- Automation & ControlView all 2,462 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Motor Soft Starters
- Encoders
- Safety Switches & Guard Locking
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Hager
Hager SBN363 3P 63 A Modular Switch Disconnector
Description
SBN363: Hager 3-pole 63 A modular switch disconnector decoded
The Hager SBN363 is a 3-pole, 63 A modular switch (switch disconnector) for DIN rail mounting, 52.5 mm wide and 3 modules. It opens and closes the circuit manually and provides isolation for maintenance. Seven Star LLC supplies SBN363 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
The catalogue description is “3P 63A Switch”. A switch disconnector has no overload or short-circuit release, so a fuse or breaker must be placed upstream. The table decodes the reference for SBN363.
| Element | Value | Meaning |
|---|---|---|
| 3P | 3 poles | Number of poles switched together |
| 63A | 63 A rated current | AC-21 and AC-22 ratings, categories A and B |
| Switch | Manual switch disconnector | Isolates and breaks load, no tripping function |
| 3M | 3 modules | Width 52.5 mm on the DIN rail |
SBN363 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Hager / SBN363 |
| Description | 3P 63A Switch |
| Poles | 3 |
| Rated current In | 63 A |
| AC-21 / AC-22 current (cat. A and B) | 63 A |
| Rated operational voltage Ue | 400 V |
| Rated insulation voltage Ui | 440 V |
| Rated impulse withstand voltage Uimp | 6000 V |
| Making capacity Icm (IEC 60947-3) | 1.33 kA at 415 V AC |
| Short-time withstand current Icw 1 s | 0.94 kA |
| Conditional short-circuit current | 6000 A with 80 A gG fuse (parallel 32 A gG) |
| Power loss total / per pole | 6.90 W / 2.30 W |
| Modules | 3 |
| Width x height x depth | 52.5 x 83 x 68 mm |
| Conductors | 2.5–25 mm² rigid, 2.5–16 mm² flexible |
| Terminal torque | 2.80 Nm |
| Mechanical operations | 60000 |
| Electrical durability (AC-21 / AC-22) | 5000 cycles |
| Operating temperature | −20 to 70 °C |
| Storage / transport temperature | −40 to 80 °C |
| Ingress protection | IP20 |
| Terminal alignment | Aligned terminals |
How the SBN363 isolates the circuit
SBN363 uses a snap-action mechanism, so the speed of contact opening does not depend on how fast the operator moves the lever. All 3 poles open together, and the open position gives a clear air gap that is the basis for isolation. A switch of this type is rated for load making and breaking under AC-21 (resistive loads with small overloads) and AC-22 (mixed resistive and inductive loads with moderate overloads), and the datasheet lists 63 A in both categories.
The short-time withstand current of 0.94 kA for one second and the making capacity of 1.33 kA at 415 V AC describe how the switch behaves during a fault if the upstream protective device is slow. The sheet quotes a conditional short-circuit rating of 6000 A with 80 A gG fuse (parallel 32 A gG), which assumes that device is present, so the switch should not be used as protection.
Where SBN363 fits and related Hager parts
SBN363 is installed at the head of a sub-board, ahead of motor circuits or beside the equipment it isolates. Related references include SBN325 at 25 A, SBN390 at 100 A and SBN463 with four poles. The catalogue page lists the padlockable locking kit MZN175 as an optional accessory, which allows the switch to be secured in the off position during maintenance.
Selection checklist for SBN363
- Check the load current against 63 A and the category needed (AC-21 or AC-22)
- Choose the number of poles: three phases
- Compare the prospective fault level with the 1.33 kA at 415 V AC making capacity and the 0.94 kA short-time rating
- Make sure an MCB or fuse protects the circuit upstream
- Check the terminal alignment (aligned) against any comb busbar
- Check the module count and the space on the rail
- Allow for the power loss of 6.90 W in the board heat balance
Installation, commissioning and maintenance of SBN363
Fit SBN363 on a 35 mm DIN rail and make the connections with conductors in the range 2.5–25 mm² rigid, 2.5–16 mm² flexible, tightened to 2.80 Nm. Terminal alignment is aligned, so busbar connectors must match. Label the switch with the circuit it isolates and fit a lock where the maintenance procedure requires it.
At commissioning, operate the switch several times, confirm that all poles open together, and verify voltage absence with a tester on the load side before work. In service, switch operations should be recorded, terminals checked for heat marks during shutdowns, and a switch that sticks or is slow to operate should be replaced.
