Brand:

Hager CEC441J 4P 40 A 100 mA Type AC RCCB

Description

CEC441J: Hager 4-pole 40 A 100 mA Type AC RCCB decoded

The Hager CEC441J is a residual current circuit breaker (RCCB) with 4 poles, a rated current of 40 A and a rated residual operating current of 100 mA, Type AC. It detects earth-leakage current by comparing the current in the live conductors and opens all poles when the imbalance exceeds the threshold. Seven Star LLC supplies CEC441J in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.

The 100 mA threshold is used for general earth-fault and equipment protection and discrimination. An RCCB does not protect against overload or short circuit, so it must always be coordinated with an MCB or fuse upstream. The table below decodes the catalogue description of CEC441J.

Element Value Meaning
RCCB Residual current circuit breaker Earth-leakage device without overcurrent release
4P 4 poles (3P+N) Poles switched by the device, including the neutral
40A 40 A rated current Maximum continuous load current through the device
100mA 100 mA sensitivity Rated residual operating current Idn
AC Type AC Detects sinusoidal AC residual current

CEC441J technical specifications

Parameter Specification
Manufacturer / part number Hager / CEC441J
Description RCCB 4P 40A 100mA AC
Poles 4 (3P+N)
Rated current In 40 A
Rated residual operating current Idn 100 mA
Residual current type AC
Breaking and opening capacity Idm 1.50 kA
Conditional short-circuit current Inc (EN 61008-1) 6 kA
Rated operational voltage Ue 240–415 V
Maximum operating voltage 415 V
Rated insulation voltage Ui 500 V
Rated impulse withstand voltage Uimp 4000 V
Frequency 50 Hz
Power dissipation 8.10 W (total loss)
Modules 4
Width x height x depth 70 x 83 x 70 mm
Conductors 1–25 mm² rigid, 1–16 mm² flexible
Terminal torque 2.80 Nm
Ingress protection IP20
Operating temperature −25 to 40 °C
Maximum altitude 2000 m
Mechanical / electrical endurance 4000 operations / 2000 cycles

How the CEC441J detects leakage

Inside CEC441J, a toroidal transformer encloses all live conductors. In a healthy circuit the currents cancel and the core sees no net flux. If part of the current returns through earth, through a person or a damaged insulation path, the balance is lost and the secondary winding drives a release that trips the mechanism. The device has a test button, which creates a small imbalance to confirm the mechanism, and the test should be pressed periodically.

Type AC devices respond to sinusoidal residual current. The breaking and opening capacity of 1.50 kA is the fault current the device itself can make and break under residual-current fault conditions, while the conditional short-circuit current of 6 kA is the level it can withstand when a suitable short-circuit protective device is placed upstream.

Where CEC441J fits in the board and related Hager parts

CEC441J is installed at the head of a final-circuit group or a sub-board and is fed through an MCB or fuse. Related references in the Hager range include CDC441J at 30 mA and CG463B at 500 mA, which cover the other sensitivity levels.

The catalogue page for CEC441J lists optional accessories such as the heat-dissipation insert LZ060. Check that an accessory is compatible with the width of the device before ordering.

Selection checklist for CEC441J

  • Confirm the sensitivity: 100 mA is intended for general earth-fault and equipment protection and discrimination
  • Confirm Type AC is right for the connected loads, since DC content needs Type A or better
  • Check the load current is below 40 A and that an upstream MCB or fuse protects the device
  • Compare the prospective short-circuit current with the 6 kA conditional rating
  • Check the voltage convention (240–415 V) against the network
  • Estimate total standing leakage current to avoid nuisance tripping
  • Check enclosure temperature against the −25 to 40 °C range

Installation, commissioning and maintenance of CEC441J

Mount CEC441J on the DIN rail, connect the supply conductors to the top terminals and the load to the bottom terminals, and tighten to 2.80 Nm. The datasheet gives 1–25 mm² rigid, 1–16 mm² flexible. Neutral conductors must pass through the device, and downstream neutrals must never be shared with another RCCB or connected to earth after it.

After wiring, press the test button to confirm the device trips, measure the trip current and time with a suitable tester where the site procedure requires it, and record the result. In service, test monthly or on the schedule in the maintenance plan, look for heat marks at the terminals, and replace any device that fails the test button check.

Typical applications of CEC441J in Oman and the GCC

CEC441J keeps the four-pole 40 A layout but raises the trip threshold to 100 mA. A 100 mA threshold is not for personal protection against direct contact; it is used for general earth-fault protection, for protection of equipment and for discrimination, where a 30 mA device installed downstream must trip first.

