Brand:

Hager SBN363 3P 63 A Modular Switch Disconnector

Description

SBN363: Hager 3-pole 63 A modular switch disconnector decoded

The Hager SBN363 is a 3-pole, 63 A modular switch (switch disconnector) for DIN rail mounting, 52.5 mm wide and 3 modules. It opens and closes the circuit manually and provides isolation for maintenance. Seven Star LLC supplies SBN363 in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.

The catalogue description is “3P 63A Switch”. A switch disconnector has no overload or short-circuit release, so a fuse or breaker must be placed upstream. The table decodes the reference for SBN363.

Element Value Meaning
3P 3 poles Number of poles switched together
63A 63 A rated current AC-21 and AC-22 ratings, categories A and B
Switch Manual switch disconnector Isolates and breaks load, no tripping function
3M 3 modules Width 52.5 mm on the DIN rail

SBN363 technical specifications

Parameter Specification
Manufacturer / part number Hager / SBN363
Description 3P 63A Switch
Poles 3
Rated current In 63 A
AC-21 / AC-22 current (cat. A and B) 63 A
Rated operational voltage Ue 400 V
Rated insulation voltage Ui 440 V
Rated impulse withstand voltage Uimp 6000 V
Making capacity Icm (IEC 60947-3) 1.33 kA at 415 V AC
Short-time withstand current Icw 1 s 0.94 kA
Conditional short-circuit current 6000 A with 80 A gG fuse (parallel 32 A gG)
Power loss total / per pole 6.90 W / 2.30 W
Modules 3
Width x height x depth 52.5 x 83 x 68 mm
Conductors 2.5–25 mm² rigid, 2.5–16 mm² flexible
Terminal torque 2.80 Nm
Mechanical operations 60000
Electrical durability (AC-21 / AC-22) 5000 cycles
Operating temperature −20 to 70 °C
Storage / transport temperature −40 to 80 °C
Ingress protection IP20
Terminal alignment Aligned terminals

How the SBN363 isolates the circuit

SBN363 uses a snap-action mechanism, so the speed of contact opening does not depend on how fast the operator moves the lever. All 3 poles open together, and the open position gives a clear air gap that is the basis for isolation. A switch of this type is rated for load making and breaking under AC-21 (resistive loads with small overloads) and AC-22 (mixed resistive and inductive loads with moderate overloads), and the datasheet lists 63 A in both categories.

The short-time withstand current of 0.94 kA for one second and the making capacity of 1.33 kA at 415 V AC describe how the switch behaves during a fault if the upstream protective device is slow. The sheet quotes a conditional short-circuit rating of 6000 A with 80 A gG fuse (parallel 32 A gG), which assumes that device is present, so the switch should not be used as protection.

Where SBN363 fits and related Hager parts

SBN363 is installed at the head of a sub-board, ahead of motor circuits or beside the equipment it isolates. Related references include SBN325 at 25 A, SBN390 at 100 A and SBN463 with four poles. The catalogue page lists the padlockable locking kit MZN175 as an optional accessory, which allows the switch to be secured in the off position during maintenance.

Selection checklist for SBN363

  • Check the load current against 63 A and the category needed (AC-21 or AC-22)
  • Choose the number of poles: three phases
  • Compare the prospective fault level with the 1.33 kA at 415 V AC making capacity and the 0.94 kA short-time rating
  • Make sure an MCB or fuse protects the circuit upstream
  • Check the terminal alignment (aligned) against any comb busbar
  • Check the module count and the space on the rail
  • Allow for the power loss of 6.90 W in the board heat balance

Installation, commissioning and maintenance of SBN363

Fit SBN363 on a 35 mm DIN rail and make the connections with conductors in the range 2.5–25 mm² rigid, 2.5–16 mm² flexible, tightened to 2.80 Nm. Terminal alignment is aligned, so busbar connectors must match. Label the switch with the circuit it isolates and fit a lock where the maintenance procedure requires it.

At commissioning, operate the switch several times, confirm that all poles open together, and verify voltage absence with a tester on the load side before work. In service, switch operations should be recorded, terminals checked for heat marks during shutdowns, and a switch that sticks or is slow to operate should be replaced.

Typical applications of SBN363 in Oman and the GCC

SBN363 raises the rating to 63 A on three poles in a three-module body. It is commonly installed as a sub-board main switch, taking the place of a small incomer. The sheet lists a making capacity of 1.33 kA at 415 V, a short-time withstand current of 0.94 kA for one second and an impulse withstand value of 6000 V.

