Lovato VLB30007A480 0.75 kW VLB3 Variable Speed Drive

Description

0.75 kW VLB3 variable speed drive for three-phase supply

VLB30007A480 is a VLB3 variable speed drive: 0.75 kW (1 (heavy load) HP), 2.4 A continuous output, three-phase input at 400-480VAC 50/60Hz. The output frequency range is 0-599 Hz, which covers standard 50 and 60 Hz motors and higher-speed spindles.

Radio-frequency interference is handled by the built-in EMC suppressor cat. C1/C2 inside the housing, and the serial port is RS485, Modbus-RTU.

Overload capacity is 150% for 60s; 200% for 3s, with a switching frequency of 2-16kHz.

Technical specifications

Parameter Specification
Order code VLB30007A480
Product designation Variable speed drives
Product type designation VLB3
Rated power supply voltage 400-480VAC 50/60Hz
Rated output voltage Three-phase 0-480VAC 0-599Hz
Rated output current 2.4 A
Rated output power 0.75 kW
Rated output power (General characteristics) 1 (heavy load) HP
EMC filter Built-in EMC suppressor cat. C1/C2
Communication port RS485, Modbus-RTU
Input type Three-phase
Rated mains voltage 400-480 VAC
Operating mains voltage range 340-528 VAC
Rated mains frequency 50/60 Hz
Operating mains frequency range 45-65 Hz
Rated mains current without mains choke 3.3
Rated mains current with mains choke 2.6
Output type Three-phase
Output voltage range 0-480 VAC
Output frequency range 0-599 Hz
Current overload 150% for 60s; 200% for 3s %/s
Apparent output power 1.6 (heavy load)
Power loss 4kHz: 32W (heavy load)
Brake chopper Yes
Switching frequency 2-16kHz
Motor control modes V/f linear, quadratic torque, sensorless vector control, ECO mode, servo control with encoder feedback, multipoint V/f curve, V/f closed loop control with encoder feedback, torque setpoint, sensorless
Speed reference signals External potentiometer 0-10kΩ Voltage signals: 0-10VDC or -10-+10VDC Current signals: 0/4-20mA Buttons on front keyboard Door-mount installation kit 15 preset speeds via digital inputs Motor potentiom
PID control Yes, with sleep and rinse function
Safe torque Off (STO) safety function Optional
Protections Overcurrent Output short circuit and earth/ground leakage Overvoltage Undervoltage Phase loss Motor heat overload (i2t) Overspeed Speed reverse
Special funct. Multi-pump PID control (1 main pump frequency regulated + 2 auxiliary pumps activated in direct mode in case of necessity)
Number of digital input 5
Digital input type Selectable PNP or NPN logic
Number of digital output 2
Digital output arrangement 1 relay output with changeover contact (C/O-SPDT) + 1 digital output
Output contacts ratings Relay output: 3A 250VAC Digital output: 100mA max 30VDC
Number of analog input 2
Analog input type Configurable 0/2-10VDC, -10-+10VDC, 0-5VDC, 0/4-20mA
Number of analog output 1
Analog output type configurable as 0-10VDC, 0-5VDC, 2-10VDC, 0/4-20mA
Operating temperature (min) -10 °C
Operating temperature (max) +55 °C
Current derating Switching frequency 2 or 4kHz: 2.5%/°C over 45°C switching frequency 8 or 16kHz: 2.5%/°C over 40°C
Storage temperature (min) -25 °C
Storage temperature (max) +60 °C
Relative humidity 5-95% (with no condensing)
Max altitude 4000m (over 1000m derate the rated current by 5%/1000m)
Maximum Pollution degree 2
Overvoltage category III up to 2000m altitude (II above 2000m)
Installation position Vertical
IP degree of protection IP20
Dimensions (W x H x D) 60 x 214 x 130 mm
Weight 1.1 Kg

Sizing and selection

For a motor whose nameplate current is at or below 2.4 A, this rating is the right size. The supply must be 400-480VAC 50/60Hz; the datasheet lists 3.3 A input current without a choke for protective-device sizing.

Control modes listed: V/f linear, quadratic torque, sensorless vector control, ECO mode, servo control with encoder feedback, multipoint V/f curve, V/f closed loop control with encoder feedback, torque setpoint, sensorless.

A brake chopper is built in and the safe-torque-off function is optional.

Applications and installation

Common applications include booster and circulation pumps, ventilation fans, conveyors and small process machines. On long motor cables an output filter or a different EMC category may be needed; the datasheet table of maximum cable length by category is the reference.

Dimensions of 60 x 214 x 130 mm and a mass of 1.1 Kg make this a panel-friendly size. Protection is IP20, so place it in an enclosure suited to the environment and keep motor and control cables separated.

