Brand:

Rittal SK 3382.500 TopTherm Blue e Roof Cooling Unit

Description

Rittal SK 3382.500 TopTherm Blue e roof-mounted cooling unit, 0.6 kW

The Rittal SK 3382.500 is a roof-mounted enclosure cooling unit from the TopTherm Blue e range. It has a rated cooling output of 0.6 kW at L35/L35 and 50 Hz, runs on 230 V single-phase 50/60 Hz and has an integrated e-Comfort controller with electric condensate evaporation as standard. Dimensions are 597x417x380 mm (width x height x depth) and net weight is 36.1 kg. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer; the product name and part number are used only to identify the item.

Reading SK 3382.500

SK is the series prefix for climate-control components; 3382 selects one capacity and housing in the Blue e roof-mounted group, which is catalogued as covering 0.5 to 4 kW. The L35/L35 rating means 35 °C ambient and 35 °C inside the enclosure; at L35/L50 (50 °C inside) the data sheet lists 0.47 kW at 50 Hz, a reminder that output falls as the inside temperature rises.

Technical specifications of SK 3382.500

Parameter Specification
Manufacturer / part number Rittal SK 3382.500
Design roof-mounted
Material Sheet steel
Colour RAL 7035
Supply includes Condenser with hydrophobic RiNano coating; Integral electric condensate evaporation; Fully wired ready for connection (plug-in terminal strip); Drilling template; Assembly parts
Total cooling output to DIN EN 14511 Cooling output L35 L35/50 Hz: 0.6 kW; Cooling output L35 L35/60 Hz: 0.62 kW; Cooling output L35 L50/50 Hz: 0.47 kW; Cooling output L35 L50/60 Hz: 0.48 kW
Rated operating voltage 230 V, 1~, 50 Hz/60 Hz
Rated current max. At 50 Hz: 2.3 A; At 60 Hz: 2.6 A
Start-up current max. At 50 Hz: 9.1 A; At 60 Hz: 8.8 A
Air throughput (unimpeded air flow) External circuit: 800 m³/h; Internal circuit: 170 m³/h
Energy efficiency ratio (EER) 50/60 Hz L35 L35 Refrigeration factor L35 L35 (EER) 50 Hz: 1.62; Refrigeration factor L35 L35 (EER) 60 Hz: 1.91
Dimensions Width: 597 mm; Height: 417 mm; Depth: 380 mm
Protection category to IEC 60 529 External circuit IP 34; Internal circuit IP 54
Refrigerant/cooling medium Refrigerant: R-513A; Quantity: 0.3 kg; Global Warming Potential (GWP): 631; CO2 equivalent (CO2e): 0.19 t
Type of electrical connection Plug-in terminal strip
Duty cycle 100 %
Temperature control e-Comfort controller (factory setting +35 °C)
Operating temperature range 10 °C…55 °C
Storage temperature range -40 °C…70 °C
Setting range 20 °C…55 °C
Power consumption Pel Power consumption L35 L35/50 Hz: 0.37 kW; Power consumption L35 L35/60 Hz: 0.34 kW; Power consumption L35 L50/50 Hz: 0.41 kW; Power consumption L35 L50/60 Hz: 0.39 kW
Permissible operating pressure (p. max.) 28 bar
Pre-fuse Miniature circuit-breaker/fuse: 10 A
Net weight 36.1 kg
Gross weight 38 kg
Product description Approvals SK Blue e cooling unit, roof-mounted, 0.60 kW, 230 V, 1~, 50/60 Hz,; sheet steel, WHD: 597 x 417 x 380 mm

How the SK 3382.500 cooling circuit works

A compressor-based cooling unit works like a small refrigeration system. Warm air from the enclosure is drawn across an evaporator, where the refrigerant (R-513A, 0.3 kg charge) absorbs heat; the heat is released to the room through the condenser and the external fan. The two air paths are separate: the internal circuit (170 m³/h free-blowing) and the external circuit (800 m³/h). The enclosure is therefore not opened to ambient air and the internal protection stays at IP 54. Condensate produced at the evaporator is evaporated electrically by the integral unit, so no drain hose is needed for normal operation.

