Brand:

DEIF SGC 120 Mk II Single Genset Controller

Description

Compact controller for single gensets and engine drives

The DEIF SGC 120 Mk II is a small controller with the functions needed to protect and control a genset, a genset breaker and a mains breaker. It monitors engine safety parameters such as coolant temperature and oil pressure, measures generator and mains voltage and frequency, and shows values and alarms on a graphical LCD with Stop, Start and Auto keys. DEIF lists island operation, automatic mains failure (AMF), remote start and stop, auto exercise and engine drive as the modes of operation.

Configuration is done in the free Smart Connect Mk II software over USB. It allows parameter changes, data logging, custom sensor curves and the M-Logic logic tool, which builds functions from selectable input events and output events, with an analogue comparator for custom alarms. Any SGC controller can also act as a remote display for another SGC unit over CAN (J1939) using the RDC 100 software.

Technical specifications

Parameter Specification
Manufacturer / series DEIF, SGC Mk II (application software R18)
Supply 12/24 V DC nominal; operating range 8 to 28 V DC; reverse protection to -32 V DC
Current consumption About 200 mA (excluding DC outputs); standby 124 mA at 12 V; deep sleep 20 mA
Genset voltage measurement True RMS; 32 to 300 V AC phase-neutral, 32 to 520 V AC phase-phase; 5 to 75 Hz
Mains voltage measurement True RMS; 32 to 300 V AC phase-neutral, 32 to 520 V AC phase-phase; 5 to 75 Hz
Genset current -/5 A and -/1 A CT secondary; accuracy ±1.4 % of nominal; burden 0.25 VA
Digital inputs 5, negative switching
Analogue inputs 3 resistive 0-5000 Ω; 1 voltage/current 0-5 V DC or 4-20 mA
MPU / W-point input 10 Hz to 10 kHz; 200 mV to 45 V AC RMS
D+ charging alternator PWM excitation, power limited to 3 W (12 V / 250 mA)
Digital outputs 6 DC outputs, 500 mA each, 1 A total
Communication USB 2.0 type B; RS-485 Modbus (120 Ω termination built in); CAN 250 kbps
Operating temperature -20 to +65 °C; storage -30 to +75 °C
Protection degree IP65 front with supplied sealing gasket
Dimensions / cutout 139.0 x 114.0 x 38.3 mm; cutout 118.0 x 93.0 mm
Weight 276 g without lock; 289 g with lock
Approvals listed CE; UL/cUL Recognized to UL/ULC6200:2019 1st edition

Protections and functions

Generator protections include two stages each of under and over voltage and frequency, unbalanced load, over-current (50TD), overload (32F), low load, reverse power and phase reversal. Engine protections include under and over speed, battery monitoring, charging alternator, pre-heat, coolant temperature, lube oil pressure, fuel level, fuel theft detection and ECU communication failure. Mains protections cover voltage, frequency and phase reversal. Mains functions include mains support (voltage and frequency), mains monitoring and an energy counter.

The genset functions include start and stop sequences, counters for running hours, starts, energy and maintenance, idle speed control, coolant temperature control and automatic fuel transfer.

Choosing the SGC model

Model Supply range Digital inputs Analogue inputs Dimensions (L x H x D)
SGC 120 Mk II (this page) 8 to 28 V DC 5 3 resistive + 1 V/mA 139.0 x 114.0 x 38.3 mm
SGC 420 Mk II 8 to 32 V DC 9 5 resistive + 2 V/mA 233.0 x 173.0 x 38.5 mm

Use the SGC 120 Mk II for small sets with simple I/O; use the SGC 420 Mk II when a larger display with breaker keys, earth-leakage current monitoring or site battery and shelter monitoring is required. Confirm the engine ECU protocol, the number of sensors and the intended mode before ordering.

How the DEIF SGC 120 Mk II works

The controller reads engine signals such as coolant temperature, oil pressure and speed, and it reads the generator and mains voltage and frequency. In Auto mode it waits for a start request, which can come from a remote input or from a mains failure. It starts the engine, checks the generator output and closes the generator breaker. When the request ends, it opens the breaker and stops the engine after a cool-down. Alarms and shutdowns protect the engine at any time.

Where the SGC 120 Mk II is used

  • Single gensets in island mode
  • Automatic mains failure sets
  • Remote start and stop sets
  • Engine drives
  • Compact panels with a small cut-out

Selection checklist for the SGC 120 Mk II

  • Operating mode needed
  • Supply of 12 or 24 V DC
  • Generator and mains voltage level
  • Current transformer secondary of 1 A or 5 A
  • Number of digital and analogue inputs
  • Engine speed pick-up type
  • Communication links needed
  • Panel cut-out of 118 by 93 mm

Installation, commissioning and maintenance notes for the SGC 120 Mk II

Cut the panel to size and fit the controller with its gasket. Wire the supply, the engine inputs, the outputs and the voltage and current inputs. Connect a PC over USB and set up the parameters in the Smart Connect Mk II software. Test the start and stop sequence with the breakers open, and then test with load.

