Brand: Magnetrol
Magnetrol 089-9125-002 Echotel 355 Electronic Module Lexan, No HART
Description
Magnetrol 089-9125-002: Echotel 355 electronic module without HART for Lexan housing
The electronic module is the brain of an Echotel 355, and the Magnetrol 089-9125-002 is the version without HART communication for the Lexan plastic housing. It is item 2 in the replacement parts table of manual 51-661, and it is the cheapest way to restore a 355 whose display, keypad or measurement electronics have failed, while the transducer is still sound.
The table pairs two choices, aluminum or Lexan housing and with or without HART, and so the four modules are 089-9125-001 (aluminum, no HART), 089-9125-002 (Lexan, no HART), 089-9125-003 (aluminum, HART) and 089-9125-004 (Lexan, HART). Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Key facts about 089-9125-002
- Housing: Lexan plastic, which uses the cover 003-1226-003 and the O-ring 012-2616-001.
- Communication: analog 4 to 20 mA only, with no digital HART signal.
- Includes the measuring electronics, the 2-line display and the 4-button keypad.
- Operates on a two-wire loop; the diagnostic alarm can be set to 3.6 mA, 22 mA or HOLD.
Technical data for 089-9125-002
| Parameter | Value |
|---|---|
| Part number | 089-9125-002 |
| Manual item | 2, electronic module |
| Output | 4 to 20 mA; 3.8 to 20.5 mA usable (NAMUR NE 43) |
| Diagnostic alarm | Selectable 3.6 mA, 22 mA or HOLD |
| Damping | Adjustable 1 to 60 |
| Loop resistance | 400 ohm at 24 VDC and 20 mA; 350 ohm at 24 VDC and 22 mA |
| Power consumption | Less than 1 watt |
| Warm-up time | 25 seconds |
| Display | 2-line by 16-character LCD |
| Keypad | 4 push-buttons, menu driven |
| Ambient temperature | -40 to +80 C |
| Accuracy | Greater of 0.2 percent of range or 0.24 inch (6 mm) |
Where 089-9125-002 is used in oil and gas, utilities, water and manufacturing
A module without HART fits plants that read the level only as a 4 to 20 mA signal in a DCS or a local controller, such as pump station sumps, municipal water towers or simple chemical day tanks. In the Gulf region the Lexan version is favored on corrosive wastewater and desalination chemical duties.
Because there is no digital layer, a technician sets up the unit through the front keypad: Range (factory default 240 inches), Blocking Distance (10 inches), Safe Zone Fault, Level Offset and the 4 mA and 20 mA set points (default 0 and 230 inches).
How 089-9125-002 differs from 089-9125-004 and 089-9125-001
| Module | Variant |
|---|---|
| 089-9125-001 | Aluminum housing, no HART |
| 089-9125-002 | Lexan housing, no HART (this part) |
| 089-9125-003 | Aluminum housing, with HART |
| 089-9125-004 | Lexan housing, with HART |
Between 089-9125-002 and 089-9125-004 the only difference is HART, so if your plant already uses HART configuration tools you should order the 004. The aluminum modules mount in a different housing.
Selection and compatibility for 089-9125-002
- Check the housing on the nameplate: a code 6 housing is the Lexan housing.
- If the old module was HART-capable, order 089-9125-004 instead.
- The transducer is a separate item (kits 089-9126-013 to 089-9126-020 for the Lexan base).
- Record the Range and set points before removing the old module, because the new module starts from factory defaults.
Installation and commissioning of 089-9125-002
Disconnect power, observe the electrostatic discharge precautions in section 2.2 of the manual, and handle the board only by its edges. Fit the module, close the housing with a good O-ring, and reconnect the loop at 16 to 30 VDC for general purpose or 16 to 28.4 VDC for intrinsically safe units.
Wait for the 25 second warm-up, then reenter the configuration and verify the reading against a measured tank level.
Maintenance and spares planning
Electronic modules are usually replaced after lightning or a wiring error. Keep the removed module for the failure analysis and keep the replacement in its anti-static bag until installation.
Transducer and application data the 089-9125-002 works with
The module does not measure alone; it drives the ultrasonic transducer of the Model 355. The values below are the transducer and performance figures printed in the manual, and they define what the module can achieve on a tank.
| Parameter | Value |
|---|---|
| Maximum range | 20 feet (6 m) under ideal conditions |
| Minimum range | 13 inches (330 mm) |
| Blocking distance | 10 inches (250 mm) |
| Frequency | 60 kHz |
| Beam angle | 10 degree conical |
| Process connection | 2 inch NPT |
| Process temperature | -40 to +175 F (-40 to +80 C) |
| Process pressure | 0 to 43.5 psig (0 to 3 bar) |
| Accuracy | Greater of 0.2 percent of range or 0.24 inch (6 mm) |
| Repeatability | 0.125 inch (3 mm) |
| Resolution | 0.1 inch (2.5 mm) |
| Output | 4 to 20 mA, optional HART, 3.8 to 20.5 mA usable (NAMUR NE 43) |
| Minimum measurement | 3 inches (76 mm) |
| Linearity | 0.4 inch (10 mm) |
| Response time | Less than 1 second, typical |
| Warm-up time | 25 seconds |
| Display | 2-line by 16-character LCD with 4-button keypad |
| Diagnostic alarm | Selectable 3.6 mA, 22 mA or HOLD |
| Power consumption | Less than 1 watt |
Measurement range depends on the tank: the manual multiplies the 20 foot maximum by performance factors such as 0.9 for slight agitation, 0.8 for much condensation and 0.8 for a light froth, which in its worked example turns 20 feet into 14.4 feet. A module without HART gives the same measurement, so size the range with those factors before blaming the electronics.
