- Automation & ControlView all 3,157 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Bürkert
Bürkert 563779 Type 8316 Pressure Transmitter 0-6 bar 4-20 mA
Description
Overview
Bürkert 563779 is a compact stainless steel pressure transmitter, Bürkert Type 8316, measuring relative pressure from 0 to 6 bar and returning a two-wire 4 to 20 mA signal. A ceramic measuring cell sits behind a G1/4 process thread, and an M12 male connector carries the loop. It is the kind of transmitter fitted on pump discharge lines, compressed-air receivers, filter differential points and small skids where a rugged, inexpensive sensor is wanted. Seven Star LLC is an independent supplier serving Oman and the GCC.
Range and signal of 563779
Within the Type 8316 chart this article is the 0 to 6 bar range with a 7 to 33 V DC unregulated supply and a UL Listed approval. The loop current of 4 mA corresponds to zero pressure and 20 mA to 6 bar, giving a linear 16 mA span. Because it is a two-wire device, one pair of conductors carries both power and signal, which keeps wiring cost low and makes it compatible with practically every PLC analogue input and loop-powered indicator. The sensor draws a maximum of 23 mA and has reverse polarity and short-circuit protection.
Technical table for Bürkert 563779
| Characteristic | Value |
|---|---|
| Article number | 563779 |
| Measuring range | 0 to 6 bar, relative pressure |
| Output | 4 to 20 mA, two-wire |
| Operating voltage | 7 to 33 V DC, unregulated |
| Process connection | G1/4 according to DIN 3852 form E |
| Electrical connection | M12 x 1 male connector |
| Measuring element | ceramic Al2O3 (96 percent) |
| Wetted parts | stainless steel 1.4404 (316L) connection, FKM seal |
| Housing | stainless steel 1.4404 (316L) |
| Measurement deviation | up to plus or minus 0.5 percent of full scale, typically 0.3 percent or better |
| Response time | under 2 ms, typically 1 ms |
| Overload pressure | 2.5 times full scale |
| Fluid temperature | minus 15 to plus 125 degrees C |
| Ambient temperature | minus 30 to plus 85 degrees C in operation |
| Protection | IP67; protection class III |
| Weight | approx. 90 g |
How 563779 differs from other Type 8316 variants
The ordering chart steps through the ranges 0.05, 0.1, 0.25, 1, 4, 6, 10, 16, 40 and 100 bar. The three lowest ranges, with article numbers 570536, 567953 and 570721, use a more sensitive ceramic element, need 10 to 33 V, and respond in under 150 ms. The 0 to 1 and 0 to 4 bar versions, 563777 and 563778, have a higher overload factor of three times full scale. From 0 to 6 bar upward the overload factor is 2.5 times full scale, and the 0 to 100 bar code 563783 changes to a metallic element. Bürkert 563779 sits in the middle of the family with fast response and the standard ceramic element.
Where it gets used
Six bar is the natural range for plant air and for many water and cooling circuits, so this transmitter appears on compressor outlets, instrument air headers, booster pump discharge lines and filter skids. Because of the stainless housing and IP67 rating it also survives washdown and outdoor locations in the Gulf. The quick response suits control loops with fast pressure changes, such as pump start-up monitoring.
Selection and wiring checks
Choose the range so that normal operating pressure lies between 30 and 80 percent of the span, and ensure surge peaks stay below 15 bar, the 2.5 times overload level. Check that the medium is compatible with 316L stainless steel, ceramic and FKM. The loop resistance must stay below the supply voltage minus 7 V divided by 20 mA, so a 24 V loop allows about 850 ohm. A 12 or 24 V DC supply is typical. A mating M12 female connector and cable are ordered separately.
Temperature behaviour and accuracy
The quoted deviation combines linearity, hysteresis and reproducibility, with the zero point and full-scale value balanced at the factory. Over a temperature span of minus 15 to plus 85 degrees C, the zero point and span drift by up to plus or minus 0.2 percent of full scale per 10 K for ranges above 0.6 bar. In a plant where the sensor sits next to a hot pump casing, the actual error in service therefore depends on where the sensor is mounted, so a short impulse line that keeps the transmitter cooler is often better than a direct connection. The measuring range resolution is better than 0.1 percent of full scale, which is smaller than the typical process noise in water and air lines.
Dynamic measurements
With a response time below 2 ms the transmitter can follow pulsating pressure, which makes it suitable for reciprocating pumps, fast valves and pneumatic cylinders, and the load cycle limit of under 100 Hz tells you how fast the pressure may oscillate. For slowly changing pressures, a damping element in the PLC or a snubber at the port can reduce noise without hiding real events. Remember that the same sensitivity means water hammer can produce brief spikes above the nominal range, which is why the overload limit of 15 bar matters for 6 bar installations on long pipelines.
Fitting the transmitter
Screw the G1/4 thread into a port with a flat sealing surface and a suitable bonded or copper seal, using a spanner on the hexagon only. Do not tighten by turning the housing. Connect the cable, and zero the reading at atmospheric pressure in the control system if required. For steam or hot fluid use a siphon or a cooling loop, since the fluid temperature limit is 125 degrees C.
Care of the sensor
The unit is sealed and has no user-serviceable parts. Keep the pressure port free of dried deposits, which can clog the ceramic cell cavity, and check the M12 plug for moisture ingress at inspections. If the reading drifts, compare against a calibrated gauge before replacing.
Ordering Bürkert 563779
Please state the pressure range, the output type and the process thread, together with the quantity. We can also offer neighbouring ranges and the NPT 1/4 versions listed in the same chart.
Related items you may also need: Bürkert 221602 Type 6213 Servo-Assisted 2/2-Way Solenoid Valve | Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Bürkert Type 8681 Control Head for Hygienic Process Valves | All Bürkert products.
Documents and quotation
The manufacturer data sheet for Type 8316 is attached, with dimensions, materials and the ordering chart. Send an RFQ with the part number Bürkert 563779, the quantity and your delivery location in Oman or the GCC, and we will reply with availability and lead time.
Datasheets & Documents
- Datasheet Bürkert 563779 Type 8316 Pressure Transmitter 0-6 bar 4-20 mA Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.
Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.
Bürkert company profile
| Founded | 1946, by Christian Bürkert |
|---|---|
| Headquarters | Ingelfingen, Germany |
| Ownership | Family-owned |
| Product families | Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers |
Bürkert types listed on this page
Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.
Ordering Bürkert valves: what we need
The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.
Facts checked against Bürkert's published company history, October 2026.
Browse Bürkert products by category: Solenoid Valve, Control Valves.
FAQ
Questions about the Bürkert 563779 Type 8316 Pressure Transmitter 0-6
Answers from our engineering team on installation, compatibility and integration.
01What is Bürkert 563779?
Bürkert 563779 is a Type 8316 stainless steel pressure transmitter, 0 to 6 bar, 4 to 20 mA two-wire output, G1/4 thread and M12 plug.
02What supply does 563779 need?
The 563779 transmitter works from 7 to 33 V DC unregulated, draws up to 23 mA and has reverse polarity and short-circuit protection.
03How accurate is Bürkert 563779?
The data sheet gives a maximum deviation of plus or minus 0.5 percent of full scale, typically 0.3 percent or better, with a response time near 1 ms.
04What is the overload limit of 563779?
For the 0 to 6 bar range the overload pressure is 2.5 times full scale, which is 15 bar.
05Does Bürkert 563779 fit hot media?
The fluid temperature range is minus 15 to plus 125 degrees C, so use a siphon or cooling leg on steam applications.


















Reviews
There are no reviews yet.