Brand:

MTL MTL7798 Power Feed and Protection Module

Description

What the MTL7798 does on the power bus

The MTL MTL7798 is not a barrier in the usual sense. It is the supply-side guardian of the MTL7700 range: a power feed and protection module that sits at the head of a bussed 24 V line and watches both voltage and current. If the source misbehaves or a downstream circuit draws too much, a solid state trip mechanism opens the output so that the fuses inside the neighbouring barriers are spared.

Because the MTL7798 works from the same 35 mm rail as the barriers it protects, a row of loops and their common feed can be laid out as one tidy assembly. Seven Star LLC lists this part for engineers who need the exact module for a spare, a repair or an extension of an existing marshalling rack.

MTL7798 key characteristics

  • Voltage sense and current sense circuits feeding a solid state trip
  • Red LED for a trip condition, green LED for power available at the outputs
  • Bussed power drawn from the top of the module through the BPL7700 link, or taken from terminals 1 and 2
  • One module can protect as many as 40 other modules on the same bus
  • Output current range 0 to 800 mA
  • Reset only by removing and restoring the supply
  • Same DIN-rail housing format as the rest of the MTL7700 family

MTL7798 technical specification

Model MTL7798 power feed and protection module
Range MTL7700 DIN-rail mounting safety barriers
Input voltage range (terminals 5 and 6) 20 to 26.8 V
Maximum input voltage capability 45 V
Power source requirement more than 1.8 A
Trip threshold 26.8 V minimum at 20 degrees C (plus 18 mV per degree C)
Output current range 0 to 800 mA
Voltage drop 20 mV at 0 mA, 1.0 V at 800 mA load
Reset interrupt the supply
Indication red LED trip, green LED power at outputs
Bus feed points BPL7700 link at the top, or terminals 1 and 2
Ambient temperature -20 to +60 degrees C working, -40 to +80 degrees C storage
Humidity 5 to 95 percent RH
Mounting 35 mm top-hat DIN rail
Terminals removable, up to 2.5 mm2 (13 AWG)
Weight about 140 g

Where an MTL7798 earns its place in Oman and GCC plants

Hazardous-area switches, solenoids, 4-20 mA transmitters and proximity detectors in a refinery marshalling room often share one 24 V source. In upstream oil and gas facilities, wellhead control panels commonly stack dozens of such loops. Water and wastewater pumping stations, power station auxiliary cabinets and chemical dosing skids repeat the pattern at smaller scale.

Wherever one supply fans out to many fused barrier channels, the MTL7798 gives that supply a single point of protection. A transient from a failing power unit stops at the module instead of reaching every barrier fuse downstream.

Choosing MTL7798 versus the MTL7799 dummy module

The datasheet describes two ways of putting 24 V onto the bus. The MTL7799 is a plain feed-through module that also serves as an earthing point for spare cores and screens. It adds no protection. The MTL7798 adds the trip function, so it is the one specified for standard barriers such as the MTL7787+ and MTL7787P+, whose fuses it is meant to preserve.

Modules that can take their power from the bus include the MTL7706, MTL7707+, MTL7707P+, MTL7741 to MTL7745, MTL7787+, MTL7787P+, MTL7788+, MTL7788R+ and MTL7789+. Looping the feed to both ends of the bussed run lets an individual barrier be pulled without interrupting power to the others.

Installing and commissioning the MTL7798

Clip the module on the rail at the start of the bussed group, connect the 20 to 26.8 V supply to terminals 5 and 6, and join the bus through the BPL7700 link or terminals 1 and 2. Confirm the source can deliver more than 1.8 A before energising, since an undersized supply can look like a fault.

On first power-up the green LED should light. To prove the protection, a technician can check that the supply stays below the 26.8 V trip level at 20 degrees C, remembering the 18 mV per degree drift when the cabinet runs warm. Keep the 50 mm segregation between safe-area and hazardous-area wiring that the barrier rack already follows.

Maintenance and spares notes for MTL7798

A red LED means the trip has operated. Find the cause first, whether an over-voltage on the source or a short on one barrier, then interrupt the supply to reset. Spare terminal packs for the range are listed in the datasheet as SAF7712 and SAF7756 for safe-area terminals, sold in packs of 10.

Keeping a spare MTL7798 on the shelf shortens an outage considerably, because the module sits upstream of every bussed loop and a failed feed takes the whole group of barriers offline at once. When fitting a replacement, check that the bus link and the two supply terminals are seated fully, that the DIN rail earth contact is clean, and that no barrier channel is still shorted from the cause of the previous trip. The datasheet also lists the removal force of the plug-in terminals as more than 15 N, so allow for a firm pull when releasing them.

Ordering information and related MTL7700 parts

Related items named in the manufacturer literature include BPL7700 power bus links (pack of 100), the TH7700 tag holder, DX070 and DX170 enclosures for 5 and 13 modules, and the THR2 DIN rail. Barriers that normally follow the MTL7798 on the bus include the MTL7787+, MTL7788+ and MTL7789+ families. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Documents and quotation

The MTL7700 range datasheet and instruction manual cover the circuit diagrams and terminal numbering for the MTL7798. Send your RFQ with the part number MTL7798 and the quantity you need, and mention the target delivery point in Oman or the wider GCC so that availability can be confirmed.