Typical applications of SBN363 in Oman and the GCC
SBN363 raises the rating to 63 A on three poles in a three-module body. It is commonly installed as a sub-board main switch, taking the place of a small incomer. The sheet lists a making capacity of 1.33 kA at 415 V, a short-time withstand current of 0.94 kA for one second and an impulse withstand value of 6000 V.
In Oman, SBN363 serves as the main isolator for distribution boards in buildings, workshops and small process units, and as the isolator ahead of motor-starter groups. At 63 A the dissipation is 6.90 W, which is meaningful in a hot room. The mechanical life of 60000 operations and the electrical durability of 5000 cycles at nominal AC-21 and AC-22 load suit infrequent maintenance switching, not repeated load switching.
SBN363 compared with other Hager modular switches
| Part number | Poles | Rated current | Making capacity | Modules | Electrical durability (cycles) |
|---|---|---|---|---|---|
| SBN232 | 2 | 32 A | 0.67 kA at 240 V AC | 1 | 25000 |
| SBN325 | 3 | 25 A | 0.52 kA at 415 V AC | 2 | 25000 |
| SBN363 | 3 | 63 A | 1.33 kA at 415 V AC | 3 | 5000 |
| SBN390 | 3 | 100 A | 1.69 kA at 415 V AC | 3 | 2500 |
| SBN440 | 4 | 40 A | 0.84 kA at 415 V AC | 4 | 5000 |
| SBN463 | 4 | 63 A | 1.33 kA at 415 V AC | 4 | 5000 |
Values are taken from the manufacturer datasheets. Verify the datasheet of the exact reference before ordering.
Information to send with an RFQ for SBN363
To quote SBN363 quickly and without back-and-forth, send the details below with your enquiry.
- Hager part number SBN363 and the quantity required
- Number of poles, rated current and voltage
- Load type (resistive, motor) and the upstream protective device
- Whether a locking kit or other accessory is required
- Project name, delivery location in Oman or the GCC and the required delivery date
- Whether the datasheet, a declaration of conformity or other documents are needed with the shipment
Documents and quotation
A datasheet for SBN363 is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.
To request a quotation, send the part number SBN363, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.
Other Models in the Hager S Switch Range
Seven Star LLC supplies models from the Hager S Switch range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Hager SBN232 2P 32 A Modular Switch Disconnector | Switchgear, Enclosures & Distribution | View details |
| Hager SBN325 3P 25 A Modular Switch Disconnector | Switchgear, Enclosures & Distribution | View details |
| Hager SBN363 3P 63 A Modular Switch Disconnector | Switchgear, Enclosures & Distribution | You are viewing this model |
Datasheets & Documents
- Datasheet Hager SBN363 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.
Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.
Hager company profile
| Founded | January 1955, Ensheim, Saarland, Germany |
|---|---|
| Founders | Peter Hager with his sons Oswald and Hermann |
| Headquarters | Blieskastel, Germany |
| Ownership | Hager family |
| First products | Meter and distribution boards |
| Product families | Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers |
Milestones
- 1955: Hager is founded in Ensheim.
- 1959: The first French plant opens in Obernai.
- 2025: Hager marks 70 years.
Hager product series
Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.
Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.
MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.
Where Hager devices are used
Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.
Hager products we list
Ordering Hager devices: what we need
Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.
Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.
Browse Hager products by category: Circuit Breakers.
FAQ
Questions about the Hager SBN363 3P 63 A Modular Switch Disconnector
Answers from our engineering team on installation, compatibility and integration.
01What is the SBN363?
It is a Hager 3-pole modular switch disconnector rated 63 A. It is 52.5 mm wide, uses 3 modules and isolates the circuit for maintenance.
02Does SBN363 provide overload protection?
No. SBN363 has no release, so an upstream MCB or fuse is needed. The datasheet quotes a conditional rating of 6000 A with 80 A gG fuse (parallel 32 A gG) with such a device.
03What load categories does SBN363 cover?
The datasheet lists 63 A in AC-21 and AC-22, categories A and B. The electrical durability at nominal load is 5000 cycles and the mechanical life is 60000 operations.
04What conductors can be connected to SBN363?
The datasheet gives 2.5–25 mm² rigid, 2.5–16 mm² flexible, tightened to 2.80 Nm. Terminal alignment is aligned.
05Can SBN363 be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number SBN363 and the quantity and Seven Star LLC will confirm availability and lead time.


















Reviews