- Automation & ControlView all 3,184 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Encoders
- Motor Soft Starters
- CCTV & Security
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Bürkert
Bürkert 131425 Type 6519 NAMUR Solenoid Valve 24 V DC
Description
Overview
Bürkert 131425 is a Type 6519 pilot-operated NAMUR solenoid valve for pneumatic actuators, built with stainless steel socket bushings, a 6 millimetre orifice and a 24 V DC coil of 2 watts. In one article it covers two jobs: with the supplied changeover plate it works as a 5/2-way or a 3/2-way valve, so the same part number can drive a double-acting actuator or a single-acting spring-return actuator directly on the NAMUR interface.
What Bürkert 131425 does in an actuator package
Process valves with quarter-turn actuators, such as ball and butterfly valves, normally carry a NAMUR pattern on the actuator housing. A NAMUR solenoid mounts straight on that flange so that the working ports 2 and 4 connect to the actuator without tubing, which shortens installation time and removes leak points. The body is made from high-quality polyamide, the seal materials are NBR and PUR, and the design works without continuous air consumption: the pilot stage does the switching work, so the coil stays small and the power consumption stays low.
The data sheet gives a flow value QNn of 900 litres per minute for the 6 mm orifice, measured at 20 degrees Celsius with 6 bar at the inlet and 1 bar differential pressure. Pressure range is 2 to 10 bar, from overpressure to atmosphere, and the valve is serviced by the standard pilot principle where a minimum pressure is needed to shift the main spool.
Bürkert 131425 technical table
| Parameter | Value |
|---|---|
| Article number | Bürkert 131425 |
| Type | 6519 pilot-operated NAMUR valve |
| Circuit function | W: 5/2 or 3/2 with changeover plate |
| Orifice | 6 mm |
| Flow QNn | 900 l/min |
| Operating voltage | 24 V DC |
| Nominal power | 2 W (DC hold about 1.7 W for the 24.5 mm coil) |
| Pressure range | 2 to 10 bar |
| Seal | NBR and PUR |
| Socket material | Stainless steel |
| Electrical connection | Plug contacts form A according to DIN EN 175301-803, plug ordered separately |
| Pneumatic connection | G ¼ supply ports 1, 3, 5, NAMUR flange for ports 2 and 4 |
| Medium temperature | -10 to +55 °C |
| Ambient temperature | -25 to +55 °C |
| Switching times | Opening about 20 ms, closing about 40 ms |
| Manual override | Included |
| Weight | About 320 g (24.5 mm coil) or 476 g (32 mm coil) |
How 131425 differs from other 6519 variants
Twin articles of Bürkert 131425 on other supply voltages are 131426 for 24 V AC at 50 or 60 Hz, 131427 for 110 V AC and 131428 for 230 V AC, all with the stainless steel sockets. The nickel-plated brass family of the same NAMUR valve uses numbers 131421 to 131424. The G ¼ standard-body Type 6519 valves, for example 132465, are the larger 8 mm orifice servo valves with a flow of 1300 litres per minute and a 5/2 function, and the Ex mb and Ex eb mb coils change the approval class for hazardous zones while the body stays identical. Type 6518, the 3/2-way companion of the series, covers only single-acting duties.
Applications in Oman and the GCC
Actuated valves in water treatment, desalination, power plants, petrochemical utilities and food plants all use NAMUR solenoids. The stainless steel sockets in this article suit corrosive coastal air better than brass and are often specified for outdoor skids. With a SIL 2 capable circuit function for monostable use, the series also supports safety functions on emergency isolation valves, depending on the architecture of the whole safety loop.
Selection and compatibility
- Check that the actuator has a NAMUR interface and that its air volume suits a 900 litre per minute valve
- Choose 24 V DC for PLC output cards, with a current of about 0.08 A at 2 W
- Order the DIN EN 175301-803 form A cable plug separately; Type 2518 is the cable plug named in the data sheet
- Verify the air quality: filtered, dry, with or without oil mist as stated in the manual
- Decide whether the valve will be used in circuit function C or H, and place the changeover plate accordingly
Installation and commissioning
Place the gasket on the NAMUR face, set the valve on the actuator and tighten with the screws. Connect the compressed air to port 1, check that the exhaust ports 3 and 5 are open or fitted with silencers, and connect the cable plug. Operate the manual override once to confirm that the actuator moves and that the position indicator is correct before turning on the electrical supply.
Keep supply tubing short and of adequate diameter, because small tubing slows down actuator travel and eliminates the benefit of the high flow of the valve.
Safety and hazardous-area notes
The data sheet states that the monostable circuit functions C, D and H can reach a safety level of SIL 2 under IEC 61508, depending on the architecture of the safety system, so the same valve family is used on shutdown valves as well as on ordinary control valves. The standard coil of this article carries no explosion protection; if the valve must sit in a classified zone, the Ex mb or Ex eb mb coils of the series replace the standard coil on the identical body and have their own approvals, for instance ATEX and IECEx for gas group IIC. The change of coil is simple because the coil plugs over the valve housing and can be locked in four positions offset by 90 degrees.
