Hager NCN106A 1P 6 A C-Curve 10 kA MCB

Description

NCN106A: Hager MCB 1P 10kA/15kA C-6A 1M explained

The Hager NCN106A is a 1-pole thermal-magnetic miniature circuit breaker, rated 6 A with a C characteristic and a breaking capacity of 10 kA / 15 kA for a 1-module width. It protects a final or sub-distribution circuit against overload and short-circuit and also acts as the local isolating device. Seven Star LLC supplies NCN106A in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.

The catalogue description reads “MCB 1P 10kA/15kA C-6A 1M”, and each element of it has a practical meaning when you choose the breaker for a board. The table below turns the description into plain engineering terms so you can compare NCN106A with other references on a bill of quantities.

Element Value What it means in practice
MCB Miniature circuit breaker Thermal-magnetic device for DIN rail mounting in a distribution board
1P 1 protected pole One pole that carries the release; the neutral is not switched
10 kA / 15 kA Breaking capacity Maximum fault level the device is rated to clear at the stated voltage
C-6A C curve, 6 A Trip characteristic and rated current at the 30 °C reference
1M 1 module Width of 17.5 mm on the DIN rail

NCN106A technical specifications

Parameter Specification
Manufacturer / part number Hager / NCN106A
Description MCB 1P 10kA/15kA C-6A 1M
Poles / curve 1P / C
Rated current In 6 A
Breaking capacity 10 kA at 230 V AC (IEC 60898-1), Icu 15 kA (IEC 60947-2), Ics 7.5 kA
Rated operational voltage Ue 230–400 V AC
Rated insulation voltage Ui 500 V
Rated impulse withstand voltage Uimp 6000 V
Frequency 50–60 Hz
Energy limitation class 3 (I²t)
Ingress protection IP20
Operating temperature −25 to 70 °C
Dissipation 1.33 W
Width x height x depth 17.5 x 83 x 70 mm
Conductors (screw terminals) 1–35 mm² rigid, 1–25 mm² flexible
Terminal torque 2.80 Nm
Standard pack 12 pieces per pack (catalogue)
Electrical endurance 4000 cycles

How the NCN106A protects the circuit

Inside NCN106A, a bimetal strip responds to sustained overcurrent and bends until it releases the latching mechanism, giving the inverse-time overload response. A magnetic coil acts instantly on a short circuit. The C characteristic releases magnetically at roughly five to ten times the rated current under the usual IEC 60898-1 convention, so it tolerates the starting current of motors, transformers and groups of power supplies without nuisance tripping.

The datasheet lists energy limitation class 3, which means the breaker restricts the let-through energy during a fault and so reduces thermal and mechanical stress on cables and downstream devices. Terminals are screw type with a biconnect bottom connection, and the breaker can be mounted in any position, which gives flexibility in tight enclosures.

Temperature behaviour of NCN106A

The datasheet gives the current that the breaker can carry at different ambient temperatures, referenced to 6 A at 30 °C. Heat inside a board is normal in Gulf conditions, so this table should be part of every loading check.

Ambient temperature Permissible current
20 °C 6.28 A
30 °C 6 A
40 °C 5.68 A
50 °C 5.35 A
60 °C 5.03 A
70 °C 4.7 A

The device is rated for operation from −25 to 70 °C and carries a dissipation of 1.33 W at rated current. When several breakers sit side by side and carry load for long periods, ambient temperature inside the enclosure can be much higher than the room, so allow for ventilation or spacing.

Where NCN106A fits and related Hager parts

NCN106A sits in the modular protection layer of a low-voltage board, downstream of an incomer or a larger moulded-case breaker and upstream of the cable to the load. Comparable references in the same range include NB110A and MT116A, which differ in pole count, curve, rating or breaking capacity.

The catalogue page for NCN106A lists optional accessories, including the padlockable locking kit MZN175, heat-dissipation insert LZ060, releases MZ203, MZ204, MZ206 and MZ212, contacts MZ201 and MZ202 and the insulated busbar KDN163B. Not every accessory fits every width, so verify the combination before ordering.

Selection checklist for NCN106A

  • Confirm the load current is below 6 A after derating for the board temperature
  • Compare the prospective short-circuit current at the board with the 10 kA / 15 kA rating
  • Check that the C curve matches the load: loads with inrush such as motors and transformers
  • Verify the supply voltage and number of poles required, including whether the neutral must be switched
  • Count the modules and the space left on the DIN rail, and check whether accessories are planned
  • Check the conductor size against the terminal range and the torque value

Installation, commissioning and maintenance of NCN106A

Mount NCN106A on a 35 mm DIN rail, connect the supply to the top screw terminal and the load to the biconnect bottom terminal, and tighten to 2.80 Nm. The datasheet lists 1–35 mm² rigid, 1–25 mm² flexible. Remove insulation to the length marked on the terminal and make sure no strands are left outside the clamp.

During commissioning, operate the handle to check the mechanism, confirm the correct handle position on all poles, measure insulation and loop impedance on the outgoing circuit and record the device reference on the circuit chart. In service, re-torque terminals during scheduled shutdowns, look for discoloured insulation next to the breaker and replace any device that has tripped on a high fault current, as the contacts may be worn.

