Lovato PMA20240 PMA20 Current Monitoring Relay

Description

Current monitoring relay for overload and underload detection

The PMA20240 is a current monitoring relay of the Lovato Electric PMA20 family for single-phase circuits. Its function is described as: ac/dc maximum current monitoring relay. Rated current Ie is 5 or 16 A, connected directly or through a current transformer, and the relay runs from an auxiliary supply of 24-240VAC/DC.

The set-point is adjustable (5-100 % of Ie) with a tripping delay of 0.1-30 s, so a short start-up peak can be ignored while a sustained overload is caught.

Technical specifications

Parameter Specification
Order code PMA20240
Product designation Current monitoring relays
Product type designation PMA20
Description AC/DC maximum current monitoring relay
Type of system Single-phase
Auxiliary supply voltage Us 24-240VAC/DC
Operating voltage range 0.85-1.1 Us
Rated frequency 50/60 ±5% Hz
Power consumption Max 3.2 VA
Power dissipation Max 1.6 W
Rated current (Ie) 5 or 16 A
Overload capacity 5Ie for 1s – 160A for 10ms – Constant 16A
Connection Direct or by current transformer
Current set-point (% Ie) (max) 5-100 %
Tripping delay 0.1-30 s
Resetting time 0.1-30 s
Resetting hysteresis 1-50 %
Inhibition time 1-60 s
Type of reset Automatic or manual
External input Resetting / Inhibition
Repeat accuracy ±1 (with constant parameters) %
Number of relays 1
Relay state Normally energised / De-energised (selectable)
Contact arrangement 1 changeover SPDT
Rated operational voltage AC (IEC) 250 VAC
Maximum switching voltage 400 VAC
IEC Conventional free air thermal current Ith ≤ 40°C 8 A
UL/CSA and IEC/EN 60947-5-1 designation B300
Electrical life (with rated load) 100000 cycles
Mechanical life 30000000 cycles
Modular version 2U
Functions and protections provided Maximum AC/DC current
Indication 1 green LED for power on / inhibition and 1 red LED for tripping
Rated insulation voltage Ui 415 V
Rated impulse withstand voltage Uimp 4 kV
Operating frequency withstand voltage 2.5 kV
Operating temperature (min) -20 °C
Operating temperature (max) +60 °C
Storage temperature (min) -30 °C
Storage temperature (max) +80 °C
Execution (n° of modules) 2
Material Self-extinguishing polyamide
Mounting Modular DIN 43880 housing
IEC degree of protection IP40 on front; IP20 at terminals
Dimensions (W x H x D) 35.8 x 104.7 x 64.9 mm
Weight 121 g

Selecting the relay

Use it where a motor current or heater current must be supervised without a full protection relay: pump dry-run detection through a drop in current, blocked conveyors through rising current, or heater burn-out through zero current.

Select the 5 A or 16 A range through the terminals as the datasheet describes, and use an external current transformer for larger loads.

Applications and wiring

The relay mounts on DIN rail in a modular enclosure and uses screw terminals. Its inhibition time lets the starting current pass before monitoring begins, and the reset can be automatic or manual.

For panel design and commissioning, the practical figures to keep at hand are: dimensions (W x H x D) 35.8 x 104.7 x 64.9 mm; weight 121 g; mounting Modular DIN 43880 housing; operating temperature (min) -20 °C; operating temperature (max) +60 °C; storage temperature (min) -30 °C; storage temperature (max) +80 °C; execution (n° of modules) 2; material Self-extinguishing polyamide; IEC degree of protection IP40 on front; IP20 at terminals. These come straight from the datasheet and are repeated here so that the key installation limits are visible without opening the PDF.

Documents and quotation

Attached is the English datasheet that Lovato Electric’s online catalogue generates for PMA20240; the specification table above reproduces its values. Please confirm the supply voltage and system type, the contact arrangement and the DIN-rail space available before you order, and note that the manufacturer may revise datasheet values. Browse controllers & data acquisition for alternatives. To order PMA20240, submit the quotation form with your quantity and site; Seven Star LLC, an independent supplier in Muscat, handles the reply.

Datasheets & Documents
  • PDF Datasheet Lovato Electric PMA20240 datasheet (EN, catalogue export) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

Frequently Asked Questions

What does the PMA20240 monitor?
AC/DC maximum current monitoring relay.
What is the rated current?
5 or 16 A.
What supply does it need?
24-240VAC/DC.
Can a current transformer be used?
The datasheet lists connection as direct or by current transformer.
What is the delay range?
0.1-30 s.