Brand:

Legrand 411097 DX3 1P+N 32 A RCBO 30 mA F Type

Description

411097: Legrand DX3 1P+N 32 A RCBO with F type 30 mA high immunity

The Legrand 411097 is a DX3 6000 residual current circuit breaker with overcurrent protection for one phase plus neutral (1P+N), 32 A, C curve, 30 mA, with F type residual detection. The F type is also classified as type A, and the catalogue calls it high immunity because it resists unwanted tripping and detects high-frequency fault currents. It is two modules wide, works at 230 V AC and has the neutral on the right-hand side. Seven Star LLC supplies 411097 in Oman and the GCC as an independent supplier in Muscat.

In a 1P+N device the phase pole provides overcurrent protection and isolation, while the neutral pole only isolates. The data sheet adds that the neutral contact closes before and opens after the phase contact, which is a safe sequence for a circuit with a residual current function.

Reading the 411097 description

Element Value Meaning
RCBO DX3 6000 Product Combined residual current and overcurrent device, 6 kA class
10 kA IEC 60947-2 breaking capacity 6 kA under EN 61009
1P+N Poles One protected phase pole and one neutral pole
32 A, curve C Overcurrent Magnetic trip between 5 and 10 x In
30 mA, F type Residual Type A plus immunity to unwanted tripping and high-frequency detection
Ref. 411097 Catalogue number Reference to quote

Technical specifications for 411097

Parameter Specification
Manufacturer / part number Legrand / 411097 (DX3 RCBO 6000, 1P+N, 32 A, C, 30 mA, type F)
Poles 2 total (1 protected phase pole plus neutral)
Rated current / curve 32 A / C
Rated residual current 30 mA, leakage type F (also type A)
Rated voltage / frequency 230 V AC, 50 Hz
Breaking capacity Icn 6 kA (EN 61009-1); 10 kA under IEC 60947-2
Current limiting class 3
Surge current capacity 3 kA
Anti-nuisance tripping version Yes
Width / built-in depth 2 modular spacings (35.6 mm) / 44 mm
Conductors Solid-core 0.75–16 mm²; multi-wire 0.75–10 mm²
Protection / pollution IP20, pollution degree 2
Compatibility Prong and fork busbars, DX3 signalling and remote-trip auxiliaries, motorised controls
Mounting 35 mm DIN rail

Why type F matters on 411097

A plain type A device handles AC and pulsating DC leakage, but modern single-phase equipment with frequency converters, switch-mode supplies and electronic power stages creates residual currents that mix several frequencies. The F type in 411097 is specified for additional immunity to unwanted tripping and for detection of high-frequency fault currents, which reduces nuisance trips on installations with electronic equipment and still protects at 30 mA.

The surge current capacity listed on the product page is 3 kA, far higher than the 0.25 kA of the plain type A and AC RCBOs, and the page flags the device as an anti-nuisance version. This is the main practical difference when a circuit includes long cables, lightning-prone supply or electronic loads that cause current spikes at switch-on.

Where 411097 fits and related parts

The device suits single-phase circuits for air-conditioning with inverter compressors, EV charge points on single-phase supplies, IT rooms and building services where electronic loads are present. The type A sibling with the same 1P+N body is 411053, which has the same rating and lower surge capacity. For double-pole switching, 411161 (2 pole, 32 A, AC) uses four modules. The data sheet lists current ratings from 3 to 40 A and AC, A and F types for this 1P+N family.

Selection checklist for 411097

  • Load: single-phase, up to 32 A, with electronic equipment likely to cause nuisance trips on an AC or A device.
  • Residual type: F, which also covers type A.
  • Sensitivity: 30 mA personal protection.
  • Fault level: 10 kA under IEC 60947-2, 6 kA under EN 61009.
  • Space: two modules (35.6 mm).
  • Wiring: neutral on the right-hand side; observe the terminal marking.

Installation, testing and maintenance of 411097

Fit the device on a DIN rail and connect phase and neutral to the correct terminals; the neutral is on the right. The terminals accept 0.75 to 16 mm² solid or 0.75 to 10 mm² flexible copper. Close the handle, press the test button to prove the residual function and record the date together with 411097 in the board schedule. A yellow indicator on the front shows a residual current trip. Test the device periodically, and replace it if it fails to trip on test.

Typical applications in Oman and the GCC

Inverter air-conditioners, commercial kitchens, data rooms and EV chargers are common in Oman and the GCC and rely on electronic power conversion. These loads justify an F-type RCBO where nuisance tripping would interrupt service. Keep the enclosure ventilated in hot weather and avoid mounting directly above heat-producing devices.