Typical applications of NCN106A in Oman and the GCC

A 6 A C-curve breaker is sized for small control and signalling supplies, PLC power, panel lighting, compact motor-control feeds and small transformers whose magnetising inrush would nuisance-trip a B-curve device. This reference is notable for the higher impulse withstand value of 6000 V and for a quoted ultimate breaking capacity of 15 kA under IEC 60947-2 alongside the 10 kA household-standard figure.

For projects in Oman, the dual rating helps when a design office checks the breaker against both the building-installation standard and the industrial one. NCN106A is a natural fit for instrumentation and control panels in oil and gas and petrochemical facilities, where many small circuits are grouped on one DIN rail, and for process-area lighting boards, where the 70 °C upper limit of the datasheet reference table leaves useful margin inside hot enclosures.

NCN106A compared with other Hager MCBs

Part number Poles Curve Rated current Breaking capacity Modules
NB110A 1P B 10 A 10 kA 1
NCN106A 1P C 6 A 10 kA / 15 kA 1
MT116A 1P B 16 A 6 kA 1
MT140A 1P B 40 A 6 kA 1
MU216A 2P C 16 A 6 kA 2
NC332A 3P C 32 A 10 kA (400 V) 3
MW332 3P C 32 A 3 kA 3

The rows above are from the manufacturer datasheets. Use them for a first match, then check the full datasheet of the device you intend to buy.

Information to send with an RFQ for NCN106A

To quote NCN106A quickly and without back-and-forth, send the details below with your enquiry.

  • Hager part number NCN106A and the quantity required
  • Number of poles (1P), curve (C) and rated current (6 A) if you are replacing an existing breaker
  • Prospective short-circuit current at the board and the supply voltage
  • Any accessories needed, such as releases, contacts or a locking kit
  • Project name, delivery location in Oman or the GCC and the required delivery date
  • Whether the datasheet, a declaration of conformity or other documents are needed with the shipment

Documents and quotation

A datasheet for NCN106A is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.

To request a quotation, send the part number NCN106A, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.

Other Models in the Hager Mcb Modular Range

Seven Star LLC supplies models from the Hager Mcb Modular range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Hager NB110A 1P 10 A B-Curve 10 kA Miniature Circuit BreakerCircuit BreakersView details
Hager NCN106A 1P 6 A C-Curve 10 kA MCBCircuit BreakersYou are viewing this model
Hager MT116A 1P 16 A B-Curve 6 kA MCBCircuit BreakersView details
Hager MT140A 1P 40 A B-Curve 6 kA MCBCircuit BreakersView details
Hager MU216A 2P 16 A C-Curve 6 kA MCBCircuit BreakersView details
Hager NC332A 3P 32 A C-Curve 10 kA MCBCircuit BreakersView details
Hager MW332 3P 32 A C-Curve 3 kA MCBCircuit BreakersView details
Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.

Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.

Hager company profile

Founded January 1955, Ensheim, Saarland, Germany
Founders Peter Hager with his sons Oswald and Hermann
Headquarters Blieskastel, Germany
Ownership Hager family
First products Meter and distribution boards
Product families Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers

Milestones

  • 1955: Hager is founded in Ensheim.
  • 1959: The first French plant opens in Obernai.
  • 2025: Hager marks 70 years.

Hager product series

Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.

Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.

MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.

Where Hager devices are used

Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.

Hager products we list

Family Examples
Circuit Breakers CDC264J 2P 63 A 30 mA Type AC RCCB, HET250JR h3+ P250 3P 250 A 70 kA LSI Ele…, HHB250Z x250 3P 250 A 25 kA Thermal-Magn…, HHS063DC h3+ P160 3P 63 A 25 kA Thermal-…, HMT251GR h3+ P250 4P 250 A 50 kA LSnI El…, NBN106A 1P B-Curve 6 A Miniature Circuit…, SPB440D 4P Type 2 Surge Protection Devic…

Ordering Hager devices: what we need

Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.

Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.

FAQ

Questions about the Hager NCN106A 1P 6 A C-Curve 10 kA MCB

Answers from our engineering team on installation, compatibility and integration.

01What is the NCN106A?
It is a Hager 1-pole miniature circuit breaker rated 6 A with a C curve. The breaking capacity is 10 kA at 230 V AC (IEC 60898-1), Icu 15 kA (IEC 60947-2), Ics 7.5 kA, and it takes 1 module on the DIN rail.
02What breaking capacity does NCN106A have?
The datasheet lists 10 kA at 230 V AC (IEC 60898-1), Icu 15 kA (IEC 60947-2), Ics 7.5 kA. Always compare this value with the prospective fault level at the point of installation before selecting the breaker.
03How wide is NCN106A and how is it connected?
It is 17.5 mm wide and 70 mm deep, with a screw terminal at the top and a biconnect terminal at the bottom. It accepts 1–35 mm² rigid, 1–25 mm² flexible and is tightened to 2.80 Nm.
04Is the NCN106A suitable for high ambient temperatures?
The datasheet lists permissible current by temperature, for example 5.68 A at 40 °C, 5.35 A at 50 °C, 5.03 A at 60 °C. The device operates from −25 to 70 °C.
05Can NCN106A be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number NCN106A and the quantity, and Seven Star LLC will confirm availability and lead time.