Allen-Bradley PowerFlex 525 25B-D017N114 7.5 kW AC Drive

Description

The 7.5 kW PowerFlex 525 with integral filter

The Allen-Bradley 25B-D017N114 is a 7.5 kW (10 HP) PowerFlex 525 with 17.0 A output at 380 to 480 V, the top rating of Frame C. For many plants it is the standard drive for 7.5 kW process pumps and fans because it fits the compact 109 mm frame, can still be DIN-rail mounted, and includes an integral EMC filter, EtherNet/IP and Safe Torque Off.

The drive provides closed-loop velocity vector control, permanent magnet motor control and PointStop positioning, so it can serve in light machine automation as well as in utilities. Overload capability is 110 percent for 60 seconds in normal duty.

Technical specifications

Parameter Specification
Catalog number 25B-D017N114 (PowerFlex 525, bulletin 25B)
Input voltage / phases 380…480V AC (-15%, +10%), 3-phase; input voltage range 323…528V
Output 0…460V, 3-phase, 0…500 Hz programmable
Normal duty rating 7.5 kW (10 HP)
Heavy duty rating 7.5 kW (10 HP)
Output current 17.0 A
Frame size / mounting Frame C; DIN rail or screw mounting
Dimensions / weight 109.0 x 220.0 x 184.0 mm (4.29 x 8.66 x 7.24 in.), W x H x D; 2.3 kg (5.0 lb)
Total watts loss 230 W
EMC filter Integral EMC filter fitted (emission class 1)
Input current (two values as printed) 16.8 A / 18.4 A
Contactor / breaker (UL table) 100-E26 (UL); IEC 100-C23 / 100-E26 / 140MT-D9E-C20
IEC fuse range (min / max, A) 25 / 40
Overload Normal duty 110% for 60 s, 150% for 3 s; heavy duty 150% for 60 s, 180% for 3 s (200% programmable)
Control methods V/Hz, sensorless vector, SVC economizer, closed-loop velocity vector, PM motor control
Carrier frequency 2…16 kHz, drive rating based on 4 kHz
Efficiency / power factor 97.5% typical; displacement power factor 0.98
Control inputs 7 digital (6 programmable), 2 isolated analog (±10V or 0…10V and 4…20 mA), pulse input to 100 kHz
Control outputs 2 relays (1 Form A, 1 Form B), 2 opto outputs, 1 analog output 0…10V or 4…20 mA
Safety Safe Torque Off, Cat. 3 / PLd (EN ISO 13849-1), SIL CL2 (EN 62061); TÜV Rheinland certified
Ambient temperature -20…+50 °C without derating; up to 60 °C (70 °C with control module fan kit) with derating; altitude 1000 m without derating
Sound pressure level 57 dBA at 1 m (frame C)
Certifications (as printed) c-UL-us (UL 61800-5-1, CSA C22.2 No. 274-17), RCM, CE (LVD, EMC, ATEX, Machinery, RoHS), UKCA, TÜV functional safety

Choosing the N114 or N104 version

The N114 in this catalog number means the drive has an integral EMC filter and standard interface module, losing 230 W, while the N104 (25B-D017N104) has no filter and loses 221 W. Select the filtered version when the drive is the only EMC measure in the installation, for example with a shielded motor cable, and the non-filtered version when an external filter or an isolated supply is used.

Protection devices from the table are the 100-E26 contactor, the 140MT-D9E-C20 motor protector and IEC fuses of 25 to 40 A. In a multi-drive panel the heat is concentrated, so check the 230 W loss against the panel size.

Catalog code and family ratings

Reading the catalog number: 25B is the PowerFlex 525, D is the 380…480V 3-phase supply, the next group is the output current code, N is the IP20 open enclosure, 1 is the standard interface, and the following digit is the emission class: 1 means an integral EMC filter and 0 means no filter. The last digit 4 is the version.

Catalog number (filtered) Normal duty kW (HP) Output current Frame
25B-D1P4N114 0.4 (0.5) 1.4 A A
25B-D2P3N114 0.75 (1.0) 2.3 A A
25B-D4P0N114 1.5 (2.0) 4.0 A A
25B-D6P0N114 2.2 (3.0) 6.0 A A
25B-D010N114 4.0 (5.0) 10.5 A B
25B-D013N114 5.5 (7.5) 13.0 A C
25B-D017N114 7.5 (10) 17.0 A C
25B-D024N114 11 (15) 24.0 A D
25B-D030N114 15 (20) 30.0 A D
25B-D037N114 18.5 (25) 37.0 A E
25B-D043N114 22 (30) 43.0 A E

Key features for 7.5 kW pump and fan duty

  • Modular construction: the control module separates from the power module, so programming and wiring can start before the power section is installed.
  • Embedded EtherNet/IP port with integration into Studio 5000 Logix Designer through Add-on Profiles, which reduces separate configuration work on Logix-based systems.
  • Safe Torque Off built in, so a safety relay can remove torque without switching the motor supply through a contactor for every stop.
  • Several motor control modes in one drive, from simple V/Hz for fans to sensorless vector and closed-loop velocity vector for conveyors and positioning.
  • SVC economizer mode, which reduces motor flux at light load to save energy on variable-torque loads.
  • Configuration through the integral keypad, Connected Components Workbench software or a USB connection, with the ability to program the control module without mains power through USB.

