Brand:

Hager ESC325 25 A 3NO 230 V Modular Contactor

Description

ESC325: Hager 25 A 3 NO 230 V contactor explained

The Hager ESC325 is a modular installation contactor with 3 NO contacts, a rated current of 25 A and a 230 V AC coil, in a body that is 35.75 mm wide (2 modules). It switches heating, lighting and small-motor loads on command from a push button, timer, thermostat or building-management output. Seven Star LLC supplies ESC325 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.

The catalogue description is “Contactor 25A, 3NO, 230V~50Hz”. A contactor differs from a circuit breaker: it makes and breaks load current repeatedly on a control signal but carries no short-circuit or overload release, so a breaker or fuse must protect the circuit upstream. The table below decodes the description of ESC325.

Element Value Meaning
Contactor Installation contactor Remote switching device for DIN rail boards
25A 25 A rated current Thermal current of the contacts
3NO 3 NO contacts NO closes when the coil is energised; NC opens
230V~ 230 V AC coil Command voltage 230 V AC
50Hz Frequency Mains frequency of the coil

ESC325 technical specifications

Parameter Specification
Manufacturer / part number Hager / ESC325
Description Contactor 25A, 3NO, 230V~50Hz
Contacts 3 NO
Rated current In 25 A
Category of use AC-7a / AC-7b
Rated operational voltage Ue 400 V
Rated insulation voltage Ui 440 V
Rated impulse withstand voltage Uimp 4000 V
Coil (command) voltage 230 V AC
Coil inrush power 21 VA
Power dissipation at In 6 W
Modules 2
Width x height x depth 35.75 x 83 x 60 mm
Conductors 1–6 mm² flexible, 1–10 mm² rigid
Terminal torque 1.20 Nm
Operating temperature −10 to 50 °C
Storage / transport temperature −40 to 80 °C
Mechanical operations 100000
Electrical endurance 30000 cycles
Manual switch No

How the ESC325 switches the load

When 230 V AC is applied to the coil of ESC325, an electromagnet pulls the armature and moves the contact carrier so the normally open contacts close. When the coil is de-energised a spring returns the carrier. All poles move together, so the load is made and broken in step.

The coil of ESC325 draws 21 VA at inrush and the contactor dissipates 6 W at rated current. With the category AC-7a/AC-7b rating, it is aimed at household-type and light commercial duty rather than heavy industrial motor starting. The datasheet lists 100000 mechanical operations and 30000 electrical cycles.

Where ESC325 fits and related Hager parts

ESC325 is placed after the protective device and before the load, with the coil circuit controlled from a switch, timer, thermostat, BMS output or PLC relay. Related Hager contactors include ESC225 and ESC425, which differ in the number of poles. The catalogue page for ESC325 lists the heat-dissipation insert LZ060 as an optional accessory.

Selection checklist for ESC325

  • Confirm the load current against the 25 A rating
  • Confirm the coil voltage of 230 V AC matches the control supply
  • Count the poles and the contact arrangement needed: 3 NO
  • Check that an MCB or fuse protects the circuit upstream
  • Compare the duty with the AC-7a/AC-7b category and decide whether an industrial contactor is better
  • Allow for board temperature within −10 to 50 °C and include the dissipation in the heat balance

Installation, commissioning and maintenance of ESC325

Snap ESC325 on to the DIN rail and leave a small gap or use the LZ060 insert when several contactors are mounted side by side. Tighten the screw terminals to 1.20 Nm. The datasheet gives 1–6 mm² flexible, 1–10 mm² rigid. Keep power and coil wiring separate and mark the coil circuit clearly.

At commissioning, energise the coil and check that all contacts close and release, measure the voltage at the coil and confirm that nothing is chattering. During maintenance look for discoloured terminals, noise and signs of overheating. Replace a contactor that shows welded contacts or inconsistent operation.

Typical applications of ESC325 in Oman and the GCC

ESC325 has three normally open contacts at 25 A and a two-module width of 35.75 mm. It is the common choice for switching a three-phase resistive load, for example banks of heaters, or for load groups where all three phases must close together. The rated operational voltage is 400 V and the insulation voltage is 440 V.

In the GCC, three-pole 25 A contactors are widely used in HVAC plant, water heating, lighting contactors for three-phase lighting circuits, and as the switching element behind a time clock or a BMS. In hot plant rooms the operating range of −10 to 50 °C stated on the datasheet should be compared with the board temperature, and the dissipation of 6 W per device must be included in the thermal estimate.

