PRESSURE SWITCH H100-190 United Electric, USA
Description
Overview
The United Electric H100-190 pressure switch is a low-range industrial unit engineered for reliable operation in services where system over-pressure events are common. Covering an adjustable set point range of 5 to 30 psi, it combines sensitive low-range detection with an outstanding proof pressure of 2500 psi.
Built in the USA by United Electric Controls, the H100-190 is a robust choice for low-pressure alarm, shutdown, and control duties on gas systems, tank blanketing, and process lines where impulse lines can see severe pressure transients.
Engineering & Design
The switch uses a diaphragm piston sensing element with a precision snap-action switch to ensure repeatable set point operation and a clean contact transfer. The 0.70 inch orifice provides reliable response in low-pressure services while the massive proof pressure rating protects the mechanism during commissioning and system upsets.
The Type 4X die-cast aluminium enclosure is epoxy powder coated, gasketed, and fitted with captive cover screws for weatherproof and corrosion-resistant installation. The 1/2 inch NPT female process connection with 316 stainless steel wetted parts suits standard piping, and the 15A electrical rating handles industrial control circuits directly.
Key Features
- Adjustable set point range 5 to 30 psi
- Dead band 1 to 6 psi
- Exceptional proof pressure 2500 psi
- Max over range pressure 1500 psi
- 316 stainless steel wetted parts
- 1/2 inch NPT female pressure connection with 0.70 inch orifice
- Type 4X certified die-cast aluminium enclosure
- 15A @ 125/250/480 VAC resistive electrical rating
- Ambient temperature -40°C to 71°C
Applications
- Low-pressure alarm and shutdown on gas systems
- Tank blanketing and pad pressure control
- Fuel gas low-pressure protection
- Filter differential pressure monitoring
- Instrument air system alarms
- Process lines with severe pressure transients
Specifications
| Specification | Value |
|---|---|
| Manufacturer | United Electric Controls, USA |
| Model | H100-190 |
| Adjustable Set Point Range | 5 to 30 psi |
| Dead Band | 1 to 6 psi |
| Max Over Range Pressure | 1500 psi |
| Proof Pressure | 2500 psi |
| Wetted Parts | 316 stainless steel |
| Pressure Connection | 1/2 inch NPT (female), 0.70 inch orifice |
| Enclosure | Type 4X, die-cast aluminium |
| Electrical Rating | 15A @ 125/250/480 VAC resistive |
| Ambient Temperature | -40°C to 71°C |
Services where pressure transients are a fact of life demand instruments with structural margin, and the United Electric H100-190 pressure switch offers a proof pressure of 2500 psi against a 5 to 30 psi set point range. This combination makes the H100-190 an excellent choice for gas systems and blanketing services where impulse lines can be exposed to severe over-pressure events.
Where pressure transients threaten low-range instruments, the United Electric H100-190 pressure switch provides the margin, and Seven Star LLC supplies the United Electric H100-190 pressure switch for gas and blanketing services.
The United Electric H100-190 pressure switch is adjusted to the trip point of the protective loop and is wired into the relay logic of the control panel. The internal switch element is rated for the 120 V AC control circuits, and the terminal strip is accessed through the cover without removing the switch from the line. The SPDT contact configuration allows the normally open and the normally closed wiring of the alarm or the shutdown function.
Why Seven Star LLC
Seven Star LLC supplies the United Electric H100-190 pressure switch with complete documentation, supporting both new projects and maintenance spares. Our team verifies set point ranges and electrical configurations to ensure the right switch for your application.
We serve oil and gas, power, and general industrial customers across Oman and the GCC with responsive B2B service and dependable after-sales support.
Robust Design
The 0.70 inch orifice and 316 stainless steel wetted parts are specified to handle the flow and compatibility requirements of low-pressure gas service, while the diaphragm piston element absorbs transient loads without shifting the set point. The Type 4X enclosure provides complete weather protection for outdoor installations.
With a dead band of 1 to 6 psi, the switch responds promptly to small pressure excursions while remaining stable in services with normal pressure ripple.
Identifying and Specifying the H100-190
United Electric H100 switches are ordered by model number, and the suffix shows the range and sensing configuration. For a like-for-like replacement, read the complete model number from the nameplate on the enclosure and confirm the set point range (5 to 30 psi for this model), the 1/2 inch NPT process connection and the electrical rating. If the application has changed since the original installation, check that the new set point sits comfortably inside the adjustable range rather than at either end.
Installation Best Practice
- Mount the switch on a vibration-free support and connect it through an isolation valve so it can be tested and replaced without shutting the line down.