Information to send with an RFQ for 411097

  • Reference 411097 and the quantity, including spares for panel maintenance.
  • Rated current, curve and residual type (A or F).
  • Nature of the load, such as inverter equipment or EV charging.
  • Board layout and busbar type.
  • Delivery location (Muscat, Sohar, Salalah or elsewhere in the GCC) and the date you need the goods.
  • Any documents you need with the quotation, such as a technical data sheet or a compliance statement.

Storage, handling and spares for the Legrand 411097

Keep Legrand 411097 units in their original packaging until they are mounted. Store them indoors in a dry, dust-free room, away from direct sun and condensation. Panel shops in Oman and the GCC often hold stock in warehouses that get very hot in summer, so check that storage temperature stays within the limits given in the manufacturer datasheet.

  • Check the label and order code on every unit against the drawing before it goes into the panel.
  • Use the correct tool and tightening torque for the terminals, as given in the instructions supplied with the product.
  • Keep a small number of spare units for each rating used on site, so that a failed or damaged part can be replaced without waiting for a new shipment.
  • Record the order code in the panel documentation and the as-built drawings, so that maintenance teams can reorder the same part later.

When you plan spares for a project, group the Legrand 411097 with the other parts of the same panel in one RFQ. This keeps delivery dates aligned and makes it easier to confirm stock for the whole bill of materials at once.

Documents and quotation

The Legrand technical data sheet that covers 411097 is attached on this page. It gives the range table, dimensions, curves and accessories, so check its notes against your design before you order.

To request a quotation, send reference 411097, the quantity and your delivery location. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer; we will confirm availability and lead time for your order.

Other Models in the Legrand Dx3 Rcbo 1pn Range

Seven Star LLC supplies models from the Legrand Dx3 Rcbo 1pn range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Legrand 411097 DX3 1P+N 32 A RCBO 30 mA F TypeCircuit BreakersYou are viewing this model
Legrand 411053 DX3 1P+N 32 A RCBO 30 mA Type ACircuit BreakersView details
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Legrand is a French maker of electrical and digital building infrastructure, headquartered in Limoges. Its roots lie in a nineteenth-century porcelain workshop in Limoges, and it grew into one of the largest makers of wiring devices, circuit protection, cable management and data centre products. Legrand is listed on Euronext Paris and sells under brands including Legrand, Bticino and Cablofil.

Seven Star LLC, an independent supplier in Muscat, lists Legrand circuit breakers for electrical contractors and panel builders in Oman and the GCC, at present a DX3 4-pole miniature circuit breaker rated C32.

Legrand company profile

Headquarters Limoges, France
Listing Euronext Paris
Brands Legrand, Bticino, Cablofil, Zucchini
Product families DX3 miniature circuit breakers and RCDs, wiring devices, cable trays, busbar trunking, UPS

Legrand DX3 circuit breakers

DX3 is the Legrand family of modular protection devices for DIN rail mounting. The item on our site is a 4-pole MCB with a C tripping curve and a 32 A rated current. Three things besides the pole count define a breaker of this kind: the curve, the rated current and the breaking capacity printed on the front. Legrand catalogs DX3 breakers in 6000 A and 10000 A versions under separate references.

Ordering Legrand breakers: what we need

Send the Legrand catalog number printed on the device, a six-digit reference, where it is legible. Otherwise give the number of poles, the curve, the rated current, the breaking capacity and the voltage. Mention any auxiliary contact or residual current add-on module fitted beside the breaker, and the board type.

Facts checked against Legrand's published corporate information, October 2026.

FAQ

Questions about the Legrand 411097 DX3 1P+N 32 A RCBO 30 mA F Type

Answers from our engineering team on installation, compatibility and integration.

01What is 411097?
It is a Legrand DX3 6000 RCBO for one phase plus neutral, 32 A, C curve, 30 mA, F type with high immunity to unwanted tripping, two modules wide, for 230 V AC.
02What does F type mean for 411097?
Type F is also a type A device, with additional immunity to unwanted tripping and detection of high-frequency fault currents, a profile that suits electronic loads.
03What surge current withstand does 411097 have?
The product page lists a surge current capacity of 3 kA and marks the device as an anti-nuisance version, compared with 0.25 kA on the plain type A RCBO.
04Which conductors does 411097 accept?
The terminals take 0.75 to 16 mm² solid-core and 0.75 to 10 mm² multi-wire copper, and the device fits prong and fork busbars.
05How do the poles of 411097 work?
The phase pole provides overcurrent protection and isolation, while the neutral pole gives isolation only; the neutral contact closes before and opens after the phase contact.