Brand: Veeder-Root
Veeder-Root Mag-FLEX In-Tank Probes for Tall Tanks
Description
Flexible probe for tall tanks, with wired and wireless versions
The Veeder-Root Mag-FLEX in-tank probes monitor gas, diesel and alternative fluids in underground and aboveground tanks that are too tall for a rigid probe. The probe has a corrugated flexible shaft of stainless steel 316 Ti, a stainless steel 303 canister, floats and a weight, and measures product level, water level and temperature.
Twenty part-number configurations are listed: UL/cUL (0889591) and ATEX/IECEx (0889561) versions, each wired or wireless, with gasoline and water floats, diesel and water floats, no water float, methanol tanks without water float, or plastic tanks without water floats. All are inventory-only probes with no leak detection.
Technical specifications
Values come from the Veeder-Root datasheet P/N 577014-449-07 Rev. F (2025). The product identifier on this page is our own; part numbers are shown as printed.
| Parameter | Specification |
|---|---|
| Manufacturer / product | Veeder-Root Mag-FLEX in-tank probe |
| UL/cUL part numbers | 0889591-4xx gasoline and water floats, wired; -5xx diesel and water floats, wired; -6xx no water float, wired; -8xx methanol tanks, wired; -9xx plastic tanks, wired; -0xx plastic tanks, wireless; -1xx gasoline, wireless; -2xx diesel, wireless; -3xx no water float, wireless; -7xx methanol, wireless |
| ATEX/IECEx part numbers | Same configuration set under 0889561-0xx to 0889561-9xx |
| Monitoring function | No leak detection; inventory only |
| Products listed | Gasohol up to 15% ethanol, gasoline blends with methanol, MTBE, TAME, ETBE or TBA, leaded gasoline, mineral spirits, premium and regular unleaded; diesel #2, kerosene #1 and low-density biodiesel with the diesel float kit; methanol (8xx and 7xx); DEF/AdBlue (0xx and 9xx) |
| Measurement accuracy | Product 0.0800 in (2.032 mm); water 0.12 in (3.048 mm) |
| Resolution | 0.02 in (0.508 mm) per sample |
| Minimum measurement | 7.3 in (18.54 cm) product; water 5.5 in (13.97 cm) standard float, 1.9 in (4.83 cm) low-level float |
| Operating temperature | -40 to +140 °F (-40 to +60 °C); 5 thermistors |
| Materials | Canister stainless steel 303; rigid shaft sections 304; corrugated flexible shaft and floats 316 Ti; weight 303 (steel tall tanks) or 316L (plastic tall tanks) |
| Probe length (low-level float kits) | 5 ft to 72.1 ft (1.5 m to 22 m) |
| Float kits | 0330020-776 low-level water float for gasoline; -777 for diesel; -824 for biodiesel (1.9 in, require a 4 in tank opening) |
| Accessories | 0848100-004 overvoltage protection device (1 per probe recommended); 0576008-708 2 in NPT adapter for AST installation (1 per probe) |
| Console compatibility | TLS-450PLUS (up to 64 probes), TLS4 (12), TLS4B (6), TLS-350/R/PLUS (16, via 0329356-002), TLS-300i (4), TLS-300C (2); UL/cUL versions need TLS4, TLS4B or TLS-450PLUS with software 6.A or higher |
Installation points for tall tanks
The datasheet’s installation drawing marks the insertion measuring point, riser dimensions, null zone, measured insertion length, weight length, dead zone and the tank grounding bracket and grounding cable. Order the smaller probe when the measured insertion length falls between two lengths, and use the non-magnetic weight in plastic tanks, where clearance off the bottom applies. Plastic tall-tank probes do not have the conductive magnet casing.
Low-level water float kits (4 in opening required, wall guide included) connect to the existing water float to reduce the minimum water measurement to 1.9 in.
What to confirm before ordering
- Tank material (steel or plastic) and height, to choose the correct part-number group and probe length.
- Fluid: gasoline, diesel, methanol or DEF, which decides the float configuration.
- Wired or wireless, and UL/cUL or ATEX/IECEx approval.
- Console and its software version, because the UL/cUL versions require version 6.A or higher.
Key features of the Mag-FLEX design
- A corrugated flexible shaft in stainless steel 316 Ti, so a probe up to 72.1 ft (22 m) long can be handled and fed into a tall tank without a single rigid section of that length.
- Simultaneous measurement of product level, water level and temperature from one probe, with five thermistors spread along the length for temperature data.
- Product accuracy of 0.0800 in (2.032 mm) and resolution of 0.02 in (0.508 mm) per sample, as stated on the datasheet.
- Float configurations matched to the fluid: gasoline and water, diesel and water, no water float, methanol and plastic-tank (DEF/AdBlue) versions.
- Wired and wireless versions in both the UL/cUL (0889591) and ATEX/IECEx (0889561) families.
