Brand:

Caprari NMC and NMCS Monobloc EN 733 Pumps, DN32 to DN150

Description

Monobloc EN 733 pumps for HVAC, boosters and industry

The Caprari NMC and NMCS are horizontal-axis monobloc centrifugal electric pumps with main features and dimensions according to EN 733 (DIN 2455), with an additional 80/400 size to complete the range. The NMC has an integral motor pump shaft; the NMCS has an extended pump shaft, a bearing that absorbs the axial thrust and a standardised motor. The catalogue (code 998913A/11-25, 56 pages) covers delivery ports DN32 to DN150 for 2-pole and 4-pole 50 Hz motors.

Listed uses are heating and air-conditioning, industry, civil applications, booster sets and irrigation. The pumped liquid is clean fresh water of non-aggressive chemical and mechanical nature, up to 140 C.

Technical specification

Parameter Specification
Construction Horizontal axis monobloc centrifugal pump to EN 733 (DIN 2455); extra size 80/400
Versions NMC: integral motor shaft. NMCS: extended shaft, axial-thrust bearing and standardised motor
Motor Three-phase or single-phase asynchronous squirrel-cage, enclosed with external ventilation
Protection and insulation IP55, class F
Standard voltage 230/400 V up to 3 kW; 400/690 V above 3 kW; 50 Hz
Efficiency class IE3 or IE4; IE2 for the single-phase version
Maximum liquid temperature 140 C (284 F)
Maximum starts per hour 3 to 51, depending on motor power
Performance tolerance UNI/ISO 9906 Grade 3B, cold water at 15 C and 1 bar
Reference liquid Density 1 kg/dm3, kinematic viscosity 1 mm2/s or less
Special versions Bronze or stainless steel impellers; full bronze; inverter on board; special voltage; IE4 motor
Flanges UNI EN 1092-2, PN10-16 (DN200 at PN10)

Materials

Part NMC NMCS
Pump casing Cast iron Cast iron; nodular cast iron on some models
Impeller Brass or cast iron, by model Cast iron; brass or cast iron on some models
Lantern bracket Cast iron Cast iron
Support (NMCS) – Cast iron
Shaft Stainless steel Stainless steel
Mechanical seal Alumina/carbon/EPDM or carbon/ceramic/rubber, by model Alumina/carbon/EPDM

Screws and nuts are stainless steel.

Operating ranges by size

Each size has an operating-data page with curves by motor power. The table gives the flow span of the printed chart axis and the motor powers marked on the curves; the axis span is the chart scale, not a guaranteed maximum.

Size 2-pole chart flow m3/h 2-pole motors kW 4-pole chart flow m3/h 4-pole motors kW
NMC 32 5.4 to 28.8 0.55 to 4 2.2 to 18 0.37 to 0.75
NMC 32L 7.2 to 36 2.2 to 7.5 – –
NMC 40 14.4 to 54 1.1 to 15 3.6 to 32.4 0.37 to 3
NMC 50 21.6 to 86.4 2.2 to 22 7.2 to 54 1.1 to 4
NMC(S) 65 32.4 to 147.6 4 to 37 18 to 100.8 1.1 to 9.2
NMC(S) 80 64.8 to 198 7.5 to 55 25.2 to 183.6 1.1 to 37
NMC(S) 100 97.2 to 306 18.5 to 55 43.2 to 216 3 to 37
NMC(S) 125 – – 72 to 334.8 5.5 to 55
NMC(S) 150 – – 122.4 to 720 18.5 to 55

NMCS pages extend this with standardised motors up to 75 kW at DN100 and 90 kW at DN150, shown with the IE4 super premium efficiency motor badge.

Flange dimensions

DN PN Holes Hole diameter mm u mm v mm
32 10-16 4 19 100 140
40 10-16 4 19 110 150
50 10-16 4 19 125 165
65 10-16 4 19 145 185
80 10-16 8 19 160 200
100 10-16 8 19 180 220
125 10-16 8 19 210 250
150 10-16 8 23 240 285
200 10 8 23 295 340

The catalogue marks these as indicative; the executive drawing is supplied on request at order.

Selection, ordering and installation

The code reads series NMC or NMCS, nominal diameter, impeller trimming letter, motor type and supply code. Examples printed: NMCS32D+C40075T211 and NMCS40A+C40220T211, where the C-code distinguishes the motor (C2 single-phase IE2, C3 three-phase IE3, C4 three-phase IE4), followed by nominal power and the pole, voltage and generation digits. Choose NMC where the motor and pump share one integral shaft and NMCS where a standardised motor and a separate thrust bearing are wanted. Keep to the stated start limit and the 140 C ceiling, and use the inverter-on-board option where speed control is needed.

Applications in GCC industries

Chilled-water and hot-water circulation in building services, pressure boosting, industrial utility water and farm irrigation are the catalogue uses. The standard parts are cast iron and brass, so for seawater or brine ask for the bronze or full bronze version. The catalogue prints no ATEX, fire-pump or drinking-water approval for this series, so none is claimed.