Requesting a quotation for the DEIF SGC 120 Mk II

Please send the mode needed, the supply voltage and the quantity. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.

SGC 120 Mk II supply

The supply is 12 or 24 V DC, with an operating range of 8 to 28 V DC.

SGC 120 Mk II voltage measurement

Generator and mains voltage are measured as true RMS from 32 to 300 V phase-neutral.

SGC 120 Mk II inputs and outputs

There are 5 digital inputs, 4 analogue inputs and 6 digital outputs of 500 mA each.

SGC 120 Mk II communication

The links are USB, RS-485 Modbus and CAN at 250 kbps.

SGC 120 Mk II software

Smart Connect Mk II gives parameter changes, data logging, custom sensor curves and M-Logic.

SGC 120 Mk II enclosure

The front has IP65 protection with the supplied gasket.

SGC 120 Mk II temperature range

Operation runs from minus 20 to plus 65 degrees C.

Controller records for the SGC 120 Mk II

Record the application software version and the saved parameter file.

Choosing the right SGC 120 Mk II mode

Choose AMF for a standby set and remote start for a set that another system controls.

Documents and quotation

The DEIF data sheet is attached. Send the model, quantity and engine data for a quotation. See Diesel Generator Spare Parts for further generator control products.

Datasheets & Documents
  • PDF Datasheet DEIF SGC 120 Mk II data sheet 4921240652 (EN) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

DEIF is a Danish, family-owned manufacturer of control and protection equipment for power generation. It was founded on 1 June 1933 in Copenhagen by Erling Foss and two partners as Dansk Elektro Instrument Fabrik, and is now headquartered in Skive, Jutland, where its production and R&D are based. Its controllers run generator sets, switchboards and ship bridges on land and at sea.

Seven Star LLC is an independent supplier in Muscat. We list DEIF genset controllers, voltage regulators and protection units for generator packagers, power plant operators and marine users in Oman and the GCC.

DEIF company profile

Founded 1 June 1933, Copenhagen, Denmark, as Dansk Elektro Instrument Fabrik
Founders Erling Foss and two partners
Headquarters Skive, Denmark
Ownership Founder's son Toke Foss and his three children
Product families Genset and engine controllers (AGC, GC, multi-line 2), protection relays, switchboard meters and transducers, bridge instrumentation, wind turbine controls

Milestones

  • 1933: DEIF is founded in Copenhagen and starts by hand-assembling electromagnetic measuring instruments.
  • Today: Production and R&D are based at the Skive headquarters; the group remains in the Foss family.

DEIF product series

Genset controllers range from the compact SGC 120 Mk II and SGC 420 Mk II (with breaker keys) and the CGC 400 to the AGC 150, which handles genset, mains and bus-tie breaker applications, the AGC 200 and the AGC-4 Mk II for group and plant control with many gensets. The iE 250 is an intelligent energy controller for gensets in hybrid and grid-connected plants.

Protection and paralleling units include the GPU-3 generator protection unit in marine and gas versions and the GPC-3 generator paralleling controller, while the PPM 300 and PPU 300 serve marine power management. The DVC 350 and DVC 550 are digital voltage controllers (AVRs) for synchronous generators.

Where DEIF controllers are used

Stand-by power for buildings, hospitals and data centres, prime power at remote oil and gas and mining sites, multi-genset paralleling plants, gas engine plants, and ship and offshore power management.

DEIF products we list

Family Examples
Diesel Generator Spare Parts AGC 150 Advanced Genset, AGC 200 Automatic Genset Controller, AGC-4 Mk II Genset, CGC 400 Compact Genset Controller, DVC 350 Digital Voltage Controller AVR 5 A, DVC 550 Digital Voltage Controller AVR 7 A, GPC-3 Generator Paralleling Controller, GPU-3 Gas Generator Protection Unit and 3 more
Controllers & Data Acquisition PPM 300 Marine Protection and Power Mana…, PPU 300 Marine Paralleling and Protectio…

Ordering DEIF controllers: what we need

Name the exact model and variant, the software package or option letters where they apply, the quantity, the engine make and ECU protocol, and the breaker and mains configuration. DEIF configures several controllers by variant and option, so the data sheet on each page should be checked against the project before a quotation is issued.

Facts checked against DEIF's own history and facts pages (deif.com) and the Danish business register, October 2026.

FAQ

Questions about the DEIF SGC 120 Mk II Single Genset Controller

Answers from our engineering team on installation, compatibility and integration.

01What modes of operation does the SGC 120 Mk II offer?
Island, automatic mains failure (AMF), remote start and stop, auto exercise and engine drive.
02What supply voltage does it accept?
Nominal 12/24 V DC with an operating range of 8 to 28 V DC.
03How is it configured?
With the free Smart Connect Mk II software over a USB 2.0 type B connection, or through the display buttons.
04Can it act as a remote display?
Yes. An SGC controller can be configured as a remote display for another SGC controller over CAN J1939 with the RDC 100 software.
05Which approvals does DEIF list?
CE, and UL/cUL Recognized to UL/ULC6200:2019 1st edition.