The e-Comfort controller holds a factory setpoint of +35 °C, which can be changed within the setting range in the data sheet, and shows operating state and fault messages. The condenser carries a hydrophobic RiNano coating, which is intended to help the surface shed dirt and moisture.

Electrical data and sizing of SK 3382.500

Maximum rated current is At 50 Hz: 2.3 A; At 60 Hz: 2.6 A and the miniature circuit-breaker or fuse the data sheet specifies is 10 A. Power consumption at L35/L35 and 50 Hz is 0.37 kW, which together with the 0.6 kW cooling output gives an energy efficiency ratio (EER) of 1.62. To size a unit, start from the total heat dissipation of the devices inside, add the heat gain through the enclosure walls where ambient exceeds the inside temperature, and choose a unit whose output at your design point exceeds the total with a margin. Unit data at 35/35 flatters the unit in a hot plant, so check the L35/L50 or an equivalent curve and not only the headline kW figure.

Where SK 3382.500 fits and related parts

The Blue e roof-mounted group also includes SK 3273.500 (noted in the data sheet as suitable for office areas because of low noise), SK 3382.500, SK 3383.500 and SK 3385.500. At the smallest output of the four, this unit suits compact panels with moderate heat load. Accessories mentioned for the cooling range include the Blue e IoT adaptor for networking units from 500 W, and the external electric condensate evaporator SK 3301.500 for wall-mounted units. Roof-mounted units need an enclosure with a roof cut-out of the size given in the assembly instructions, so verify the enclosure design and roof strength before purchase.

Selection checklist for SK 3382.500

  • Total heat load of devices plus wall heat gain, against 0.6 kW at the right temperature point.
  • Roof space on the enclosure for a 597x417x380 mm unit and the height clearance above it.
  • Supply 230 V 1~ 50/60 Hz and the protection device rating given above.
  • Ambient range: the operating range is 10 °C to 55 °C and the table above gives the exact limits for each frequency.
  • Approvals listed: UL + C-UL (listed), UL + C-UL – FTTA.
  • Free air space around the condenser inlet and outlet.

Installation, commissioning and maintenance

Cut the roof opening with the supplied drilling template, remove burrs, fit the unit with the seal and assembly parts and make the connection through the plug-in terminal strip. The enclosure must be sealed, with doors closed and cable entries sealed, otherwise warm humid air will be drawn in and the unit will run continuously. Do not set the setpoint lower than needed, since a very low setpoint increases condensation and energy use. Keep the unit upright, and allow the compressor to stand before first start if it was transported at an angle.

Maintenance is mostly cleaning the condenser and filter areas, checking fans and checking the refrigerant circuit for leaks. Because the unit contains a fluorinated refrigerant, service work should be done by qualified staff under local rules. Keep a spare filter or fan assembly in your plant stores if downtime is expensive.

Typical applications in Oman and the GCC

Cooling units are common for electronics enclosures in hot-climate plants: drive panels, PLC and DCS cabinets, analyser shelters and switchgear control rooms in oil and gas, power and desalination facilities. High summer ambient and sun load are the main design cases, so always calculate with the highest ambient and not the average. In dusty areas a closed loop avoids filter clogging inside the enclosure, and in coastal sites check the housing and condenser for salt-laden air. The data sheet limits the maximum ambient for this unit as shown above; where ambient exceeds it, a different type or an air-conditioned room is needed.

Information to send with an RFQ for SK 3382.500

  • Part number SK 3382.500 and quantity.
  • Enclosure make, size and heat dissipation of its contents.
  • Maximum ambient temperature and required inside temperature.
  • Power supply available and frequency.
  • Delivery location and date.

Documents and quotation

The manufacturer data sheet for SK 3382.500 is attached on this page and lists the dimensions, materials and approvals for this article. Please check it against your drawings before ordering.

For a quotation send the part number SK 3382.500, the quantity, the delivery location in Oman or the GCC and any project requirements. Seven Star LLC will reply with availability and lead time.

Datasheets & Documents
  • PDF Datasheet Rittal SK 3382.500 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Rittal is a German manufacturer of enclosures, power distribution, climate control and IT infrastructure, founded in 1961 by Rudolf Loh in Rittershausen, Hesse, as Rudolf Loh Elektrogerätebau. In its first year it launched the first standard enclosure, built in series and available from stock instead of made to order. Rittal is headquartered in Herborn and belongs to the family-owned Friedhelm Loh Group.

