pFlow GFCL Ultrasonic Flowmeter for HVAC Systems

Description

Overview

The pFlow GFCL Ultrasonic Flowmeter is a non-invasive device that uses the transit-time method to measure flow rates accurately across the full range of HVAC system water circuits, from chilled water and heating water loops to cooling towers and air handling units. Its integrated external clamping structure enables easy installation without breaking pipelines, giving building services engineers a fast, accurate way to bring flow visibility to existing HVAC infrastructure.

As the official authorized partner and exclusive regional representative for pFlow Gentos, Seven Star LLC proudly supplies the GFCL to HVAC contractors, building automation integrators, and facilities management teams across the Sultanate of Oman, Muscat, and the wider GCC. Its versatility across chilled water, heating water, and cooling tower applications makes it a practical all-around choice for HVAC energy management projects.

Measurement Principle

The pFlow GFCL measures flow using the ultrasonic transit-time method, achieving 2.0% accuracy with 0.4% repeatability across a flow velocity range of 0.03m/s to 5.0m/s, corresponding to a flow range of 0.02 to 35 m³/h. Because the transducer clamps onto the pipe exterior, the GFCL avoids introducing any pressure drop or obstruction into HVAC circuits, keeping cooling and heating systems fully operational during installation.

This non-invasive principle supports a wide range of HVAC monitoring functions: chilled water flow monitoring ensures the cooling system operates efficiently; heating water flow measurement improves energy efficiency and reliability in hot water systems; and cooling tower water management tracks water entering and exiting the tower to optimize heat dissipation.

Engineering Design of the pFlow GFCL

The pFlow GFCL is built as an all-in-one transmitter paired with a clamp-on transducer, connected via a 5mm six-core shielded cable with a standard 4-meter length. The enclosure uses PC (polycarbonate) material with an aluminum alloy pipe clamp, and the unit carries an IP54 rating for reliable operation in mechanical rooms and plant spaces.

A 1.54-inch TFT-LCD colorful display with 240×240 resolution and three touch keys provide clear readings and straightforward field configuration. Communication is handled via RS485, supporting both FUJI and MODBUS protocols alongside a standard 4–20mA output, giving HVAC control system integrators flexibility when connecting the GFCL into building management platforms for energy management and cost analysis over time.

Key Features

The pFlow GFCL combines precise HVAC flow measurement with flexible connectivity. Core capabilities include:

  • Non-invasive clamp-on installation with no pipe cutting for DN15 to DN50 pipes.
  • 2.0% measurement accuracy with 0.4% repeatability for reliable HVAC monitoring.
  • RS485 communication supporting both FUJI and MODBUS protocols, plus 4–20mA output.
  • 1.54-inch TFT-LCD colorful display with 240×240 resolution for clear field readings.
  • Compatible with stainless steel, copper, PVC, and PPR pipe materials.
  • Suitable for chilled water, heating water, cooling tower, and AHU flow monitoring.
  • Pump performance monitoring capability when installed on discharge lines.
  • Supports energy management and cost analysis through integration with BMS platforms.
  • rn t

  • Standard 4-meter cable length between transmitter and transducer for flexible mounting.

Industrial Applications

The pFlow GFCL is engineered for the full range of HVAC water flow monitoring needs across Oman’s commercial and institutional building stock, including chilled water systems, heating water loops, cooling towers, air handling units, and heat exchangers. Its ability to optimize heat transfer processes and monitor pump performance makes it a valuable tool for facilities teams seeking to improve HVAC energy efficiency.

As the officially authorized partner for pFlow Gentos, Seven Star LLC distributes the GFCL to building automation projects, process industries including chemical, pharmaceutical, and food and beverage facilities, and energy management programs throughout the Sohar and Salalah economic zones and the broader GCC region.

Technical Specifications

Full technical parameters for the pFlow GFCL ultrasonic flowmeter:

Parameter Specification
Model pFlow GFCL
Measurement Principle Ultrasonic Transit-Time, Clamp-on
Velocity Range 0.03m/s to 5.0m/s
Accuracy 2.0%
Repeatability 0.4%
Pipe Size DN15, DN20, DN25, DN32, DN40, DN50
Pipe Material Stainless Steel, Copper, PVC, PPR
Communication RS485 (FUJI & MODBUS Protocol), 4–20mA
Display 1.54-inch TFT-LCD Colorful Display, 240×240
Fluid Temperature 0°C to 60°C
Enclosure Rating IP54, PC Body with Aluminum Alloy Clamp

Why Choose Seven Star LLC for HVAC Flow Metering

HVAC retrofits across Oman’s commercial building stock often involve multiple flow points spread across chilled water, heating water, and cooling tower circuits, each potentially needing a different protocol to integrate with the building’s existing BMS. Seven Star LLC’s engineers confirm whether a project’s control system expects FUJI or standard MODBUS communication before the GFCL ships, avoiding a protocol mismatch that would otherwise surface only during commissioning.

