- Automation & ControlView all 3,009 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Katronic
Katronic KATflow 150 Advanced Clamp-On Ultrasonic Flowmeter
Description
Overview
When one flowmeter has to serve water mains, hot oil lines, HVAC loops and heat metering without a different model for each, the Katronic KATflow 150 is the instrument Katronic points to. It is described by the maker as its premier product for flexibility and performance: a wall-mounted clamp-on ultrasonic transit-time flowmeter with one or two measurement channels, a pipe range of 10 to 6,500 mm and up to ten input or output slots. Seven Star LLC is an independent supplier serving Oman and the GCC.
What the Katronic KATflow 150 measures
Two clamp-on sensors on the outside of the pipe send ultrasonic pulses alternately with and against the flow, and the difference in transit time gives the velocity. The meter covers 0.01 to 25 m/s with a resolution of 0.25 mm/s and repeatability of 0.15 percent of measured value plus or minus 0.015 m/s. Accuracy is plus or minus 1 to 3 percent of measured value depending on the application, improving to plus or minus 0.5 percent with process calibration. Gaseous and solid content of the liquid should stay under 10 percent of volume.
Specification of Katronic KATflow 150
| Parameter | Datasheet value |
|---|---|
| Pipe diameter range | 10 mm to 6,500 mm |
| Sensor temperature range | minus 30 to plus 250 degrees C (higher on request) |
| Flow velocity | 0.01 to 25 m/s |
| Turn down ratio | 1/100 |
| Measurement rate | 1 Hz standard; response 1 s, optional 90 ms |
| Channels | 1 or 2, with sum, average, difference and maximum functions |
| Enclosure | Wall mounted polycarbonate (UL94 V-0), IP 66 |
| Dimensions and weight | 237 x 258 x 146 mm (H x W x D), about 2.3 kg |
| Display | Backlit LCD graphic, 128 x 64 dots |
| Power supply | 100 to 240 V AC, 50/60 Hz, or 9 to 36 V DC; under 10 W |
| Operating temperature | minus 10 to plus 60 degrees C |
| Communication | RS 232, optional USB, RS 485, Modbus RTU, HART compatible, Profibus PA |
| Outputs | 0/4-20 mA, open collector, 2 relays, 0-10 V, frequency 2 Hz to 10 kHz |
| Data logger | About 30,000 or 100,000 measurements |
| ATEX enclosure | Additional enclosure, II 2G/D Ex d IIB T4 to T6 IP67, CESI 01 ATEX 063 |
How the Katronic KATflow 150 differs from the KATflow 180 and the portable models
The KATflow 180 is the gas-only version with an Ex-capable aluminium housing, a single channel and velocities up to 75 m/s. The KATflow 150 is a general liquid meter with dual-channel capability, an optional heat quantity function and a polycarbonate housing weighing about 2.3 kg. Where the Ex requirement exists, the 150 is placed in an additional wall-mounted ATEX enclosure of cast alloy, 358 x 278 x 218 mm, which brings the system weight to about 20 kg. Portable KATflow models trade the fixed housing for a carry case.
Applications in Oman and the GCC
The datasheet lists HVAC measurements, large pipes using two sensor pairs in X configuration, product recognition and interface detection, ATEX measurements with Ex-certified transducers, effluent and wastewater, and automated process control. In the Gulf these cover district cooling plants, desalination and water transmission, refinery and tank farm lines, and wastewater works, where cutting into a large pipe is costly or unwelcome.
Options and accessories
Options include PT100 transducers or analogue temperature inputs for heat quantity measurement and temperature compensation, a secondary ATEX enclosure, a sound velocity output function, and the KATdata+ software for downloading and evaluating logged data. Current inputs allow pressure and density compensation. Hazardous area transducers K1Ex and K4Ex cover 50 to 3,000 mm and 10 to 250 mm pipes respectively, with stainless steel heads.
Installation and commissioning
Select the transducer type from the pipe size and fluid temperature, mount it with couplant at the spacing shown by the meter, route the cables to the wall-mounted housing and power up. Enter pipe and fluid data, check the signal level and compare velocity with the expected value. Use the data logger to record a trial period before final acceptance.
Maintenance
With nothing in contact with the fluid, upkeep consists of inspecting cables, glands and the transducer coupling, and downloading logs. Recouple or re-seat a sensor if the signal quality falls.
Heat metering with the KATflow 150
With the optional heat quantity function and two PT100 sensors on the supply and return pipes, the meter measures energy flow in W, kW and MW, and quantity in J, kJ and kWh. This is helpful for chilled water and hot water circuits in large Gulf buildings, where billing or efficiency monitoring needs a retrofit meter without shutting down the loop.
