Brand: Hager
Hager CG463B 4P 63 A 500 mA Type AC RCCB
Description
CG463B: Hager 4-pole 63 A 500 mA Type AC RCCB decoded
The Hager CG463B is a residual current circuit breaker (RCCB) with 4 poles, a rated current of 63 A and a rated residual operating current of 500 mA, Type AC. It detects earth-leakage current by comparing the current in the live conductors and opens all poles when the imbalance exceeds the threshold. Seven Star LLC supplies CG463B in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
The 500 mA threshold is used for fire-risk protection and discrimination at the head of a feeder. An RCCB does not protect against overload or short circuit, so it must always be coordinated with an MCB or fuse upstream. The table below decodes the catalogue description of CG463B.
| Element | Value | Meaning |
|---|---|---|
| RCCB | Residual current circuit breaker | Earth-leakage device without overcurrent release |
| 4P | 4 poles (3P+N) | Poles switched by the device, including the neutral |
| 63A | 63 A rated current | Maximum continuous load current through the device |
| 500mA | 500 mA sensitivity | Rated residual operating current Idn |
| AC | Type AC | Detects sinusoidal AC residual current |
CG463B technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Hager / CG463B |
| Description | RCCB 4P 63A 500mA AC |
| Poles | 4 (3P+N) |
| Rated current In | 63 A |
| Rated residual operating current Idn | 500 mA |
| Residual current type | AC |
| Breaking and opening capacity Idm | 0.63 kA |
| Conditional short-circuit current Inc (EN 61008-1) | 10 kA |
| Rated operational voltage Ue | 230–400 V |
| Maximum operating voltage | 440 V |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4000 V |
| Frequency | 50 Hz |
| Power dissipation | 19.70 W (total loss) |
| Modules | 4 |
| Width x height x depth | 70 x 83 x 70 mm |
| Conductors | 1–25 mm² rigid, 1–16 mm² flexible |
| Terminal torque | 2.80 Nm |
| Ingress protection | IP20 |
| Operating temperature | −25 to 40 °C |
| Maximum altitude | 2000 m |
| Mechanical / electrical endurance | 4000 operations / 2000 cycles |
How the CG463B detects leakage
Inside CG463B, a toroidal transformer encloses all live conductors. In a healthy circuit the currents cancel and the core sees no net flux. If part of the current returns through earth, through a person or a damaged insulation path, the balance is lost and the secondary winding drives a release that trips the mechanism. The device has a test button, which creates a small imbalance to confirm the mechanism, and the test should be pressed periodically.
Type AC devices respond to sinusoidal residual current. The breaking and opening capacity of 0.63 kA is the fault current the device itself can make and break under residual-current fault conditions, while the conditional short-circuit current of 10 kA is the level it can withstand when a suitable short-circuit protective device is placed upstream.
Where CG463B fits in the board and related Hager parts
CG463B is installed at the head of a final-circuit group or a sub-board and is fed through an MCB or fuse. Related references in the Hager range include CD485Z for 100 A and CEC441J for 100 mA sensitivity.
The catalogue page for CG463B lists optional accessories such as LZ060 and CZ001. Check that an accessory is compatible with the width of the device before ordering.
Selection checklist for CG463B
- Confirm the sensitivity: 500 mA is intended for fire-risk protection and discrimination at the head of a feeder
- Confirm Type AC is right for the connected loads, since DC content needs Type A or better
- Check the load current is below 63 A and that an upstream MCB or fuse protects the device
- Compare the prospective short-circuit current with the 10 kA conditional rating
- Check the voltage convention (230–400 V) against the network
- Estimate total standing leakage current to avoid nuisance tripping
- Check enclosure temperature against the −25 to 40 °C range
Installation, commissioning and maintenance of CG463B
Mount CG463B on the DIN rail, connect the supply conductors to the top terminals and the load to the bottom terminals, and tighten to 2.80 Nm. The datasheet gives 1–25 mm² rigid, 1–16 mm² flexible. Neutral conductors must pass through the device, and downstream neutrals must never be shared with another RCCB or connected to earth after it.
After wiring, press the test button to confirm the device trips, measure the trip current and time with a suitable tester where the site procedure requires it, and record the result. In service, test monthly or on the schedule in the maintenance plan, look for heat marks at the terminals, and replace any device that fails the test button check.
Typical applications of CG463B in Oman and the GCC
CG463B is a four-pole 63 A RCCB with a 500 mA trip threshold. This high value is not intended to protect people from contact. It is selected for protection of installations against fire risk caused by earth leakage, and for the head of a discriminating scheme, where lower-threshold devices sit further downstream.
