TDK B44066S2410J230 Capacitor Contactor 22 kvar, 230 V Coil

Description

A capacitor contactor that pre-charges each step through resistors

The TDK B44066S2410J230 is a three-pole capacitor contactor from the EPCOS B44066S range, built for switching one stage of a power factor correction bank. The J in the code marks the version with leading contacts and resistor spirals that pre-charge the capacitor before the main contacts close; the 230 means a 220 to 240 V AC coil at 50 Hz. According to the datasheet it switches 10.5 to 22 kvar on 415 to 440 V networks (10 to 20 kvar at 380 to 400 V) with an AC6b operational current of 14 to 28 A.

The S2410 body sits between the small S1810 (0 to 13 kvar at 415 to 440 V) and the S3210 (10.5 to 27 kvar). It is a good fit where the bank is made of 12.5, 15 or 20 kvar steps and you want a compact unit with one auxiliary contact already fitted.

Technical specification

Parameter Specification
Ordering code B44066S2410J230 (companion coil code B44066S2410J110 for 110 V)
Capacitor power at 50 C and 60 C 380 to 400 V: 10 to 20 kvar; 415 to 440 V: 10.5 to 22 kvar; 660 to 690 V: 17 to 33 kvar
Rated operational current AC6b 14 to 28 A at 50 Hz/60 Hz, both 50 C and 60 C
Thermal current Ith (AC1) 45 A at 50 C, 40 A at 60 C (manual table)
Coil voltage, type J230 220 to 240 V AC at 50 Hz; 230 to 264 V AC at 60 Hz; operating range 0.85 to 1.1 x Vs
Power loss at maximum rated capacitor current 5.7 W
Rated insulation voltage 690 V AC (Vimp 8 kV for earthed-neutral systems, overvoltage category I to IV, pollution degree 3)
Maximum operating frequency 120 operations per hour
Contact life 0.15 million operations without reactors; 0.30 million with reactors
Main terminals, 1 cable per clamp Solid or stranded 1.5 to 25 mm2; flexible 2.5 to 16 mm2; flexible with ferrule 1.5 to 16 mm2; AWG 16 to 10 solid, 14 to 4 flexible
Main terminals, 2 cables per clamp Sizes listed in the datasheet, for example 16 mm2 + 2.5 to 6 mm2
Weight including auxiliary contact 0.67 kg
Short-circuit fuses gL (gG) 50 A to 80 A
Auxiliary contact 1 NO; AC15 3 A at 230 V and 2 A at 400 V; AC1 10 A at 690 V; insulation 690 V AC
Utilisation category AC6b for switching three-phase capacitors
Approvals as printed cUL; CCC (China Compulsory Certification)

How the J and N versions differ

The installation manual divides the range into J types for conventional banks without reactors and N types for detuned banks. N230 contactors have no pre-charge resistors and may only be used in detuned systems with reactors, so using an N type on a plain bank is not permitted. This page is the J230 version with resistors, so it is the right one when the bank has no series reactors; with reactors the datasheet raises contact life from 0.15 to 0.30 million operations.

Selection and cable sizing

  • Pick the contactor by capacitor current, not only by kvar. At 415 V a 20 kvar step draws about 28 A (derived), the top of the AC6b range.
  • The manual compares AC6b with Ith: for the S2410 the reserve over the capacitor current is 60 % at 50 C and 43 % at 60 C, against the 30 % minimum quoted from EN 61921.
  • Use copper cable only at the terminals; the manual forbids soldering strands and says insulation must not be clamped.
  • Supply cable cross sections follow IEC 60947-1 table 9; the manual quotes 25 mm2 for 85 A and 10 mm2 for 50 A.
  • Protect the step with gL/gG fuses between 50 A and 80 A as per the datasheet.

Installation notes for switchrooms

The datasheet warns that only difficultly inflammable, self-extinguishing materials may be used near the resistor spirals because abnormal temperatures cannot be excluded there. The manual also asks for storage away from corrosive atmospheres, meaning chloride, sulphide, acid, alkali or salt, and for regular cleaning in dusty rooms. Do not install a contactor that is mechanically damaged. If auxiliary contacts are used to switch discharge resistors, keep that current below the 3 A AC15 rating.