Choosing sensors and mounting arrangement
A fixed installation is best served by the transducer type selected for the pipe diameter and the fluid temperature, up to 250 degrees C as standard. For small pipes, use the reflect arrangement with both sensors on one side, and on large pipes, use the diagonal arrangement across the diameter, or two sensor pairs in an X configuration to average out flow profile effects. Straight pipe lengths upstream and downstream improve the result, and the meter informs the user about the spacing needed. For liquids with a lot of gas bubbles or suspended solids, keep under the 10 percent of volume limit, or the signal will weaken.
Fit the transducer cables into conduit or tray in outdoor routes to protect them from sun and mechanical damage.
Data logging and software
The built-in logger stores about 30,000 or 100,000 measurements, each with up to ten selectable measurement units, so a trial run can capture flow, totals and temperatures over days. The KATdata+ software downloads measured values and parameter sets, shows them in graphs or lists, exports to third-party programs and can transfer data online. The meter displays flow in cubic metres, litres, US gallons or barrels per hour, minute or day, and totals in the matching volume or mass units, which suits oil and water duties alike.
Ordering notes for Katronic KATflow 150
State the pipe data, the fluid, the temperature, the number of channels, the power supply, the outputs and any ATEX needs. Transducers are selected for the pipe and fluid.
Related items you may also need: Katronic KATflow 200 Hand-Held Clamp-On Ultrasonic Flow Meter | Katronic KATflow 170 Explosion-Proof Clamp-On Ultrasonic Flow Meter | Katronic KATflow 100 Clamp-On Ultrasonic Flow Meter | All Katronic products.
Documents and quotation
The manufacturer datasheet for the Katronic KATflow 150 is attached to this page. Send your RFQ with the model, configuration, quantity and delivery location in Oman or the GCC.
Datasheets & Documents
- Datasheet Katronic KATflow 150 Advanced Clamp-On Ultrasonic Flowmeter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Katronic Technologies is a British manufacturer of clamp-on ultrasonic flow meters, based in Coventry. Founded in 1996 as a distributor of process measurement instruments with a focus on ultrasonics, it went on to design and make its own KATflow range. Its fixed, portable and explosion-proof meters measure liquid flow from outside the pipe.
Seven Star LLC is an independent supplier in Muscat. We list Katronic flowmeters for water, process and HVAC users in Oman and the GCC.
Katronic company profile
| Founded | 1996, England |
|---|---|
| Headquarters | Coventry, England |
| Technology | Clamp-on transit-time ultrasonic |
| Product families | KATflow 100 and 150 fixed meters, KATflow 170 explosion-proof meters, KATflow 200 and 230 portable meters |
Katronic product series
Fixed meters include the KATflow 100 clamp-on meter and the KATflow 170 explosion-proof meter.
Portable meters include the KATflow 200 hand-held meter and the KATflow 230 dual-channel meter.
Clamp-on meters measure flow from outside the pipe using transit-time ultrasound, so there is no pressure drop and no need to stop the process. Accuracy depends on the pipe data, straight run and transducer mounting.
Portable meters are used for flow surveys and checking fixed meters, while fixed meters provide continuous measurement with outputs to control systems.
Where Katronic flowmeters are used
Flow measurement without cutting the pipe in water networks, chilled water, process lines, hydrocarbons and flow surveys.
Katronic products we list
| Family | Examples |
|---|---|
| Flowmeters | KATflow 100 Clamp-On Ultrasonic Flow Meter, KATflow 170 Explosion-Proof Clamp-On Ult…, KATflow 200 Hand-Held Clamp-On Ultrasoni…, KATflow 230 Portable Dual-Channel Clamp-… |
Ordering Katronic flowmeters: what we need
Send the model, pipe size and material, liquid, temperature, outputs and any hazardous-area needs.
Facts checked against Katronic directory listings and WWEM exhibitor profile, October 2026.
Browse Katronic products by category: Flowmeters.
FAQ
Questions about the Katronic KATflow 150 Advanced Clamp-On Ultrasonic
Answers from our engineering team on installation, compatibility and integration.
01What pipe sizes can the Katronic KATflow 150 measure?
It measures pipes from 10 mm to 6,500 mm in diameter, using clamp-on transducers with a temperature range of minus 30 to plus 250 degrees C.
02How many channels does the Katronic KATflow 150 have?
It has one or two measurement channels, with sum, average, difference and maximum calculations when used in dual-channel mode.
03How accurate is the Katronic KATflow 150?
Volume flow accuracy is plus or minus 1 to 3 percent of measured value, or plus or minus 0.5 percent with process calibration.
04Can the Katronic KATflow 150 be used in hazardous areas?
Yes, with an additional ATEX enclosure (II 2G/D Ex d IIB T4 to T6) and Ex-certified transducers such as the K1Ex and K4Ex.
05What outputs and communication does the Katronic KATflow 150 offer?
Current, open collector, relay, voltage and frequency outputs, plus RS 485, Modbus RTU, Profibus PA and HART compatible options.


















Reviews
There are no reviews yet.