In Oman and the GCC, 500 mA devices are found at the head of feeders to older buildings, workshops, pump stations and mixed-use plants, where a 30 mA threshold at the main would cause too many outages. The conditional short-circuit rating is 10 kA with a total power loss of 19.70 W at 63 A, and the breaking and opening capacity is given as 0.63 kA. Confirm that the upstream backup device respects the 10 kA figure.
CG463B compared with other Hager RCCBs
| Part number | Poles | In | Idn | Type | Inc | Ue |
|---|---|---|---|---|---|---|
| CD241J | 2 | 40 A | 30 mA | AC | 6 kA | 230 V |
| CCC217J | 2 | 16 A | 10 mA | AC | 6 kA | 240 V |
| CD440B | 4 | 40 A | 30 mA | AC | 10 kA | 230–400 V |
| CD441J | 4 | 40 A | 30 mA | AC | 6 kA | 230–400 V |
| CDC441J | 4 | 40 A | 30 mA | AC | 6 kA | 240–415 V |
| CEC441J | 4 | 40 A | 100 mA | AC | 6 kA | 240–415 V |
| CD485Z | 4 | 100 A | 30 mA | AC | 6 kA | 240–415 V |
| CG463B | 4 | 63 A | 500 mA | AC | 10 kA | 230–400 V |
| CD440J | 4 | 40 A | 30 mA | A | 6 kA | 230–400 V |
Values are taken from the manufacturer datasheets. Always verify the datasheet of the exact reference before ordering.
Information to send with an RFQ for CG463B
To quote CG463B quickly and without back-and-forth, send the details below with your enquiry.
- Hager part number CG463B and the quantity required
- Number of poles, rated current, sensitivity and type if you are replacing an existing RCCB
- Supply voltage and the upstream protective device
- Whether accessories such as a locking kit or releases are needed
- Project name, delivery location in Oman or the GCC and the required delivery date
- Whether the datasheet, a declaration of conformity or other documents are needed with the shipment
Documents and quotation
A datasheet for CG463B is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.
To request a quotation, send the part number CG463B, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.
Other Models in the Hager Rccb Modular Range
Seven Star LLC supplies models from the Hager Rccb Modular range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Hager CD241J 2P 40 A 30 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CCC217J 2P 16 A 10 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CD440B 4P 40 A 30 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CD441J 4P 40 A 30 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CDC441J 4P 40 A 30 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CEC441J 4P 40 A 100 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CD485Z 4P 100 A 30 mA Type AC RCCB | Circuit Breakers | View details |
| Hager CG463B 4P 63 A 500 mA Type AC RCCB | Circuit Breakers | You are viewing this model |
| Hager CD440J 4P 40 A 30 mA Type A RCCB | Circuit Breakers | View details |
Datasheets & Documents
- Datasheet Hager CG463B Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.
Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.
Hager company profile
| Founded | January 1955, Ensheim, Saarland, Germany |
|---|---|
| Founders | Peter Hager with his sons Oswald and Hermann |
| Headquarters | Blieskastel, Germany |
| Ownership | Hager family |
| First products | Meter and distribution boards |
| Product families | Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers |
Milestones
- 1955: Hager is founded in Ensheim.
- 1959: The first French plant opens in Obernai.
- 2025: Hager marks 70 years.
Hager product series
Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.
Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.
MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.
Where Hager devices are used
Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.
Hager products we list
Ordering Hager devices: what we need
Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.
Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.
Browse Hager products by category: Circuit Breakers.
FAQ
Questions about the Hager CG463B 4P 63 A 500 mA Type AC RCCB
Answers from our engineering team on installation, compatibility and integration.
01What is the CG463B?
It is a Hager 4-pole residual current circuit breaker rated 63 A with 500 mA sensitivity and Type AC detection. It occupies 4 modules and is mounted on a DIN rail.
02Does CG463B protect against overload?
No. CG463B detects earth leakage only. Overload and short-circuit protection must come from an upstream MCB or fuse, and the conditional short-circuit rating of 10 kA applies with such a device.
03What does Type AC mean for CG463B?
Type AC devices detect sinusoidal AC residual current only. They are not meant for circuits with DC content from rectifiers or drives.
04What is the operating temperature of CG463B?
The datasheet gives an operating range of −25 to 40 °C and a maximum altitude of 2000 m. In hot enclosures, check the actual temperature around the device.
05Can CG463B be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number CG463B and the quantity and Seven Star LLC will confirm availability and lead time.