Datasheets & Documents
  • PDF Datasheet MTL MTL7798 Power Feed and Protection Module Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

MTL is a British maker of intrinsic safety interfaces, surge protection and hazardous-area equipment, founded in 1971 in Luton as Measurement Technology Ltd, a spin-off from Kent Instrumentation. In 2008 Cooper Industries bought MTL Instruments for £144 million and placed it in its Crouse-Hinds division; Eaton acquired Cooper in 2012. MTL is now part of Eaton's Crouse-Hinds business, alongside the MEDC signalling range.

Seven Star LLC lists MTL isolators, a fieldbus barrier and the configuration tools for them, and supplies MTL (Eaton) barriers and spare modules to sites in Oman as an independent supplier.

MTL (Eaton) company profile

Founded 1971, Luton, England, as Measurement Technology Ltd
Origin Spin-off from Kent Instrumentation
Headquarters Luton, England
Ownership Eaton (Crouse-Hinds), via Cooper Industries from 2008
Product families MTL5500 and MTL4500 isolators, MTL7700 zener barriers, 9300 fieldbus barriers, surge protection devices, process junction boxes, PCS45 configuration software; MEDC beacons, sounders and call points

Milestones

  • 1971: Measurement Technology Ltd is founded in Luton.
  • 2007: MTL acquires ELPRO Technologies, RTK Instruments and Ocean Technical Systems.
  • 2008: Cooper Industries acquires MTL Instruments for £144 million.
  • 2012: Eaton acquires Cooper Industries.

MTL product families listed here

Most of the listed items are DIN-rail galvanic isolators. The MTL5541 repeater power supply and the MTL5576-THC temperature converter belong to the MTL5500 range, and the MTL 5043 repeater power supply comes from the earlier MTL5000 range that many plants still run. The MTL 9370-FB2 is a fieldbus barrier for intrinsically safe FOUNDATION fieldbus spurs. PCS45 software with the PCL45USB link is the configurator for MTL converter modules. For the listed part CPM08-BN, please send a label photo so the number can be matched to the manufacturer's records. Newer labels show Eaton MTL, older ones Measurement Technology Ltd, and the module numbers are the same. The MTL 9608 is a fieldbus junction box with eight spur outlets plus a trunk-in connection, listed under the Crouse-Hinds series part number FCS-9608.

Where MTL barriers and isolators are used

These interfaces sit in marshalling cabinets wherever instruments are located in Zone 0, 1 or 2 areas: gas plants, refineries, offshore platforms, tank farms and chemical units across the GCC. They power 2-wire transmitters, pass HART, convert thermocouple signals and drive solenoids or alarms while limiting energy to the field circuit.

MTL (Eaton) products we list

Family Examples
Isolator & Barrier Eaton MTL5541 Repeater Power Supply, MTL 5043, MTL 9370-FB2 Intrinsically Safe Fieldbus…, MTL CPM08-BN, MTL5576-THC Temperature Isolator Module
Automation Accessories MTL 9608 Process Junction Box
Automation Software MTL PCS45 Configuration Software and PCL…

Ordering MTL modules: what we need

Send the full module number including every suffix, for example MTL5576-THC and not just MTL5576, and the quantity. Tell us if the module mounts on DIN rail or on a backplane, because MTL5500 and MTL4500 parts are not interchangeable. For a fieldbus barrier give the number of spurs and the enclosure reference. A photo of the side label, which shows the certificate numbers, helps when the certificate for your project file must match.

Facts checked against the Eaton MTL company history and Drives & Controls coverage of the 2008 Cooper offer, October 2026.

FAQ

Questions about the MTL MTL7798 Power Feed and Protection Module

Answers from our engineering team on installation, compatibility and integration.

01At what voltage does the MTL7798 trip?
The datasheet gives a minimum trip point of 26.8 V at 20 degrees C, shifting by 18 mV per degree C, so the module cuts the bussed output when the supply rises above that level.
02How is a tripped MTL7798 reset?
Reset is done by interrupting the supply to the unit. The red LED marks the tripped state and the green LED shows that power is available at the outputs.
03How many other modules can one MTL7798 feed?
The manufacturer states that a single MTL7798 can protect up to 40 other modules through the bussed power facility, using the BPL7700 bus power link or terminals 1 and 2.
04Does the MTL7798 need a minimum source rating?
Yes. The datasheet specifies a power source requirement of more than 1.8 A, with an input range of 20 to 26.8 V on terminals 5 and 6 and a 45 V maximum input capability.
05When is the MTL7799 used instead of the MTL7798?
The MTL7799 dummy barrier gives direct feed-through of a 24 V supply onto the power bus without the voltage and current trip. The MTL7798 is chosen when fuse protection of the barriers behind it is wanted.