet, spindle and gland can be replaced without cutting the line. Keep the handwheel accessible and mark the open/closed position.

Confirm the connection type (butt weld here; socket weld and other versions have different codes), the neck length, and the working pressure class against your design code. Danfoss sells flanges, cap and handwheel accessories separately where needed.

Other types and sizes from the same Danfoss family that appear in the Danfoss store listing include SVA-S 65 (148B4931), SVA-S 6-10 (148B5013), SVA-S 15-20 (148B5276), SVA-S 25-40 (148B5476), SVA-S 50 (148B5728), SVA-S 80 (148B5916), SVA-S 100 (148B6012), SVA-S 125 (148B6116). These are listed for orientation only; each has its own datasheet values, so check size, connection and version before ordering.

Documents and quotation

The attached file is the Danfoss Shut-off valve, type SVA-S and SVA-L AI242886444057en-001402 (manufacturer, unaltered). It is the manufacturer’s own PDF, hosted here unaltered. Related items sit under globe and stop valves. Seven Star LLC is an independent supplier in Muscat; send the code 148B5200 with the quantity and we will quote.

Datasheets & Documents
  • PDF Datasheet Danfoss Shut-off valve, type SVA-S and SVA-L AI242886444057en-001402 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

Frequently Asked Questions

What is Danfoss 148B5200?
An SVA-S 15 steel angle shut-off valve with 15 mm butt-weld connections, a handwheel and a Kv of 7 m3/h.
What is the pressure and temperature range?
Maximum working pressure 52 bar (754 psig); temperature -60 to 150 C.
Is it bi-flow?
Yes, the product page lists bi-flow, with an embossed arrow on the body.
Can the internals be serviced?
Yes, the valve belongs to the SVL Flexline family with spare parts.
Which document is attached?