In Oman and the GCC, this is a typical upstream device in a two-stage residual-current scheme. It sits at the head of a board or feeder, with 30 mA RCCBs on the final circuits, so a leakage fault trips only the local circuit and not the whole building. Large standing leakage currents, for instance from variable-speed drives and filters in plant rooms, are also easier to live with at 100 mA. Dissipation is 8.10 W, the highest in the 40 A group.

CEC441J compared with other Hager RCCBs

Part number Poles In Idn Type Inc Ue
CD241J 2 40 A 30 mA AC 6 kA 230 V
CCC217J 2 16 A 10 mA AC 6 kA 240 V
CD440B 4 40 A 30 mA AC 10 kA 230–400 V
CD441J 4 40 A 30 mA AC 6 kA 230–400 V
CDC441J 4 40 A 30 mA AC 6 kA 240–415 V
CEC441J 4 40 A 100 mA AC 6 kA 240–415 V
CD485Z 4 100 A 30 mA AC 6 kA 240–415 V
CG463B 4 63 A 500 mA AC 10 kA 230–400 V
CD440J 4 40 A 30 mA A 6 kA 230–400 V

Values are taken from the manufacturer datasheets. Always verify the datasheet of the exact reference before ordering.

Information to send with an RFQ for CEC441J

To quote CEC441J quickly and without back-and-forth, send the details below with your enquiry.

  • Hager part number CEC441J and the quantity required
  • Number of poles, rated current, sensitivity and type if you are replacing an existing RCCB
  • Supply voltage and the upstream protective device
  • Whether accessories such as a locking kit or releases are needed
  • Project name, delivery location in Oman or the GCC and the required delivery date
  • Whether the datasheet, a declaration of conformity or other documents are needed with the shipment

Documents and quotation

A datasheet for CEC441J is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.

To request a quotation, send the part number CEC441J, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.

Other Models in the Hager Rccb Modular Range

Seven Star LLC supplies models from the Hager Rccb Modular range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Hager CD241J 2P 40 A 30 mA Type AC RCCBCircuit BreakersView details
Hager CCC217J 2P 16 A 10 mA Type AC RCCBCircuit BreakersView details
Hager CD440B 4P 40 A 30 mA Type AC RCCBCircuit BreakersView details
Hager CD441J 4P 40 A 30 mA Type AC RCCBCircuit BreakersView details
Hager CDC441J 4P 40 A 30 mA Type AC RCCBCircuit BreakersView details
Hager CEC441J 4P 40 A 100 mA Type AC RCCBCircuit BreakersYou are viewing this model
Hager CD485Z 4P 100 A 30 mA Type AC RCCBCircuit BreakersView details
Hager CG463B 4P 63 A 500 mA Type AC RCCBCircuit BreakersView details
Hager CD440J 4P 40 A 30 mA Type A RCCBCircuit BreakersView details
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.

Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.

Hager company profile

Founded January 1955, Ensheim, Saarland, Germany
Founders Peter Hager with his sons Oswald and Hermann
Headquarters Blieskastel, Germany
Ownership Hager family
First products Meter and distribution boards
Product families Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers

Milestones

  • 1955: Hager is founded in Ensheim.
  • 1959: The first French plant opens in Obernai.
  • 2025: Hager marks 70 years.

Hager product series

Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.

Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.

MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.

Where Hager devices are used

Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.

Hager products we list

Family Examples
Circuit Breakers CDC264J 2P 63 A 30 mA Type AC RCCB, HET250JR h3+ P250 3P 250 A 70 kA LSI Ele…, HHB250Z x250 3P 250 A 25 kA Thermal-Magn…, HHS063DC h3+ P160 3P 63 A 25 kA Thermal-…, HMT251GR h3+ P250 4P 250 A 50 kA LSnI El…, NBN106A 1P B-Curve 6 A Miniature Circuit…, SPB440D 4P Type 2 Surge Protection Devic…

Ordering Hager devices: what we need

Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.

Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.

FAQ

Questions about the Hager CEC441J 4P 40 A 100 mA Type AC RCCB

Answers from our engineering team on installation, compatibility and integration.

01What is the CEC441J?
It is a Hager 4-pole residual current circuit breaker rated 40 A with 100 mA sensitivity and Type AC detection. It occupies 4 modules and is mounted on a DIN rail.
02Does CEC441J protect against overload?
No. CEC441J detects earth leakage only. Overload and short-circuit protection must come from an upstream MCB or fuse, and the conditional short-circuit rating of 6 kA applies with such a device.
03What does Type AC mean for CEC441J?
Type AC devices detect sinusoidal AC residual current only. They are not meant for circuits with DC content from rectifiers or drives.
04What is the operating temperature of CEC441J?
The datasheet gives an operating range of −25 to 40 °C and a maximum altitude of 2000 m. In hot enclosures, check the actual temperature around the device.
05Can CEC441J be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number CEC441J and the quantity and Seven Star LLC will confirm availability and lead time.