Brand: Hager
Hager MT140A 1P 40 A B-Curve 6 kA MCB
Description
MT140A: Hager MCB 1P 6kA B-40A 1M explained
The Hager MT140A is a 1-pole thermal-magnetic miniature circuit breaker, rated 40 A with a B characteristic and a breaking capacity of 6 kA for a 1-module width. It protects a final or sub-distribution circuit against overload and short-circuit and also acts as the local isolating device. Seven Star LLC supplies MT140A in Oman and the GCC as an independent supplier in Muscat, not affiliated with the manufacturer.
The catalogue description reads “MCB 1P 6kA B-40A 1M”, and each element of it has a practical meaning when you choose the breaker for a board. The table below turns the description into plain engineering terms so you can compare MT140A with other references on a bill of quantities.
| Element | Value | What it means in practice |
|---|---|---|
| MCB | Miniature circuit breaker | Thermal-magnetic device for DIN rail mounting in a distribution board |
| 1P | 1 protected pole | One pole that carries the release; the neutral is not switched |
| 6 kA | Breaking capacity | Maximum fault level the device is rated to clear at the stated voltage |
| B-40A | B curve, 40 A | Trip characteristic and rated current at the 30 °C reference |
| 1M | 1 module | Width of 17.5 mm on the DIN rail |
MT140A technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Hager / MT140A |
| Description | MCB 1P 6kA B-40A 1M |
| Poles / curve | 1P / B |
| Rated current In | 40 A |
| Breaking capacity | 6 kA at 230 V AC (IEC 60898-1) |
| Rated operational voltage Ue | 230–400 V AC |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4000 V |
| Frequency | 50–60 Hz |
| Energy limitation class | 3 (I²t) |
| Ingress protection | IP20 |
| Operating temperature | −25 to 70 °C |
| Dissipation | 4.80 W |
| Width x height x depth | 17.5 x 83 x 70 mm |
| Conductors (screw terminals) | 1–35 mm² rigid, 1–25 mm² flexible |
| Terminal torque | 2.80 Nm |
| Standard pack | 12 pieces per pack (catalogue) |
How the MT140A protects the circuit
Inside MT140A, a bimetal strip responds to sustained overcurrent and bends until it releases the latching mechanism, giving the inverse-time overload response. A magnetic coil acts instantly on a short circuit. The B characteristic releases magnetically at a lower multiple of the rated current, typically about three to five times In under the usual IEC 60898-1 convention, so it is the right choice for resistive circuits and for long cable runs where the fault current is limited.
The datasheet lists energy limitation class 3, which means the breaker restricts the let-through energy during a fault and so reduces thermal and mechanical stress on cables and downstream devices. Terminals are screw type with a biconnect bottom connection, and the breaker can be mounted in any position, which gives flexibility in tight enclosures.
Temperature behaviour of MT140A
The datasheet gives the current that the breaker can carry at different ambient temperatures, referenced to 40 A at 30 °C. Heat inside a board is normal in Gulf conditions, so this table should be part of every loading check.
| Ambient temperature | Permissible current |
|---|---|
| 20 °C | 41.26 A |
| 30 °C | 40 A |
| 40 °C | 38.61 A |
| 50 °C | 37.22 A |
| 60 °C | 35.83 A |
| 70 °C | 34.44 A |
The device is rated for operation from −25 to 70 °C and carries a dissipation of 4.80 W at rated current. When several breakers sit side by side and carry load for long periods, ambient temperature inside the enclosure can be much higher than the room, so allow for ventilation or spacing.
Where MT140A fits and related Hager parts
MT140A sits in the modular protection layer of a low-voltage board, downstream of an incomer or a larger moulded-case breaker and upstream of the cable to the load. Comparable references in the same range include MT116A and NB110A, which differ in pole count, curve, rating or breaking capacity.
The catalogue page for MT140A lists optional accessories, including the heat-dissipation insert LZ060. Not every accessory fits every width, so verify the combination before ordering.