ESC325 compared with other Hager modular contactors

Part number Contacts Rated current Modules Coil inrush Dissipation
ESC225 2 NO 25 A 1 10.70 VA 4 W
ESC225S 2 NO 25 A 1 2.50 VA 5.20 W (total loss)
ESC325 3 NO 25 A 2 21 VA 6 W
ESC425 4 NO 25 A 2 21 VA 7.50 W
ESC340 3 NO 40 A 3 62.50 VA 11.10 W
ESC442 2 NO + 2 NC 40 A 3 62.50 VA 7.90 W
ESC463 4 NO 63 A 3 62.50 VA 21.50 W

Values are from the manufacturer datasheets. Verify the datasheet of the exact reference before ordering.

Information to send with an RFQ for ESC325

To quote ESC325 quickly and without back-and-forth, send the details below with your enquiry.

  • Hager part number ESC325 and the quantity required
  • Number and type of contacts (NO / NC), rated current and coil voltage
  • Load type and starting current so the duty can be checked
  • Control source for the coil (timer, thermostat, BMS, PLC)
  • Project name, delivery location in Oman or the GCC and the required delivery date
  • Whether the datasheet, a declaration of conformity or other documents are needed with the shipment

Documents and quotation

A datasheet for ESC325 is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.

To request a quotation, send the part number ESC325, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.

Other Models in the Hager Esc Contactor Range

Seven Star LLC supplies models from the Hager Esc Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Hager ESC225 25 A 2NO 230 V Modular ContactorContactors & Overload RelaysView details
Hager ESC225S 25 A 2NO 230 V Humfree ContactorContactors & Overload RelaysView details
Hager ESC325 25 A 3NO 230 V Modular ContactorContactors & Overload RelaysYou are viewing this model
Hager ESC425 25 A 4NO 230 V Modular ContactorContactors & Overload RelaysView details
Hager ESC340 40 A 3NO 230 V Modular ContactorContactors & Overload RelaysView details
Hager ESC442 40 A 2NO+2NC 230 V Modular ContactorContactors & Overload RelaysView details
Hager ESC463 63 A 4NO 230 V Modular ContactorContactors & Overload RelaysView details
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.

Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.

Hager company profile

Founded January 1955, Ensheim, Saarland, Germany
Founders Peter Hager with his sons Oswald and Hermann
Headquarters Blieskastel, Germany
Ownership Hager family
First products Meter and distribution boards
Product families Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers

Milestones

  • 1955: Hager is founded in Ensheim.
  • 1959: The first French plant opens in Obernai.
  • 2025: Hager marks 70 years.

Hager product series

Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.

Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.

MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.

Where Hager devices are used

Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.

Hager products we list

Family Examples
Circuit Breakers CDC264J 2P 63 A 30 mA Type AC RCCB, HET250JR h3+ P250 3P 250 A 70 kA LSI Ele…, HHB250Z x250 3P 250 A 25 kA Thermal-Magn…, HHS063DC h3+ P160 3P 63 A 25 kA Thermal-…, HMT251GR h3+ P250 4P 250 A 50 kA LSnI El…, NBN106A 1P B-Curve 6 A Miniature Circuit…, SPB440D 4P Type 2 Surge Protection Devic…

Ordering Hager devices: what we need

Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.

Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.

FAQ

Questions about the Hager ESC325 25 A 3NO 230 V Modular Contactor

Answers from our engineering team on installation, compatibility and integration.

01What is the ESC325?
It is a Hager modular contactor with 3 NO contacts, a 25 A rating and a 230 V AC coil. It is 35.75 mm wide and uses 2 modules.
02What coil voltage does ESC325 use?
The command voltage is 230 V AC. The coil inrush is 21 VA, and the dissipation at rated current is 6 W.
03Can ESC325 be used for motors?
The datasheet lists category AC-7a/AC-7b and no AC-3 value, so it is intended for resistive, lighting and light household-type loads. For motors use a rated motor contactor.
04What temperature range applies to ESC325?
It operates from −10 to 50 °C and may be stored from −40 to 80 °C. In hot enclosures, include the 6 W dissipation in the thermal estimate.
05Can ESC325 be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number ESC325 and the quantity and Seven Star LLC will confirm availability and lead time.