In Oman, SBN363 serves as the main isolator for distribution boards in buildings, workshops and small process units, and as the isolator ahead of motor-starter groups. At 63 A the dissipation is 6.90 W, which is meaningful in a hot room. The mechanical life of 60000 operations and the electrical durability of 5000 cycles at nominal AC-21 and AC-22 load suit infrequent maintenance switching, not repeated load switching.

SBN363 compared with other Hager modular switches

Part number Poles Rated current Making capacity Modules Electrical durability (cycles)
SBN232 2 32 A 0.67 kA at 240 V AC 1 25000
SBN325 3 25 A 0.52 kA at 415 V AC 2 25000
SBN363 3 63 A 1.33 kA at 415 V AC 3 5000
SBN390 3 100 A 1.69 kA at 415 V AC 3 2500
SBN440 4 40 A 0.84 kA at 415 V AC 4 5000
SBN463 4 63 A 1.33 kA at 415 V AC 4 5000

Values are taken from the manufacturer datasheets. Verify the datasheet of the exact reference before ordering.

Information to send with an RFQ for SBN363

To quote SBN363 quickly and without back-and-forth, send the details below with your enquiry.

  • Hager part number SBN363 and the quantity required
  • Number of poles, rated current and voltage
  • Load type (resistive, motor) and the upstream protective device
  • Whether a locking kit or other accessory is required
  • Project name, delivery location in Oman or the GCC and the required delivery date
  • Whether the datasheet, a declaration of conformity or other documents are needed with the shipment

Documents and quotation

A datasheet for SBN363 is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.

To request a quotation, send the part number SBN363, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.

Other Models in the Hager S Switch Range

Seven Star LLC supplies models from the Hager S Switch range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Hager SBN232 2P 32 A Modular Switch DisconnectorSwitchgear, Enclosures & DistributionView details
Hager SBN325 3P 25 A Modular Switch DisconnectorSwitchgear, Enclosures & DistributionView details
Hager SBN363 3P 63 A Modular Switch DisconnectorSwitchgear, Enclosures & DistributionYou are viewing this model
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.

Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.

Hager company profile

Founded January 1955, Ensheim, Saarland, Germany
Founders Peter Hager with his sons Oswald and Hermann
Headquarters Blieskastel, Germany
Ownership Hager family
First products Meter and distribution boards
Product families Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers

Milestones

  • 1955: Hager is founded in Ensheim.
  • 1959: The first French plant opens in Obernai.
  • 2025: Hager marks 70 years.

Hager product series

Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.

Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.

MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.

Where Hager devices are used

Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.

Hager products we list

Family Examples
Circuit Breakers CDC264J 2P 63 A 30 mA Type AC RCCB, HET250JR h3+ P250 3P 250 A 70 kA LSI Ele…, HHB250Z x250 3P 250 A 25 kA Thermal-Magn…, HHS063DC h3+ P160 3P 63 A 25 kA Thermal-…, HMT251GR h3+ P250 4P 250 A 50 kA LSnI El…, NBN106A 1P B-Curve 6 A Miniature Circuit…, SPB440D 4P Type 2 Surge Protection Devic…

Ordering Hager devices: what we need

Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.

Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.

FAQ

Questions about the Hager SBN363 3P 63 A Modular Switch Disconnector

Answers from our engineering team on installation, compatibility and integration.

01What is the SBN363?
It is a Hager 3-pole modular switch disconnector rated 63 A. It is 52.5 mm wide, uses 3 modules and isolates the circuit for maintenance.
02Does SBN363 provide overload protection?
No. SBN363 has no release, so an upstream MCB or fuse is needed. The datasheet quotes a conditional rating of 6000 A with 80 A gG fuse (parallel 32 A gG) with such a device.
03What load categories does SBN363 cover?
The datasheet lists 63 A in AC-21 and AC-22, categories A and B. The electrical durability at nominal load is 5000 cycles and the mechanical life is 60000 operations.
04What conductors can be connected to SBN363?
The datasheet gives 2.5–25 mm² rigid, 2.5–16 mm² flexible, tightened to 2.80 Nm. Terminal alignment is aligned.
05Can SBN363 be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number SBN363 and the quantity and Seven Star LLC will confirm availability and lead time.