- On gas services, slope impulse lines so condensate drains away from the switch. On liquid services, vent trapped air so that low set points are not affected by gas pockets.
- Where pressure pulsation is strong, for example near reciprocating compressors or pumps, fit a snubber to reduce contact chatter and wear.
- Use suitable cable glands and keep the cover gasket and captive screws in good condition to maintain the Type 4X enclosure rating.
Setting and Testing the Set Point
Adjust the set point with a calibrated pressure source connected through a test tee, raising and lowering the pressure slowly so both the trip and reset points can be recorded. The difference between them is the dead band. On this United Electric H100-190 pressure switch the dead band falls within the 1 to 6 psi range stated in the specifications. Record the as-found and as-left values on the calibration sheet for audit and trending.
Maintenance and Troubleshooting
Include the switch in the periodic function-test programme for the protection loop it serves. If the switch no longer trips at the set value, check for a blocked impulse line or isolation valve before adjusting it. If contacts chatter, look for pulsation or a set point very close to normal operating pressure. Inspect the enclosure for moisture inside, especially at coastal sites.
Applications in Oman and the GCC
Low-range switches with high proof pressure suit fuel gas skids, tank blanketing systems, flare and purge lines and utility air services at plants throughout Oman and the GCC. Seven Star LLC supplies United Electric switches for these duties and can match replacement units to the existing model code.
Request a Quote for PRESSURE SWITCH H100-190 United Electric, USA
For the United Electric H100-190 pressure switch, H100 series switch or any related control and instrumentation requirement, contact the Seven Star LLC team. Submit a formal inquiry through our RFQ page with your network, interface and power requirements, and our specialists will respond with a detailed commercial proposal and the official United documentation.
Other Models in the United Electric H100 Pressure Switches Range
Seven Star LLC supplies models from the United Electric H100 Pressure Switches range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| United Electric, USA H100-172 PRESSURE SWITCH | Pressure Instrumentation | View details |
| PRESSURE SWITCH H100-376 United Electric, USA | Pressure Instrumentation | View details |
| PRESSURE SWITCH H100-190 United Electric, USA | Pressure Instrumentation | You are viewing this model |
| PRESSURE SWITCH H100-361 United Electric, USA | Pressure Instrumentation | View details |
Related Products
Datasheets & Documents
- Datasheet United Electric controls PRESSURE SWITCH H100-190 United Electric, USA Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
United Electric Controls has made pressure and temperature switches since 1931 in Watertown, USA. Instrument technicians usually shorten the name to UE, which is also what appears on many nameplates.
Seven Star LLC lists United Electric pressure switches from the H100 family and the One Series and supplies them to plants in Oman for alarm and shutdown duties.
United Electric pressure switches listed here
Two kinds of UE switch are on this page:
- H100-172, H100-190, H100-361 and H100-376: electromechanical pressure switches from the 100 Series, which the manufacturer builds in a NEMA 4X enclosure. The number after the dash is the model that fixes the sensor type and the adjustable range.
- One Series 1XSWLL: an electronic pressure switch with a digital display, from UE's explosion-proof One Series.
An H100 switch needs no power to operate its contacts. A One Series unit is an electronic device, so its supply and output wiring must be considered when it replaces a mechanical switch.
Where United Electric switches are used
Pressure switches of this kind sit on pump discharge lines, compressor lube oil systems, burner trains, hydraulic units and process vessels. They raise an alarm or trip equipment when pressure moves outside a set limit. In oil and gas, power and water plants across the GCC they are found in alarm and shutdown circuits and on packaged equipment.
Ordering United Electric switches: what we need
A UE model is a string: the type, the model number and then option codes. Send it complete, exactly as on the nameplate, for example H100-190 plus any option codes that follow. If the nameplate is unreadable, give us the adjustable range, the set point and whether it acts on rising or falling pressure, the process connection, the wetted material, the switch output and the enclosure or hazardous-area requirement. For the One Series, the full 1XSWLL code with its range and option suffixes is needed. We check each code against the manufacturer documentation and propose the manufacturer's successor if a model is no longer built.
Browse United Electric controls products by category: Pressure Instrumentation.
Related products
Frequently Asked Questions
The adjustable set point range is 5 to 30 psi with a dead band of 1 to 6 psi.
The switch provides an exceptional proof pressure of 2500 psi with 1500 psi maximum over range pressure.
The H100-190 uses a 1/2 inch NPT female connection with a 0.70 inch orifice and 316 stainless steel wetted parts.
Yes, the Type 4X die-cast aluminium enclosure with gasketed captive cover is certified for outdoor and corrosive environments.
The switch is rated 15A at 125/250/480 VAC resistive, sufficient for direct switching of most industrial control circuits.