GCC use cases

Automatic capacitor banks in 415 V substations, motor control centres of desalination and pumping stations, and air-conditioning plant rooms are the typical homes for this size of contactor. In hot switchrooms note that the capacitor power figures are given up to 60 C, which gives headroom for cabinets that run warm. Pair it with a power factor controller that provides the step outputs, and with capacitors from the same EPCOS range, for example the DeltaCap X Black can. See the electrical and power category.

Selection and installation notes

A power factor correction component is selected from the capacitor bank rating, the supply voltage and the network harmonics. Check the rated voltage and current against the actual duty, allow for the cooling and clearances on the data sheet, tighten the terminals to the torque on the data sheet and fit the protection the maker names. Where the network has strong harmonics, a detuned bank with reactors is the safer choice.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Frequently asked questions

What does the J in B44066S2410J230 stand for?

The J types are contactors with leading contacts and pre-charge resistors for conventional PFC banks; N types have no resistors and are limited to detuned banks. The 230 is the 220 to 240 V coil.

How many kvar can this contactor switch at 415 V?

The datasheet lists 10.5 to 22 kvar for 415 to 440 V, with an AC6b operational current of 14 to 28 A.

How many switching operations can it do?

Contact life is 0.15 million operations without reactors and 0.30 million with reactors, at up to 120 operations per hour.

Does it have an auxiliary contact?

Yes, one normally open auxiliary contact is fitted, rated 3 A at 230 V and 2 A at 400 V (AC15).

Who supplies this part in Oman?

Seven Star LLC is an independent supplier in Muscat and not the manufacturer. Check coil voltage and kvar range with us before ordering.

Datasheets & Documents
  • PDF Datasheet TDK capacitor contactors B44066S****J110/J230 datasheet (June 2026, version 12) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

TDK Electronics, which still markets many components under the EPCOS name, is the electronic components and power quality business of TDK Corporation, the Tokyo-based group established in 1935.

Seven Star LLC is an independent supplier in Muscat. We list selected TDK Electronics (EPCOS) items with the official data sheet attached to every product page, for panel builders and power quality projects in Oman and the GCC.

TDK Electronics product series

Power factor correction components include the DeltaCap X Black 25 kvar 440 V capacitor, the B44066 capacitor contactor for switching capacitor steps and the FilterCap gas-filled AC capacitor for inverter filters.

Drive and EMC components include three-line EMC filters such as the 600 A B84143B0600S080 for converters, the 50 A four-line filter with neutral, the 40 A single-phase filter and the 10 A IEC inlet filter, as well as three-phase line reactors, the 180 A dv/dt output reactor that protects motor insulation and the 66 A LCL filter for active infeed converters.

Where TDK Electronics components are used

Capacitor banks and detuned filter panels, frequency converter and drive cabinets, UPS and inverter systems, and electronic equipment that must meet EMC limits.

Ordering TDK Electronics components: what we need

Send the ordering code starting with B, such as B32305A4252B040, together with the quantity. If the code is not known, give the voltage, rated power in kvar or rated current, number of lines, mounting and the drive or system the part is used with.

Frequently Asked Questions

What does the J in B44066S2410J230 stand for?
The J types are contactors with leading contacts and pre-charge resistors for conventional PFC banks; N types have no resistors and are limited to detuned banks. The 230 is the 220 to 240 V coil.
How many kvar can this contactor switch at 415 V?
The datasheet lists 10.5 to 22 kvar for 415 to 440 V, with an AC6b operational current of 14 to 28 A.
How many switching operations can it do?
Contact life is 0.15 million operations without reactors and 0.30 million with reactors, at up to 120 operations per hour.
Does it have an auxiliary contact?
Yes, one normally open auxiliary contact is fitted, rated 3 A at 230 V and 2 A at 400 V (AC15).
Who supplies this part in Oman?