Reading the printed limits

The motor data in the catalogue is specific. The motor is three-phase or single-phase asynchronous with a squirrel-cage rotor, IP55 and class F insulation, with 230/400 V up to 3 kW and 400/690 V above 3 kW at 50 Hz. The NMC pump stub shaft is integral with the motor shaft, which removes the coupling and the alignment step during installation, while the NMCS uses a standard motor with a separate bearing for the axial thrust. The maximum number of starts per hour runs from 3 to 51 depending on motor power, which sets the limit for frequent-start duties.

The catalogue also prints the performance tolerance, UNI/ISO 9906 Grade 3B, measured on cold water at 15 C and 1 bar, and notes that data refer to liquids with a density of 1 kg/dm3 and a kinematic viscosity up to 1 mm2/s. Warmer or thicker liquids need a correction.

Selection and installation notes

Select a pump from the duty point: the flow, the head, the liquid and its temperature, the supply voltage and the expected operating hours. Check the electrical supply and cable size against the motor rating, install the pump as the manual shows on a firm base with pipework that does not strain the ports, protect the motor against overload and dry running, and fit non-return and isolation valves in the delivery line. Keep the installation and commissioning record, and plan routine inspection of seals, bearings and wear parts.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Related items and documents

Other Caprari pumps are listed under pumps; the official catalogue is attached. Seven Star LLC is an independent supplier in Muscat: send flow, head, liquid temperature and supply, and we will match size and trimming to the Caprari curves before quoting.

Datasheets & Documents
  • PDF Datasheet Caprari NMC and NMCS monobloc pumps catalogue (EN/FR/IT, 11-25) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Caprari is an Italian pump manufacturer, founded in 1945 by Amadio Caprari as Idromeccanica Caprari and headquartered in Modena. By 1950 it was building vertical lineshaft pumps, in 1968 it produced its first submersible deep-well pump, and from the 1970s it opened subsidiaries abroad. The Italian investment firm Ambienta acquired Caprari in February 2021.

Seven Star LLC is an independent supplier in Muscat. We list Caprari pumps for water utilities, farms, contractors and industry in Oman and the GCC.

Caprari company profile

Founded 1945, Italy, by Amadio Caprari
Headquarters Modena, Italy
Ownership Ambienta, since February 2021
Production Plants in Italy, China and Turkey
Product families NMC and NC.E EN 733 end-suction pumps, MEC-MG flanged pumps for diesel drives, E6 and E8 stainless borehole pumps, Desert sand-resistant submersible pumps, D-M drainage and sewage pumps, CVD vertical multistage pumps

Milestones

  • 1945: Amadio Caprari founds Idromeccanica Caprari.
  • 1965: The current Modena headquarters opens.
  • 1968: Caprari builds its first submersible deep-well pump.
  • 2021: Ambienta acquires Caprari.

Caprari product series

Borehole pumps include the E6NVX and E8NVX 6 and 8 inch stainless steel pumps and the Desert E4X and E6X sand-resistant pumps. Surface pumps include the NMC and NMCS monobloc EN 733 pumps from DN32 to DN150, the NC.E end-suction pumps for fire-fighting units, the PM high pressure horizontal multistage pumps, the CVD vertical multistage pumps and the SCC double-suction split case pumps from DN100 to DN700.

The P Series P6P and P8P are vertical lineshaft pumps, the MEC-MG, MEC-AG and BHG pumps are flanged for diesel engine drive, and the D-M Series covers submersible drainage and sewage pumps.

Where Caprari pumps are used

Well fields and water supply, farm irrigation, pressure boosting, fire-fighting pump sets, drainage of sites and basements, and sewage lifting.

Caprari products we list

Family Examples
Pumps CVD Vertical Multistage Electric Pump, D-M Series Submersible Drainage and Sewa…, Desert E4X and E6X Sand-Resistant Boreho…, E6NVX and E8NVX 6 and 8 Inch Stainless B…, MEC-MG, NC.E EN 733 End-Suction Pumps for Fire-F…, NMC and NMCS Monobloc EN 733 Pumps

Ordering Caprari pumps: what we need

Send the model or the required flow and head, the liquid, borehole diameter or installation type, power supply and motor or engine drive.

Facts checked against Caprari's own history page and Ambienta's 2021 announcement, October 2026.

Frequently Asked Questions

What standard do the NMC and NMCS follow?
EN 733 (DIN 2455) for main features and dimensions, with an additional 80/400 size.
What is the difference between NMC and NMCS?
NMC has an integral motor pump shaft; NMCS has an extended shaft, an axial-thrust bearing and a standardised motor.
What motor protection and efficiency are printed?
IP55 enclosure, class F insulation, IE3 or IE4 efficiency, IE2 for the single-phase version.
What is the maximum liquid temperature?
140 C (284 F), for clean non-aggressive water.
Which special versions are available?
Bronze or stainless steel impellers, full bronze, inverter on board, special voltage and an IE4 motor.