Sizing considerations

Select the drive on motor full-load current rather than on kilowatts alone. A standard four-pole 7.5 kW motor at 400 V usually draws less than the 17.0 A rating, but high-pole-count, older or special motors may draw more, and the motor nameplate current must stay within the drive output current at the expected duty. For loads that need high starting torque or frequent acceleration, such as loaded conveyors, mixers or positive displacement pumps, check the heavy duty overload rating and consider stepping up a size where repeated peaks are expected.

Above 1000 m altitude, above 50 °C ambient or at high carrier frequency, derating applies; the derating curves in the specifications document should be used when the drive is installed in a hot plant room or an outdoor enclosure.

Panel installation tips

  • Keep the minimum clearances above and below the drive given by Rockwell Automation to allow cooling air flow, and remember that side-by-side mounting may require derating.
  • Use shielded motor cable with the shield bonded at both ends for best EMC performance with the integral filter.
  • Separate power and control wiring, and run analog signals in shielded twisted pair cable.
  • For long motor cables, check the manufacturer recommendations on output reactors or dV/dt filters to protect motor insulation.
  • Wire the Safe Torque Off terminals as the safety design requires; the factory jumper must be removed when STO is used.

Commissioning and maintenance

Enter the motor nameplate data and run the autotune routine before operating in vector modes. Save the parameter file to a PC or the control module so a replacement drive can be loaded quickly. Periodic maintenance consists of cleaning cooling fins and fan inlets, checking terminal tightness and reviewing the fault log; the cooling fan is a wear item and should be inspected during scheduled shutdowns.

Applications in Oman and GCC conditions

Typical duties include chilled water and condenser water pumps, cooling tower and AHU fans, booster sets, conveyor drives and small compressors. Many panels in the region operate in hot, dusty rooms, so filtered ventilation or air conditioning of the enclosure is often required to keep the drive within its rated ambient range. Where generators supply the plant, the drive input protection should be coordinated with the generator capacity and voltage variations.

What to include in an RFQ

  • Catalog number 25B-D017N114 and quantity.
  • Motor kW, full-load current and supply voltage.
  • Required communication options and any accessories such as keypads or fan kits.

Documents and quotation

Seven Star LLC supplies PowerFlex 525 drives against the full catalog number. The Rockwell Automation PowerFlex 520-series specifications document is attached. Compare with the Allen-Bradley PowerFlex 525 page and see the AC drives category. Confirm the exact catalog number, series letter and firmware or hardware revision on the product label, and the compatibility with your existing system, before ordering. Stock and lead time are confirmed at quotation.

Datasheets & Documents
  • PDF Technical data Rockwell Automation PowerFlex 520-series AC Drive Specifications, publication 520-TD001 (English) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Catalog numbers beginning 1756, 1734, 1746 or 5069 are read at a glance by anyone who maintains Allen-Bradley control panels. The brand, the control hardware name of Rockwell Automation, dates back to 1903 in Milwaukee, USA. Seven Star LLC sources and supplies Allen-Bradley PLC and I/O modules, communication adapters and PowerFlex drives for plants in Oman, matching catalog number, series letter and firmware against the manufacturer's documentation.

Allen-Bradley product families listed here

Current controller platforms on this page are ControlLogix, with the 1756-L85E ControlLogix 5580 controller and the 1756-PA72 chassis power supply, and CompactLogix 5380, with the 5069-L320ER and 5069-L340ERM. Distributed I/O is represented by POINT I/O: the 1734-AENTR dual-port EtherNet/IP adapter and the 1734-IB8 digital input module. Allen-Bradley drives listed include the PowerFlex 525 and PowerFlex 755. For installed systems there are SLC 500 parts: the 1746-A10 chassis, 1746-NI16I analog input module, 1747-ASB remote I/O adapter, 1747-KE interface and 1747-M13 memory module.

Where Allen-Bradley hardware is used

ControlLogix and CompactLogix controllers run packaged equipment and plant utilities: compressor and pump skids, water and wastewater plants, power distribution, material handling and packaging lines. PowerFlex drives control pumps, fans and conveyors. Many SLC 500 racks are still in service.

Ordering Allen-Bradley modules and drives: what we need

Send the full catalog number, the series letter and, for controllers and communication modules, the firmware revision printed on the side label. Compatibility with an existing project depends on these. For PowerFlex drives, give the complete catalog string, which encodes voltage, current rating, enclosure and options, plus the motor nameplate data. For SLC 500 parts, tell us the rack size and processor so that we can check slot and power supply loading in the manufacturer's manuals. A label photo avoids most mistakes.

Frequently Asked Questions

What is the rating of the 25B-D017N114?
7.5 kW (10 HP) at 380 to 480 V, 17.0 A output, Frame C.
Does the N114 version have a filter?
Yes, an integral EMC filter is included; the N104 version does not have one.
How much heat does it dissipate?
230 W for the filtered N114 and 221 W for the N104.
Which breaker does Rockwell list?
The 140MT-D9E-C20 manual motor controller, with the 100-E26 contactor and 25 to 40 A IEC fuses.
Can it control permanent magnet motors?
Yes, the PowerFlex 525 supports surface mount and interior PM motor control.