Observe the permitted temperature class when a hazardous-area coil is used: the medium temperature must stay at least 5 kelvin below the class limit, which is 135 degrees Celsius for T4, 100 for T5 and 85 for T6. For the standard coil of this article the medium limit is plus 55 degrees Celsius, which is lower than any class limit and is therefore the governing value.
Typical wiring and control
A single output of a PLC card switches the coil. With a 24 V DC coil of 2 W the current is below 0.1 A, so almost any output card can drive it directly. Surge suppression is built into the plug versions of the cable plugs; where a plain plug is used, add a diode or varistor across the coil to protect the output stage. Group several valves on a manifold if a cabinet with many actuators is planned; the series allows single or manifold mounting, which reduces tubing and saves cabinet space.
Pneumatic supply planning
- Use a supply pressure between 2 and 10 bar and set the regulator for the actuator spring and torque need
- Pick the tubing diameter to match the high flow of the valve; narrow tubing throttles the actuator
- Fit silencers on exhaust ports, with a restrictor if you want slower actuator motion
- Protect from dirt by using a filter of 40 micrometres or finer as recommended by the manual
Maintenance
Air quality determines life. Replace the supply filter regularly, drain moisture, and cycle rarely used valves occasionally so that the spool does not stick. The coil can be changed without opening the pneumatic circuit.
Please remember that Bürkert 131425 is delivered without cable plug and without silencers; note these accessories on the request.
Seven Star LLC is an independent supplier serving Oman and the GCC.
Related items you may also need: Bürkert 221602 Type 6213 Servo-Assisted 2/2-Way Solenoid Valve | Bürkert Type 6026 Direct-Acting 2/2-Way Plunger Solenoid Valve | Bürkert Type 8681 Control Head for Hygienic Process Valves | All Bürkert products.
Checklist before ordering the Bürkert 131425
- Before ordering the Bürkert 131425, compare the nameplate of the unit being replaced with the code shown on this page, character by character.
- Our team confirms the Bürkert 131425 code, condition and lead time in writing before any order is placed.
- The datasheet attached to this page is the reference for the Bürkert 131425 dimensions, ratings and wiring.
- The Bürkert 131425 is listed in our solenoid valves range and ships to sites across Oman and the GCC.
Documents and quotation
The Type 6519 data sheet explains circuit functions, ordering charts and hazardous-area variants for Bürkert 131425. In your RFQ give part number Bürkert 131425, the quantity, the actuator size and any accessories such as the cable plug.
Datasheets & Documents
- Datasheet Bürkert 131425 Type 6519 NAMUR Solenoid Valve 24 V DC Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Bürkert is a German family-owned maker of fluid control systems, headquartered in Ingelfingen, Baden-Württemberg. Christian Bürkert founded the company in 1946, and it is known for solenoid valves, process and control valves, flow and analytical sensors, and mass flow controllers. Its products serve water treatment, hygienic processing, gas handling and laboratory applications.
Seven Star LLC lists Bürkert valves and valve automation devices and supplies Bürkert solenoid valves and spare parts to plants in Oman as an independent supplier.
Bürkert company profile
| Founded | 1946, by Christian Bürkert |
|---|---|
| Headquarters | Ingelfingen, Germany |
| Ownership | Family-owned |
| Product families | Solenoid valves, angle seat process valves, positioners, flow meters, mass flow controllers |
Bürkert types listed on this page
Two types are listed. Type 6026 is a direct-acting 2/2-way plunger solenoid valve, with a stainless steel bellows that separates the medium from the coil, and as a direct-acting valve it switches without needing a pressure difference. Type 8681 is the Bürkert control head that mounts on top of hygienic process valves to pilot the actuator and report valve position to the control system. Control heads of this kind are common in food, beverage and pharmaceutical plants in the GCC.
Ordering Bürkert valves: what we need
The type number alone is not enough. Send the identification number from the label, or else the type with orifice, port connection, body and seal material, coil voltage and frequency, circuit function and pressure range. For a Type 8681 control head add the communication variant and the make and model of the process valve it sits on.
Facts checked against Bürkert's published company history, October 2026.
Browse Bürkert products by category: Solenoid Valve, Control Valves.
FAQ
Questions about the Bürkert 131425 Type 6519 NAMUR Solenoid Valve 24 V
Answers from our engineering team on installation, compatibility and integration.
01What circuit function does Bürkert 131425 offer?
With the supplied changeover plate it can operate as a 5/2-way or a 3/2-way pilot-operated valve, called circuit function W in the chart.
02What voltage and power does 131425 have?
It has a 24 V DC coil with a nominal power of 2 watts.
03What flow does 131425 deliver?
The 6 mm orifice gives a QNn value of 900 litres per minute at 6 bar inlet pressure and 1 bar differential.
04Is a cable plug supplied with 131425?
No, the data sheet states that the cable plug form A must be ordered separately.
05Which pressure range applies to 131425?
From 2 to 10 bar overpressure relative to atmosphere.


















Reviews