A residual current device (RCD) disconnects a circuit when current leaks to earth, for example through a damaged cable, a faulty appliance or a person touching a live part. It protects people against electric shock and installations against fire caused by earth faults, which an ordinary circuit breaker cannot detect because the leakage current is far below its trip level. This guide explains how an RCD works, the difference between an RCCB and an RCBO, the waveform types AC, A, F and B, and how to select the sensitivity.

How a Residual Current Device Works

All live conductors of the circuit (phase and neutral, or the three phases and neutral) pass through a toroidal current transformer inside the device. In a healthy circuit the currents going out and coming back are equal, so their magnetic fields cancel. If some current returns through earth instead, the sum is no longer zero. This difference is the residual current. When it reaches the trip level, the transformer energises a release that opens the contacts.

  • The rated residual operating current is written as IΔn, for example 30 mA.
  • Under the product standards, the device must not trip below 50% of IΔn and must trip at IΔn, so a 30 mA device trips somewhere between 15 and 30 mA.
  • A general (non-delayed) type must trip within 300 ms at IΔn and within 40 ms at 5 × IΔn.
  • An RCD does not detect current flowing from phase to neutral, so it does not protect against overload or short circuit unless it is combined with a circuit breaker.

RCCB, RCBO, Add-On Blocks and Earth Leakage Relays

DeviceStandardWhat it doesTypical use
RCCB (residual current circuit breaker)IEC 61008Earth leakage protection only; needs an upstream or downstream MCBProtecting a group of circuits in a distribution board
RCBO (residual current breaker with overcurrent protection)IEC 61009Earth leakage plus overload and short-circuit protection in one deviceOne RCBO per final circuit, so one fault trips only that circuit
RCD add-on block (for example Vigi modules)IEC 61009 / manufacturer systemClips onto an MCB to make an RCBOAdding earth leakage protection to an existing MCB range
Earth leakage relay with toroidIEC 60947-2 Annex MMeasures leakage with an external toroid and trips a breaker through a shunt tripHigh currents, MCCBs and ACBs, adjustable sensitivity and delay
Residual current monitor (RCM)IEC 62020Measures and alarms without trippingMonitoring insulation and leakage where tripping is not acceptable

A practical rule: an RCCB protecting several circuits is cheaper, but a single fault switches off all of them. RCBOs cost more per circuit but keep the rest of the installation running. For background on breaker types and trip curves, see our guide to circuit breaker types: MCB vs MCCB vs ACB.

Residual Current Device Types: AC, A, F and B

The type letter tells you which leakage current waveforms the residual current device will detect. Modern loads with electronics produce leakage currents that are not simple sine waves, and a device of the wrong type may not trip, or may be blinded by a DC component.

TypeDetectsTypical loads
ACSinusoidal AC residual current onlySimple resistive loads; restricted or no longer permitted in some countries
AAC plus pulsating DC (with a small smooth DC component, typically up to 6 mA)Single-phase electronics, washing machines, lighting with drivers, general use
FType A plus composite currents of mixed frequency from single-phase inverters, with higher DC toleranceSingle-phase variable speed drives, heat pumps, inverter air conditioners
BType F plus smooth DC residual current and higher frequencies (typically up to 1 kHz)Three-phase VFDs, UPS, PV inverters, EV chargers without DC detection, medical equipment

Type A, F and B devices are defined in IEC 61008, IEC 61009 and IEC 62423. Some manufacturers also offer B+ or B-SI versions with a wider frequency range or better immunity to nuisance tripping. For EV charging, the charger either includes a 6 mA DC detection device, in which case a Type A RCD is commonly used upstream, or a Type B device is needed; follow the charger manufacturer instructions and the local wiring rules.

Choosing the Sensitivity: 10, 30, 100, 300 mA and Above

IΔnMain purposeTypical application
10 mAHigh-sensitivity personal protectionBathrooms, laboratories, medical and special locations where required
30 mAAdditional protection against electric shockSocket outlet circuits, outdoor equipment, portable tools, final circuits
100 mAFault protection and selectivityUpstream of 30 mA devices, some equipment circuits
300 mAProtection against fire caused by earth faultsIncomers and sub-main feeders, agricultural and fire-risk locations
500 mA and adjustableEquipment and installation protectionIndustrial feeders with earth leakage relays

IEC 60364-4-41 requires additional protection by a residual current device of not more than 30 mA for socket outlets up to 32 A used by ordinary persons, and for mobile equipment used outdoors, with limited exceptions. Local regulations can add further requirements, so always check the rules that apply to the project.

Time-Delayed (S Type) RCDs and Selectivity

When two RCDs are in series, a fault on a final circuit can trip both, switching off the whole board. To keep the upstream device closed, use a selective (S type) device upstream. An S type has a built-in time delay; it must not trip in less than 130 ms at 2 × IΔn and must trip within 500 ms at IΔn.

  • Use an S type device upstream and a general type downstream.
  • Make the upstream IΔn at least three times the downstream value, for example 300 mA S upstream of 30 mA.
  • Earth leakage relays allow adjustable sensitivity and delay for selectivity between larger feeders.
  • S type devices are not used for 30 mA additional protection, because the delay defeats the purpose.

