Brand:

Bürkert 434871 Type 8032 SE32 PNP Flow Threshold Detector

Description

Overview

Bürkert 434871 is a paddle wheel threshold detector from the Bürkert Type 8032 line: the SE32 electronics with one PNP transistor output and a female cable plug to DIN EN 175301-803. It monitors liquid flow in pipes from DN 06 to DN 65 and switches when the flow passes a set value, so pumps can be protected against running dry, cooling circuits supervised and dosing lines released only while there is flow. Seven Star LLC is an independent supplier serving Oman and the GCC.

Switching behaviour of Bürkert 434871

The single transistor sources the supply voltage when active, which makes it a PNP output that fits sinking PLC inputs and relays. It carries up to 700 mA with short-circuit protection and can switch at up to 300 Hz. Its thresholds are parameterised on the module as either a hysteresis pair or a window, which lets the same device raise an alarm when the flow drops below a minimum or leaves a band around a setpoint.

Data table of Bürkert 434871

Parameter Value
Article 434871, SE32 threshold detector, 1 x PNP, no UL
Output 1 transistor PNP, open collector, 700 mA max.
Electrical connection Female cable plug DIN EN 175301-803
UL approval No (UL Recognized version is 570474)
Principle Paddle wheel with 8-digit backlit LCD
Supply 12 to 36 V DC plus or minus 10 percent, SELV and LPS, reverse-polarity protected
Current consumption 80 mA or less with no load
Flow range 0.5 to 1000 l/min, 0.3 to 10 m/s with Type S030 fitting
Deviation teach-in plus or minus 1 percent; standard K factor plus or minus 3 percent
Linearity and repeatability 0.5 percent of full scale; 0.4 percent of reading
Operating mode threshold with window or hysteresis
Pipe size DN 06 to DN 65
Viscosity and solids 300 cSt max.; up to 1 percent solids, 0.5 mm
Fluid temperature with S030 PVC 0 to 50; PP 0 to 80; PVDF, steel or brass minus 15 to plus 100 degrees C
Fluid pressure plastic PN 10, metal PN 16
Housing glass fibre reinforced PC, polyester front film

How Bürkert 434871 differs from other SE32 articles

Four other threshold versions share the same housing. Article 436474 has one NPN transistor with the same cable plug. Article 436473 has two NPN or PNP transistors and a free positionable 5-pin M12 male connector. Article 436475 replaces the transistors with a relay. The transmitter versions 560403, 560402 and 560547 add a 4 to 20 mA process value output. 434871 is the simplest PNP choice and, with its cable plug, the easiest to wire in a plain cabinet.

Combining the SE32 electronics with an S030 fitting

The SE32 module is half of a flow measuring point. It clips by bayonet into a Bürkert Inline sensor-fitting Type S030, which carries the paddle wheel and fixes the pipe size from DN 06 to DN 65, the connection style and the wetted materials. Plastic fittings suit corrosive water lines and metal fittings suit higher pressure and temperature. The wheel is PVDF on a ceramic axis, and seals are FKM or EPDM depending on the fitting chosen. Always state the fitting when requesting a quote, since it is ordered as a separate article.

Commissioning and teach-in routine

Before the first start, flush the line, install the fitting with the arrow in the flow direction and press the electronics into the bayonet until it locks. Apply power and select the language, unit and K factor from the three keys. For better accuracy, run the teach-in: fill a measured volume through the pipe, enter it, and let the device calculate the K factor. Then set the switching points and test them by throttling a valve while watching the display. Record the settings on the commissioning sheet for later comparison.

Typical duties in Oman and the GCC

Common uses are minimum flow protection of cooling water to compressors and engines, circulation monitoring on chilled water loops, flow confirmation before a chemical dosing pump starts and wash water proving on filling lines. The sensor is also used as a simple on-off controller of a make-up valve when the display and keys are used to define thresholds.

Pump protection with Bürkert 434871

The commonest use of a flow switch is to stop a pump running dry. The PNP output of this article connects to a PLC input or to a protection relay; when flow falls below the set threshold for longer than a delay time, the PLC trips the pump. Set the delay long enough to cover the start-up period, when flow is not yet established, usually five to thirty seconds depending on the line. Use hysteresis so that the output does not chatter around the threshold, and add a latching alarm that needs a manual reset after a trip.

Because the sensor measures actual flow, it protects against closed valves, blocked strainers and air-locked pumps, which a pressure switch alone may not detect.

Quotation notes for Bürkert 434871

Please give the article number, the number of units, the pipe size and material of the line so that a matching Type S030 fitting can be quoted, and the cable plug requirement. State whether the PLC input is sinking or sourcing, so that we can confirm that the PNP output suits your wiring. Delivery to Oman and the GCC can then be planned.

Delivery notes for Bürkert 434871

The device is delivered as the SE32 electronics with a female cable plug; the Inline fitting is a separate article. The attached data sheet shows dimensions, pressure-temperature diagrams and the pin assignment. Tell us about special requirements such as certificates or UL versions at enquiry stage, so that the right article can be quoted for delivery to Oman.

Related items you may also need: Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Bürkert Type 8681 Control Head for Hygienic Process Valves | KRACHT SVC 10 K1F1R2SH Screw Flow Meter | All Bürkert products.

Documents and quotation

The Type 8032 data sheet that contains Bürkert 434871 is attached with ordering charts, dimension drawings and pressure-temperature diagrams. Please send an RFQ with part number 434871, quantity and delivery location in Oman or the GCC, and state the pipe size and material so that a matching Inline fitting can be offered.

Datasheets & Documents
  • PDF Datasheet Bürkert 434871 Type 8032 SE32 PNP Flow Threshold Detector Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.

Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.

Bürkert company profile

Founded 1946, by Christian Bürkert
Headquarters Ingelfingen, Germany
Ownership Family-owned
Product families Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers

Bürkert types listed on this page

Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.

Ordering Bürkert valves: what we need

The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.

Facts checked against Bürkert's published company history, October 2026.

FAQ

Questions about the Bürkert 434871 Type 8032 SE32 PNP Flow Threshold

Answers from our engineering team on installation, compatibility and integration.

01What output has Bürkert 434871?
It has one PNP open-collector transistor output, rated 700 mA with short-circuit protection and a frequency up to 300 Hz.
02Is 434871 a transmitter or a threshold detector?
It is a threshold detector without a 4 to 20 mA output; transmitter versions have other article numbers such as 560403.
03What connector does Bürkert 434871 use?
The electrical connection is a female cable plug according to DIN EN 175301-803, supplied with the device.
04What pipe sizes can 434871 monitor?
With a Type S030 Inline sensor-fitting the module covers pipes from DN 06 to DN 65 and flows from 0.5 to 1000 l/min.
05Does 434871 have UL approval?
No. The UL Recognized equivalent with one PNP output carries article number 570474 in the Type 8032 ordering chart.