Selection checklist for MT140A
- Confirm the load current is below 40 A after derating for the board temperature
- Compare the prospective short-circuit current at the board with the 6 kA rating
- Check that the B curve matches the load: resistive or long-cable circuits
- Verify the supply voltage and number of poles required, including whether the neutral must be switched
- Count the modules and the space left on the DIN rail, and check whether accessories are planned
- Check the conductor size against the terminal range and the torque value
Installation, commissioning and maintenance of MT140A
Mount MT140A on a 35 mm DIN rail, connect the supply to the top screw terminal and the load to the biconnect bottom terminal, and tighten to 2.80 Nm. The datasheet lists 1–35 mm² rigid, 1–25 mm² flexible. Remove insulation to the length marked on the terminal and make sure no strands are left outside the clamp.
During commissioning, operate the handle to check the mechanism, confirm the correct handle position on all poles, measure insulation and loop impedance on the outgoing circuit and record the device reference on the circuit chart. In service, re-torque terminals during scheduled shutdowns, look for discoloured insulation next to the breaker and replace any device that has tripped on a high fault current, as the contacts may be worn.
Typical applications of MT140A in Oman and the GCC
Forty amperes in a single pole is a large rating for a modular breaker. It is typically used for dedicated loads such as an instantaneous water heater, a cooker, a small air-conditioning condensing unit or a sub-board feeder on a single phase. The B curve keeps the magnetic trip level low enough for a short fault to clear promptly, and the datasheet confirms the 6 kA breaking capacity at 230 V.
In Oman, the loading question is the one that matters most. At 40 A the datasheet lists 4.80 W of dissipation per pole, and the allowable current falls to 38.61 A at 40 °C and 37.22 A at 50 °C. In an outdoor switchboard in direct sun, or a packed distribution board with no ventilation, that reduction decides whether the circuit stays stable. MT140A is therefore best matched to loads with a continuous current comfortably below 40 A.
MT140A compared with other Hager MCBs
| Part number | Poles | Curve | Rated current | Breaking capacity | Modules |
|---|---|---|---|---|---|
| NB110A | 1P | B | 10 A | 10 kA | 1 |
| NCN106A | 1P | C | 6 A | 10 kA / 15 kA | 1 |
| MT116A | 1P | B | 16 A | 6 kA | 1 |
| MT140A | 1P | B | 40 A | 6 kA | 1 |
| MU216A | 2P | C | 16 A | 6 kA | 2 |
| NC332A | 3P | C | 32 A | 10 kA (400 V) | 3 |
| MW332 | 3P | C | 32 A | 3 kA | 3 |
The rows above are from the manufacturer datasheets. Use them for a first match, then check the full datasheet of the device you intend to buy.
Information to send with an RFQ for MT140A
To quote MT140A quickly and without back-and-forth, send the details below with your enquiry.
- Hager part number MT140A and the quantity required
- Number of poles (1P), curve (B) and rated current (40 A) if you are replacing an existing breaker
- Prospective short-circuit current at the board and the supply voltage
- Any accessories needed, such as releases, contacts or a locking kit
- Project name, delivery location in Oman or the GCC and the required delivery date
- Whether the datasheet, a declaration of conformity or other documents are needed with the shipment
Documents and quotation
A datasheet for MT140A is attached on this page. It lists the rated values used in the tables above, so your engineer can check them against the single-line diagram before an order is placed.
To request a quotation, send the part number MT140A, the quantity and your delivery location. Seven Star LLC will confirm availability and lead time and reply with a written offer.