Nuisance Tripping: Causes and Fixes

An RCD that trips without an obvious fault is usually responding to real leakage that adds up from many loads, or to transients:

  • Standing leakage from EMC filters in computers, drives, LED drivers and power supplies. A common design guideline is to keep the total standing leakage on one device below about 30% of IΔn, so split the loads across more devices or RCBOs.
  • Long cables, which have capacitance to earth and leak current, especially with VFDs.
  • Surges from lightning or switching; immune or super-immune versions (often marked SI or Hpi) resist this.
  • Neutral-to-earth faults, or a neutral shared between two RCD-protected circuits.
  • Moisture in outdoor fittings, junction boxes and heating elements.
  • Wrong type: a Type A device next to a three-phase VFD can be blinded or trip erratically; use Type B where the drive manufacturer requires it.

Never bypass a tripping residual current device. Find the fault with an insulation resistance test and a leakage clamp meter, circuit by circuit.

Testing and Maintenance

  1. Press the test button at the interval stated by the manufacturer or local rules, often every three or six months. The button checks the mechanism, not the earth connection or the trip time.
  2. Use an RCD tester to measure the trip time at IΔn and 5 × IΔn during periodic inspection, and record the results.
  3. Check that the device type (AC, A, F, B) still suits the loads after equipment changes, such as new drives or chargers.
  4. Inspect the terminals for heat damage and tighten to the specified torque during shutdown.

Residual Current Devices From Our Catalog

Examples of RCD types in our catalog. Each link goes to the product page.

ProductTypeTypical use
Schneider Electric 16924 Acti9 RCCB-ID 30 mA Type ARCCB, Type A, 30 mASocket and final circuit groups
Schneider Electric EZ9R36263 Easy9 2P 63 A 30 mA RCCBRCCB, 2-poleResidential and small commercial boards
Schneider Electric A9R12463 Acti9 iID 4P 63 A 100 mA RCCBRCCB, 4-pole, 100 mAThree-phase distribution, selectivity
Schneider Electric R9R54263 Resi9 2P 63 A 300 mA RCCBRCCB, 300 mAFire protection at incomers
Hager CD440J 4P 40 A 30 mA Type A RCCBRCCB, 4-pole, Type AThree-phase final circuits
Hager CCC217J 2P 16 A 10 mA Type AC RCCBRCCB, 10 mAHigh-sensitivity circuits
Schneider Electric A9D14816 iC60H RCBO 16 A 30 mA 1P+NRCBOOne device per final circuit
CHINT NXBLE-32 RCBO Residual Current Circuit Breaker, 6-32 ARCBOFinal circuits in compact boards
Schneider Electric A9V41463 Vigi iC60 4P 63 A 30 mARCD add-on blockAdding earth leakage protection to an MCB
Schneider Electric Vigirex RH197M Ground Fault RelayEarth leakage relayMCCB and ACB feeders with adjustable settings
Lovato 31RC60415 Earth Leakage Relay 60 mm Toroid, Type AEarth leakage relay with toroidIndustrial feeders
Bender RCMA420-D-2 AC/DC Residual Current Monitor, 10-500 mAAC/DC residual current monitorMonitoring without tripping

Browse more in our circuit breakers category. To get a quotation, send the number of poles, rated current, sensitivity, type (AC, A, F or B), breaking capacity for RCBOs, and the part number of any existing device through our quote request form or to [email protected].

Sourcing Residual Current Devices in Oman Through Seven Star LLC

Seven Star LLC is an independent supplier in Oman of low-voltage switchgear and protection devices for commercial buildings, industry, oil and gas and utilities. We quote RCCBs, RCBOs, add-on blocks, earth leakage relays and residual current monitors from manufacturers such as Schneider Electric, ABB, Hager, Eaton, CHINT, Lovato and Bender, and can match an installed device by part number. Specifications, approvals and lead time are confirmed against the manufacturer data at quotation.

Frequently asked questions

What is the difference between an RCCB and an RCBO?

An RCCB (IEC 61008) detects earth leakage only and must be used with a circuit breaker for overload and short-circuit protection. An RCBO (IEC 61009) combines earth leakage, overload and short-circuit protection in one device, so each final circuit can have its own protection.

Which residual current device type do I need for a VFD?

Single-phase drives usually need at least Type F. Three-phase drives can produce smooth DC leakage, so Type B is normally required. Always follow the drive manufacturer recommendation.

Is a 30 mA or 300 mA RCD better?

They do different jobs. A 30 mA device gives additional protection against electric shock on final circuits. A 300 mA device protects against fire caused by earth faults and is often used at the incomer, usually as an S type for selectivity.

Why does my RCD trip for no reason?

Common causes are accumulated standing leakage from electronic loads, long cables, surges, moisture, neutral-to-earth faults and the wrong device type. Split the loads, use immune versions and test each circuit for insulation and leakage.

How often should a residual current device be tested?

Press the test button at the interval stated by the manufacturer or local rules, often every three or six months, and measure the trip time with an RCD tester during periodic inspection.