Key features that set the VLB3 apart

  • Wide choice of control modes: from simple linear or quadratic V/f to sensorless vector and encoder-based closed loop, so the same drive model can serve a fan today and a positioning conveyor tomorrow.
  • Built-in brake chopper: with an external braking resistor, the drive can dissipate regenerative energy from high-inertia or overhauling loads instead of tripping on overvoltage.
  • Integrated C1/C2 EMC suppressor: reduces conducted emissions without a separate filter box in most panel layouts.
  • RS485 Modbus-RTU as standard: start, stop, speed reference and diagnostics can be handled over two wires from a PLC or SCADA system.
  • Tolerant input range: operation from 340 to 528 VAC and 45 to 65 Hz accommodates weak networks and generator supplies.

Mains choke: when it is worth adding

The data shows input current falling from 3.3 A without a mains choke to 2.6 A with one. That reduction reflects lower harmonic current drawn from the supply. A choke is worth considering where many drives share one transformer, where the supply is a generator, or where the network is known to carry voltage spikes; it also tends to extend the life of the drive’s DC-link capacitors. On a small single installation with a stiff supply it is often optional.

Commissioning tips

Enter the motor nameplate data first, then choose the control mode that suits the load: quadratic torque or ECO mode for pumps and fans, sensorless vector where good torque is needed at low speed. Set acceleration and deceleration ramps to match the mechanics; if short stopping times are required, size and connect a braking resistor to the chopper terminals. Configure the speed reference source, whether a 0-10 V signal, 4-20 mA loop, keypad or Modbus, and test the stop function before handing over the machine.

Switching frequency and motor noise

A higher carrier frequency within the 2-16 kHz range makes the motor quieter, but increases losses in the drive and can increase leakage current through long motor cables. The 32 W loss value is quoted at 4 kHz; if a higher setting is used, check the derating curves in the Lovato manual, especially in a warm cabinet.

Considerations for GCC installations

Water treatment plants, HVAC systems and small industrial lines in Oman and the wider Gulf often place drives in enclosures that see high summer temperatures. Allow for ventilation or panel cooling, keep the heat sink clean of dust, and confirm the cabinet temperature stays within the drive’s rated range. Where long motor cables run to submersible or remote pumps, an output filter may be needed to protect motor insulation.

Details to include in a quotation request

  • Order code VLB30007A480 and the quantity required.
  • Optional items: mains choke, braking resistor, remote keypad or communication modules.
  • Motor data and type of load, if you want the size confirmed.
  • Delivery location and required date.

Documents and quotation

A copy of the manufacturer’s datasheet for VLB30007A480, exported from the Lovato Electric catalogue in English, is attached to this page; every figure in the table comes from it. Ordering checklist: the motor nameplate current, the supply type and voltage, the EMC category needed for your cable lengths and whether a keypad or safe-torque-off option is required. Data in the datasheet is subject to change by the manufacturer. For related parts browse ac drives. Send the order code VLB30007A480, the quantity and the delivery location through the quotation form and Seven Star LLC, an independent supplier in Muscat, will reply with availability.

Datasheets & Documents
  • PDF Datasheet Lovato Electric VLB30007A480 datasheet (EN, catalogue export) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is an Italian manufacturer of low-voltage electrical equipment for industrial and building applications, founded in 1922 in Bergamo and still owned by the founding family. Its products cover motor control and protection, automation, energy measurement and stand-by power management.

Seven Star LLC is an independent supplier in Muscat. We list Lovato Electric contactors, soft starters, drives, controllers and meters for panel builders, maintenance teams and generator packagers in Oman and the GCC.

Lovato Electric product series

On the motor side, the range includes BF series three-pole contactors with AC or DC coils, SM1P motor protection circuit breakers, ADXT and ADXL soft starters (the ADXL with built-in bypass) and VLB3 variable speed drives for small motors. For control panels there are 31L multifunction time relays, LRD micro PLCs and DIN rail auxiliaries.

Energy and power management products include the DCRG8 and DCRL8 automatic power factor controllers for capacitor banks, the DMG digital multimeters and DMED direct-connected energy meters, the RGK600 automatic mains failure gen-set controller and the ATL600 automatic transfer switch controller for two-source systems.

Where Lovato Electric devices are used

Motor control centres and pump panels, HVAC and building services switchboards, power factor correction panels, generator control panels and changeover panels, and compact machine control cabinets. The power factor and transfer controllers are common in commercial buildings and industrial sites that run diesel stand-by sets.

Ordering Lovato Electric products: what we need

Send the complete order code, for example BF0910A230, which includes the coil voltage or supply variant. For soft starters and drives, also give the motor power, current and supply voltage; for power factor controllers, the number of steps and the CT ratio; for generator and transfer controllers, the engine interface and the communication option needed. State the quantity and any approval required for the project.

Frequently Asked Questions

What power and current does the VLB30007A480 deliver?
0.75 kW (1 (heavy load) HP) at 2.4 A output current, from a supply of 400-480VAC 50/60Hz.
Is the supply single-phase or three-phase?
The datasheet lists the input type as three-phase with rated mains voltage 400-480VAC 50/60Hz.
Does the VLB30007A480 have an EMC filter?
It is listed with Built-in EMC suppressor cat. C1/C2.
Which communication port does it have?
RS485, Modbus-RTU.
What is the overload capacity?
150% for 60s; 200% for 3s.