Seven Star LLC is an independent supplier in Muscat. We list Rittal enclosures, cooling units and power distribution products for panel builders and maintenance teams in Oman and the GCC.

Rittal company profile

Founded 1961, Rittershausen (Dietzhölztal), Germany, by Rudolf Loh
Headquarters Herborn, Hesse, Germany
Ownership Friedhelm Loh Group (Loh family); sister companies include Eplan and Cideon
Idea Standard enclosures in series production, available from stock
Product families VX25 and AX/KX enclosures, TS 8 baying systems, Blue e+ cooling units and fan-and-filter units, RiLine busbar systems, IT racks and data centre modules

Milestones

  • 1961: Rudolf Loh founds the company and launches the first standard enclosure.
  • 1969: The company takes the Rittal name, according to Rittal.
  • 2021: Rittal marks 60 years.

Rittal product series

Enclosures include the TS 8 free-standing bayable system, AE compact enclosures such as the AE 1380.500 and AE 1034.500, and the CS outdoor wall-mounted enclosure. For hazardous areas there are the KEL 9404.600 stainless steel and AX 9206.100 plastic Ex enclosures. Power distribution is covered by the VX25 Ri4Power switchgear system and its 185 mm busbar system.

Climate control includes Blue e+ wall-mounted cooling units, the TopTherm Blue e SK 3273.500 roof-mounted unit and the LCP Inline CW liquid cooling package for IT racks.

Where Rittal products are used

Machine and process control panels, motor control and power distribution switchboards, outdoor telecom and utility cabinets, junction boxes in hazardous areas and IT racks. In the Gulf, cabinet cooling is often the deciding factor for reliable electronics.

Rittal products we list

Family Examples
Automation Accessories AE 1034.500 Compact Enclosure 300 x 400…, AE 1380.500 Compact Enclosure 380 x 380…, AX 9206.100 Ex Plastic Enclosure 600 x 6…, CS 9791.015 Outdoor Wall-Mounted Enclosure, KEL 9404.600 Ex Stainless Steel Enclosur…, VX25 Ri4Power 185 mm Busbar System, VX25 Ri4Power Switchgear and Power Distr…
Enclosure Climate Control Blue e+ Wall-Mounted Enclosure Cooling U…
Cooling SK 3273.500 TopTherm Blue e Roof-Mounted…
Switchgear, Enclosures & Distribution TS 8 Free-Standing Enclosure System

Ordering Rittal products: what we need

Rittal parts are ordered by a seven-digit model number such as 9404.600. Send that number, or the width, height and depth, material, protection category and door arrangement. For cooling units add the cooling output, rated voltage and mounting cut-out of the unit being replaced; for Ex enclosures, the zone and marking required.

Facts checked against Rittal's own company pages and Friedhelm Loh Group material, October 2026.

FAQ

Questions about the Rittal SK 3382.500 TopTherm Blue e Roof Cooling Unit

Answers from our engineering team on installation, compatibility and integration.

01What are the dimensions and weight of SK 3382.500?
The outer dimensions are 597x417x380 mm (width x height x depth) and the net weight is 36.1 kg according to the manufacturer data sheet. Always confirm clearances for doors, covers and cable entries on your drawing.
02What protection category does SK 3382.500 have?
The data sheet states IP 34 / IP 54 for this article. This describes protection against solid objects and water under the standard test conditions, and it only holds while doors, covers, seals and cable entries are correctly closed and fitted.
03What cooling output does SK 3382.500 have?
The data sheet gives the output at L35/L35 and 50 Hz as the figure in the title of this page, with lower values at higher inside temperatures. Size the unit using the maximum ambient and the total heat load, not only the headline number.
04Which documents are available for SK 3382.500?
The manufacturer data sheet for this article, with dimensions, materials and the approvals listed for it, is attached on this page. Send the part number with your RFQ if you need other documents and we will confirm what is available.
05Does Seven Star LLC supply SK 3382.500 in Oman?
Seven Star LLC is an independent supplier in Muscat serving customers in Oman and the GCC, and is not affiliated with the manufacturer. Send the part number SK 3382.500, quantity and delivery location, and we will respond with availability and lead time.