Other Models in the Hager Mcb Modular Range
Seven Star LLC supplies models from the Hager Mcb Modular range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Hager NB110A 1P 10 A B-Curve 10 kA Miniature Circuit Breaker | Circuit Breakers | View details |
| Hager NCN106A 1P 6 A C-Curve 10 kA MCB | Circuit Breakers | View details |
| Hager MT116A 1P 16 A B-Curve 6 kA MCB | Circuit Breakers | View details |
| Hager MT140A 1P 40 A B-Curve 6 kA MCB | Circuit Breakers | You are viewing this model |
| Hager MU216A 2P 16 A C-Curve 6 kA MCB | Circuit Breakers | View details |
| Hager NC332A 3P 32 A C-Curve 10 kA MCB | Circuit Breakers | View details |
| Hager MW332 3P 32 A C-Curve 3 kA MCB | Circuit Breakers | View details |
Datasheets & Documents
- Datasheet Hager MT140A Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Hager Group is a German family-owned maker of electrical installation systems, founded in January 1955 in Ensheim, Saarland, by Peter Hager with his sons Oswald and Hermann. It first made meter and distribution boards and opened its first French plant in Obernai, Alsace, in 1959. The group is headquartered in Blieskastel, Germany, and still controlled by the Hager family.
Seven Star LLC is an independent supplier in Muscat. We list Hager protective devices for panel builders and contractors in Oman and the GCC.
Hager company profile
| Founded | January 1955, Ensheim, Saarland, Germany |
|---|---|
| Founders | Peter Hager with his sons Oswald and Hermann |
| Headquarters | Blieskastel, Germany |
| Ownership | Hager family |
| First products | Meter and distribution boards |
| Product families | Miniature circuit breakers, RCDs and RCBOs, h3+ moulded-case circuit breakers, consumer units and distribution boards, enclosures, surge protection, KNX and building automation, EV chargers |
Milestones
- 1955: Hager is founded in Ensheim.
- 1959: The first French plant opens in Obernai.
- 2025: Hager marks 70 years.
Hager product series
Modular devices include the NBN106A 1P B-curve 6 A miniature circuit breaker, the CDC264J 2P 63 A 30 mA Type AC RCCB, the SPB440D 4P Type 2 surge protection device and the ESC125 25 A modular contactor.
Moulded case circuit breakers include the HHS063DC h3+ P160 63 A, the HHB250Z x250 250 A thermal-magnetic MCCB, the HET250JR h3+ P250 with LSI electronic trip and 70 kA breaking and the HMT251GR h3+ P250 four-pole LSnI electronic MCCB.
MCB curves set the magnetic trip: B for resistive loads and long cables, C for general use and D for motors and transformers. Electronic MCCB trip units such as LSI and LSnI allow long time, short time, instantaneous and neutral settings to coordinate with downstream devices.
Where Hager devices are used
Final distribution boards, main and sub-main panels, building services and commercial and industrial installations.
Hager products we list
Ordering Hager devices: what we need
Send the Hager reference, or the rated current, poles, curve or trip unit, breaking capacity and accessories required.
Facts checked against Hager Group's own history pages (hagergroup.com), October 2026.
Browse Hager products by category: Circuit Breakers.
FAQ
Questions about the Hager MT140A 1P 40 A B-Curve 6 kA MCB
Answers from our engineering team on installation, compatibility and integration.
01What is the MT140A?
It is a Hager 1-pole miniature circuit breaker rated 40 A with a B curve. The breaking capacity is 6 kA at 230 V AC (IEC 60898-1), and it takes 1 module on the DIN rail.
02What breaking capacity does MT140A have?
The datasheet lists 6 kA at 230 V AC (IEC 60898-1). Always compare this value with the prospective fault level at the point of installation before selecting the breaker.
03How wide is MT140A and how is it connected?
It is 17.5 mm wide and 70 mm deep, with a screw terminal at the top and a biconnect terminal at the bottom. It accepts 1–35 mm² rigid, 1–25 mm² flexible and is tightened to 2.80 Nm.
04Is the MT140A suitable for high ambient temperatures?
The datasheet lists permissible current by temperature, for example 38.61 A at 40 °C, 37.22 A at 50 °C, 35.83 A at 60 °C. The device operates from −25 to 70 °C.
05Can MT140A be supplied with a datasheet?
Yes, the datasheet is attached on this page. Send the part number MT140A and the quantity, and Seven Star LLC will confirm availability and lead time.


















Reviews