How the part number is built
The two seven-digit prefixes separate the approval family, and the first digit of the three-digit suffix selects the configuration. A wired gasoline probe with water float sits in the 4xx block, the wireless gasoline version in the 1xx block, and so on. The remaining digits relate to the length chosen for the tank. Because the same configuration set exists in both families, quote the full number from the datasheet table rather than only the suffix, so that the approval and the configuration are both clear.
| Suffix block | Configuration | Connection |
|---|---|---|
| 4xx / 1xx | Gasoline and water floats | Wired / wireless |
| 5xx / 2xx | Diesel and water floats | Wired / wireless |
| 6xx / 3xx | No water float | Wired / wireless |
| 8xx / 7xx | Methanol tanks, no water float | Wired / wireless |
| 9xx / 0xx | Plastic tanks, no water floats | Wired / wireless |
Inventory monitoring, not leak detection
Every Mag-FLEX configuration is listed as an inventory-only probe. It reports level, water and temperature to the console for stock reconciliation and delivery records, but it does not run the in-tank leak tests that some other probes support. Where a site needs a statistical or static leak test, that function has to come from another device or method approved for the purpose, and this should be settled with the system designer before the probe is ordered.
Applications in Oman and the GCC
Tall vertical aboveground tanks are common at fuel depots, power stations, desalination plants and mining or construction camps across Oman and the wider GCC, where diesel is stored for generators and vehicle fleets. A flexible probe suits these tanks because it can be carried to site coiled and installed through a riser without lifting a long rigid assembly over the roof. The stated operating range of -40 to +60 °C should be compared with the actual conditions inside risers and manholes, which can heat considerably in direct summer sun; shading of riser caps and junction boxes is good practice. For DEF/AdBlue stored in plastic tanks at truck depots, the plastic-tank versions with the non-magnetic weight apply.
Maintenance and good practice
- Fit the recommended 0848100-004 overvoltage protection device, one per probe, especially at sites exposed to lightning or long cable runs.
- Keep the tank grounding bracket and cable shown in the installation drawing in place and check them during routine inspections.
- When the probe is removed for tank cleaning, check the floats for free movement and the shaft for mechanical damage before reinstalling.
- Compare console readings with manual dips periodically so any drift or float problem is noticed early.
What to include in an RFQ
A complete enquiry lets us match the configuration on the first attempt. Please state the tank material and internal height, the riser size and the measured insertion length if known, the stored fluid, whether a low-level water float kit is wanted (it needs a 4 in opening), wired or wireless connection, the required approval family, and the console model with its software version. For aboveground tanks, also state whether the 0576008-708 2 in NPT adapter is required.
Documents and quotation
The Veeder-Root Mag-FLEX datasheet is attached to this page as a PDF with the full part-number list and installation drawing. Send us the tank type, height, fluid and console and we will quote the correct configuration. Seven Star LLC is an independent supplier in Muscat; price and lead time are confirmed per RFQ. Related range: level instrumentation.
Datasheets & Documents
- Datasheet Veeder-Root Mag-FLEX In-Tank Probes datasheet (P/N 577014-449-07 Rev. F) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Veeder-Root is a fuel management specialist based in Simsbury, Connecticut, USA, founded in 1866 and part of Vontier. It is best known for TLS automatic tank gauges, magnetostrictive in-tank probes and leak detection sensors for fuel storage.
Seven Star LLC is an independent supplier in Muscat. We list Veeder-Root consoles, probes and sensors from the maker's published datasheets for fuel stations, depots and airports in Oman and the GCC.
Veeder-Root product series
Tank gauge consoles include the TLS4 and the non-expandable TLS4B, the TLS-450PLUS and the legacy TLS-350PLUS. Mag Plus in-tank probes are offered for gasoline and diesel, jet fuel, LPG and light and heavy oil, and Mag-FLEX probes cover tall tanks. Leak detection sensors include the discriminating containment sump sensor 0794380-352 and the interstitial sensor 0794390-420 for double-wall steel tanks. The EMR4 electronic meter register is used on fuel delivery trucks.
Where Veeder-Root products are used
Petrol stations, fuel depots, airports and fleet fuelling sites, where the system measures product level, water and temperature in underground and aboveground tanks, monitors sumps and interstitial spaces and supports inventory reconciliation and leak tests.
Ordering Veeder-Root products: what we need
Send the console model and the modules installed, the number of tanks, the product in each tank, the tank type and diameter for probe length, and the sensors required. Where a model is discontinued, we say so on the product page and confirm the successor before quoting.
Browse Veeder-Root products by category: Level Instrumentation.
Related products
Frequently Asked Questions
Level, water and temperature monitoring in tall tanks using a probe with a corrugated flexible shaft.
No. Mag-FLEX probes are inventory-only.
Yes. Both UL/cUL and ATEX/IECEx part-number groups include wireless variants.
The datasheet lists DEF/AdBlue for the plastic-tank part numbers 0xx and 9xx.
0.0800 in (2.032 mm) for product and 0.12 in (3.048 mm) for water.