Documents and quotation
The manufacturer manual 51-661 for the Echotel Model 355 is attached to this page as the datasheet for 089-9125-002; its section 3.4 holds the parts table and section 3.6 the specifications used above. To receive a quotation, send an RFQ giving part number 089-9125-002, quantity, the model number printed on the transmitter nameplate and the delivery location in Oman or the GCC.
Typical Questions From Maintenance Teams
Maintenance engineers replacing a Magnetrol 089-9125-002 usually ask whether the new unit is a direct fit, whether settings can be copied from the old one, and whether any accessories must be ordered separately. The answer depends on the exact order code and the generation of the installed ultrasonic level transmitters, so the nameplate details are the best starting point. Send them with your request and we will check the match, point out any differences in connections or options, and list the parts needed so that the job can be finished in one visit.
What to Include in Your Magnetrol 089-9125-002 Enquiry
An accurate quotation for the Magnetrol 089-9125-002 depends on a few details. Please share the complete part number, any suffix codes for options or approvals, the operating conditions at the installation point, and whether certificates of conformity or test reports must ship with the goods. It also helps to know whether the unit is for planned maintenance, a shutdown or an urgent breakdown, because that decides how it is sourced and shipped. With this information our team can check compatibility with your existing ultrasonic level transmitters and reply with availability and a realistic delivery estimate.
Other Models in the Magnetrol 355 Module Range
Seven Star LLC supplies models from the Magnetrol 355 Module range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Magnetrol 089-9125-004 Echotel 355 HART Electronic Module Lexan | Ultrasonic Level Transmitters | View details |
| Magnetrol 089-9125-002 Echotel 355 Electronic Module Lexan, No HART | Ultrasonic Level Transmitters | You are viewing this model |
Datasheets & Documents
- Datasheet Magnetrol 089-9125-002 Echotel 355 Electronic Module Lexan, No HART Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Magnetrol is the American level and flow measurement specialist known for the Eclipse guided wave radar, Pulsar radar transmitters and the float and displacer switches that guard boilers and vessels. It was founded in 1932, is based in Aurora, Illinois, and has been part of AMETEK since 2021.
Seven Star LLC is an independent supplier in Muscat. We list Magnetrol level transmitters and level and flow switches, and supply them to refineries, gas plants and utilities in Oman and the GCC by complete model number.
Magnetrol company profile
| Established | 1932, USA; headquarters in Aurora, Illinois |
|---|---|
| Ownership | Acquired by AMETEK in March 2021 and now part of its Electronic Instruments Group |
| Product families | Guided wave radar, non-contact radar, displacer and buoyancy transmitters, ultrasonic and thermal dispersion switches, float switches and magnetic level indicators (through its Orion Instruments brand) |
| Applications | Separators, storage tanks, boilers and feedwater heaters, interface measurement, pump protection and flow detection |
Milestones
- 1932: The first mechanical buoyancy level switch; the company grows into Magnetrol, based in Aurora, Illinois.
- 1998: Eclipse Model 705, a loop-powered guided wave radar transmitter for industrial liquid level, according to Magnetrol.
- 2021: AMETEK acquires Magnetrol on 29 March.
Magnetrol products we list
| Model | Principle | Typical use |
|---|---|---|
| Eclipse 706 | Guided wave radar | Level and interface in separators, chambers and boiler drums, unaffected by changing density |
| Pulsar R80 | 80 GHz FMCW radar | Narrow-beam non-contact level in tanks with internals and in solids |
| Pulsar R86 | 26 GHz radar | Non-contact level in process and storage vessels |
| Pulsar R96 | 6 GHz radar | Non-contact level where vapour, foam or condensation are present |
| E4 Modulevel | Displacer | Level and interface in high-pressure, high-temperature vessels, often replacing older torque tube units |
| Echotel 961/962 | Ultrasonic gap switch | High and low level alarms and pump protection |
| Thermatel TD1/TD2 | Thermal dispersion switch | Flow and no-flow detection and level switching for liquids and gases |
Guided wave radar sends pulses down a probe and times the reflection from the surface, so dust, vapour and changes in density don't affect the reading. That is why it often replaces displacers on separators and chambers. Non-contact radar suits tanks where nothing should touch the product, and a higher frequency gives a narrower beam that avoids tank internals.
Where Magnetrol instruments are used
In Oman and the GCC, Magnetrol transmitters and switches measure level in production separators, slug catchers, storage tanks, boiler drums and feedwater heaters, and protect pumps in oil and gas, refining, petrochemical, power and water plants.
Ordering Magnetrol instruments: what we need
Send the complete model number from the nameplate. On Magnetrol instruments every digit sets the electronics, the probe or antenna, the process connection and the approvals. For a new application, send the medium, the dielectric constant if known, the measuring range, the pressure and temperature, the process connection and the hazardous area classification.
Facts checked against Magnetrol and AMETEK company information, October 2026.
Browse Magnetrol products by category: Level Transmitter.
FAQ
Questions about the Magnetrol 089-9125-002 Echotel 355 Electronic
Answers from our engineering team on installation, compatibility and integration.
01What is Magnetrol 089-9125-002?
It is the Echotel 355 electronic module without HART for the Lexan plastic housing, listed as item 2 in manual 51-661.
02How is it different from 089-9125-004?
089-9125-004 is the HART version for the Lexan housing; 089-9125-002 provides the analog 4 to 20 mA output only.
03What are the factory defaults after a module replacement?
The manual shows a default Range of 240 inches, Blocking Distance of 10 inches and 4 mA and 20 mA set points of 0 and 230 inches.
04What loop voltage can the 355 use?
General purpose and XP units use 16 to 30 VDC in the manual caution and IS units 16 to 28.4 VDC.
05Can Seven Star LLC quote 089-9125-002?
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Send an RFQ with the part number, quantity and delivery location.