As the authorized regional partner for pFlow Gentos, we also help facilities management teams plan multi-point GFCL rollouts across chilled water, heating water, and cooling tower circuits in a single building, and can coordinate bulk orders for developments standardizing HVAC energy monitoring across Muscat, Sohar, and the wider GCC, and can advise on which flow points within a building deliver the most useful energy-management data for a given retrofit budget.

Request a Quote for pFlow GFCL Ultrasonic Flowmeter for HVAC Systems

To submit a formal Request for Quote (RFQ), check current availability and lead time, or request complete technical datasheets for the pFlow GFCL Ultrasonic Flowmeter for HVAC Systems, please contact the official instrumentation division at Seven Star LLC today. As the authorized partner for pFlow Gentos in Oman and the GCC, our engineers are ready to assist with commercial sourcing and HVAC flow metering integration.

Related Products

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Clamp-on ultrasonic flow measurement is what pFlow does. The sensors strap to the outside of the pipe and measure liquid flow by transit time, so the line is not cut and nothing touches the fluid. The brand comes from Gentos, an instrument maker focused on ultrasonic flowmeters, flow sensors and heat and cooling energy meters.

Seven Star LLC is the pFlow agency for Oman and the GCC, listing pFlow ultrasonic flowmeters in fixed, portable and LoRaWAN versions, BTU meters and LoRaWAN flow control valves.

pFlow flowmeter families

Most of the listed models are compact clamp-on sensors grouped by pipe size and duty. The GF family (GFCL, GFR, GF-S-CL, GF-SH-CL for hot water and GF-GH-CL for immersion cooling) and the MF micro flowmeters (MFR, MFCL) serve cooling and process loops on small and medium pipes. The MP series are plug-and-play flow sensors, including the MP801 and a LoRaWAN version. The D116-BTU is a wall-mounted ultrasonic BTU meter, the P116 a portable flowmeter for surveys, and the F8 a fixed meter used in aquaculture. Gentos also builds the F3 series clip-on flowmeters, including a panel-mount version. The VC200-R is a LoRaWAN ball valve that works as a flow switch.

Where pFlow meters are used

The manufacturer documents use in liquid cooling for data centers and semiconductor plants, chilled and hot water metering in central air conditioning, water supply networks and irrigation, aquaculture, and utility lines in petrochemical and power plants.

Ordering a pFlow ultrasonic flowmeter: what we need

Clamp-on meters are selected from pipe data. Send the pipe outside diameter, wall thickness and material, any liner, the liquid and its temperature, the expected flow span and the straight pipe length available. Add the output you need (4-20 mA, pulse, Modbus, LoRaWAN) and the supply voltage. For BTU meters include the supply and return temperature span.

FAQ

Questions about the pFlow GFCL Ultrasonic Flowmeter for HVAC Systems

Answers from our engineering team on installation, compatibility and integration.

01What HVAC applications is the pFlow GFCL designed for?
The GFCL is designed for chilled water flow monitoring, heating water measurement, cooling tower water management, air handling unit flow monitoring, and heat exchanger optimization.
02Does the GFCL require cutting the pipe to install?
No. The GFCL uses a non-invasive clamp-on installation that avoids breaking pipelines, keeping HVAC systems fully operational during installation.
03What communication protocols does the GFCL support?
The GFCL communicates via RS485, supporting both FUJI and MODBUS protocols, alongside a standard 4-20mA analog output.
04What accuracy does the GFCL provide?
The GFCL delivers 2.0% measurement accuracy with 0.4% repeatability across a flow velocity range of 0.03m/s to 5.0m/s.
05Is Seven Star LLC an authorized representative for pFlow products?
Yes. Seven Star LLC is the officially authorized partner and exclusive regional representative for pFlow Gentos in Oman and the GCC, supplying genuine products with local technical support.