Brand: Riello UPS
Riello UPS Master HP MHT 100-600 kVA Three-Phase UPS
Description
The Riello UPS Master HP MHT is a transformer-based, three-phase ON LINE double-conversion UPS from 100 to 600 kVA for data centres, industrial loads and other installations where the UPS must tolerate harsh supply conditions. It combines an IGBT rectifier with a delta zig-zag output isolation transformer housed inside the cabinet, which gives complete galvanic separation between the load and the battery. The same datasheet covers the Master HE high-efficiency variant (100 to 800 kVA, power factor 1).
Isolated, zero-impact UPS for generators, industrial plant and parallel systems
The IGBT rectifier delivers an input power factor of 0.99 with input current distortion under 3 percent, plus a power walk-in function and start-up delay. That lowers the oversizing needed on generator sets. The output transformer allows separate mains and bypass inputs from different sources, and no neutral is needed at the rectifier input. Riello UPS also states a high inverter short-circuit current, up to three times nominal, for clearing load-side faults.
Availability features include distributed parallel operation of up to 8 units, a centralised bypass cabinet (MSB) supporting up to 7 UPS modules, dual-bus configurations, Hot System Expansion to add a unit without switching off the system, fault-tolerant operation if the parallel cable is interrupted and an Efficiency Control Mode for parallel systems. Battery care includes deep discharge protection and temperature compensation.
Technical specifications
| Parameter | Specification |
|---|---|
| Models | MHT 100, 120, 160, 200, 250, 300, 400, 500, 600 |
| Rated power (kVA / kW) | 100/90, 120/108, 160/144, 200/180, 250/225, 300/270, 400/360, 500/450, 600/540 |
| Input | 380 / 400 / 415 V three-phase; 400 V plus or minus 20 percent at full load; 45 to 65 Hz; power factor above 0.99; THDi below 3 percent; soft start 0 to 100 percent in 120 s |
| Bypass | 380 / 400 / 415 V three-phase plus N; 50 or 60 Hz selectable; frequency tolerance plus or minus 2 percent (1 to 5 percent selectable) |
| Output | 380 / 400 / 415 V three-phase plus N selectable; static stability plus or minus 1 percent; distortion below 1 percent linear and below 3 percent non-linear; crest factor 3:1 |
| Overload | 110 percent for 60 min, 125 percent for 10 min, 150 percent for 1 min |
| Battery | VRLA AGM, GEL, NiCd, Li-ion, supercapacitors; separate or common battery in parallel systems |
| Efficiency | ECO mode up to 98 percent; efficiency up to 99.4 percent in STANDBY ON mode as stated for the Master HP/HE family |
| Weight (kg) | 700, 755, 830, 956, 1060, 1500, 1720, 2525, 2700 for the nine models in order |
| Dimensions (W x D x H) | 800 x 850 x 1900 mm; 1000 x 850 x 1900 mm; 1500 x 1000 x 1900 mm; 2100 x 1000 x 1900 mm depending on rating |
| Communications | Graphic display, 2 communication slots, 2 x RS232, remote signals (1 opto input, 3 relay outputs), R.E.P.O. |
| Ambient / IP | 0 to 40 degrees C; 5 to 95 percent humidity non-condensing; IP20; RAL 7016 |
| Standards | LV 2014/35/EU, EMC 2014/30/EU, IEC EN 62040-1, IEC EN 62040-2, RoHS; VFI-SS-111 per IEC 62040-3 |
Selection and site checks
Master HP is chosen where galvanic isolation, selectivity between mains and bypass and robust parallel architectures outweigh the footprint advantage of transformer-free designs. Active power of MHT is 90 percent of kVA; Master HE offers kW equal to kVA. Confirm the rated load in kW, the battery type and room, the separate-neutral or common-neutral arrangement, the number of parallel units and the isolation transformer options (TBX ISO series for separate sources). Riello UPS lists these transformers up to 600 kVA, with TBX ISO 800 for MHE 800 on request.
For a different approach in the modular category, see the APC Symmetra PX 128kW UPS, and browse UPS and batteries.
Master HP and Master HE ratings
| Model | Apparent power | Active power | Series |
|---|---|---|---|
| MHT 100 to 250 | 100 to 250 kVA | 90 to 225 kW | Master HP |
| MHT 300 to 600 | 300 to 600 kVA | 270 to 540 kW | Master HP |
| MHE 100 to 600 | 100 to 600 kVA | kW equal to kVA | Master HE |
| MHE 800 | 800 kVA | 800 kW | Master HE |
Documents and quotation
The combined Master HP and Master HE datasheet (DATMHTF3Y23BREN) is attached to this page. Seven Star LLC is an independent supplier in Muscat. Send the exact model code, the load in kW or VA, the input and output voltage and the autonomy needed, and we will quote against the manufacturer data.
Datasheets & Documents
- Datasheet Riello UPS Master HP and Master HE datasheet (DATMHTF3Y23BREN, EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Riello UPS is the uninterruptible power supply brand of the Riello Elettronica Group, with design and production based in Legnago, near Verona, Italy. Its ON LINE and line-interactive UPS cover single-phase IT protection, three-phase industrial systems and modular critical-power installations. Seven Star LLC is an independent supplier in Muscat and lists Riello UPS models together with the manufacturer datasheets.
Riello UPS ranges for IT, industry and data centres
The Sentinel Pro2, Sentinel Dual2 and Sentinel Tower families protect servers, network equipment and small control rooms from 700 VA to 10 kVA. Sentryum, Master MPS and Master HP serve three-phase commercial and industrial loads, while NextEnergy and Multi Power2 modular systems address larger data-centre and critical-power installations. The manufacturer publishes technical data, option lists and dimensions for each range.
Ordering UPS equipment
Send the exact model code, the load in kW or VA, the input and output voltage, the autonomy required and the battery type. We check the request against the manufacturer datasheet before quoting.
Related products
Frequently Asked Questions
Master HP (MHT) is rated at power factor 0.9, for example 100 kVA = 90 kW. Master HE (MHE) shares the technology with output power factor 1 and a best-in-class efficiency of 95.5 percent in ON LINE mode.
Yes. An output isolation transformer inside the cabinet separates the load from the battery, and mains and bypass inputs can be fed from separate sources.
Distributed parallel up to 8 units, or centralised parallel up to 7 units with the MSB bypass cabinet.
It allows another UPS to be added to an existing system without switching off the units already running or transferring the load to bypass.
VRLA AGM and GEL, NiCd, lithium-ion and supercapacitors, with one-level, two-level or cyclic recharge selectable.

Reviews