A residual current device (RCD) disconnects a circuit when current leaks to earth, for example through a damaged cable, a faulty appliance or a person touching a live part. It protects people against electric shock and installations against fire caused by earth faults, which an ordinary circuit breaker cannot detect because the leakage current is far below its trip level. This guide explains how an RCD works, the difference between an RCCB and an RCBO, the waveform types AC, A, F and B, and how to select the sensitivity.
How a Residual Current Device Works
All live conductors of the circuit (phase and neutral, or the three phases and neutral) pass through a toroidal current transformer inside the device. In a healthy circuit the currents going out and coming back are equal, so their magnetic fields cancel. If some current returns through earth instead, the sum is no longer zero. This difference is the residual current. When it reaches the trip level, the transformer energises a release that opens the contacts.
- The rated residual operating current is written as IΔn, for example 30 mA.
- Under the product standards, the device must not trip below 50% of IΔn and must trip at IΔn, so a 30 mA device trips somewhere between 15 and 30 mA.
- A general (non-delayed) type must trip within 300 ms at IΔn and within 40 ms at 5 × IΔn.
- An RCD does not detect current flowing from phase to neutral, so it does not protect against overload or short circuit unless it is combined with a circuit breaker.
RCCB, RCBO, Add-On Blocks and Earth Leakage Relays
| Device | Standard | What it does | Typical use |
|---|---|---|---|
| RCCB (residual current circuit breaker) | IEC 61008 | Earth leakage protection only; needs an upstream or downstream MCB | Protecting a group of circuits in a distribution board |
| RCBO (residual current breaker with overcurrent protection) | IEC 61009 | Earth leakage plus overload and short-circuit protection in one device | One RCBO per final circuit, so one fault trips only that circuit |
| RCD add-on block (for example Vigi modules) | IEC 61009 / manufacturer system | Clips onto an MCB to make an RCBO | Adding earth leakage protection to an existing MCB range |
| Earth leakage relay with toroid | IEC 60947-2 Annex M | Measures leakage with an external toroid and trips a breaker through a shunt trip | High currents, MCCBs and ACBs, adjustable sensitivity and delay |
| Residual current monitor (RCM) | IEC 62020 | Measures and alarms without tripping | Monitoring insulation and leakage where tripping is not acceptable |
A practical rule: an RCCB protecting several circuits is cheaper, but a single fault switches off all of them. RCBOs cost more per circuit but keep the rest of the installation running. For background on breaker types and trip curves, see our guide to circuit breaker types: MCB vs MCCB vs ACB.
Residual Current Device Types: AC, A, F and B
The type letter tells you which leakage current waveforms the residual current device will detect. Modern loads with electronics produce leakage currents that are not simple sine waves, and a device of the wrong type may not trip, or may be blinded by a DC component.
| Type | Detects | Typical loads |
|---|---|---|
| AC | Sinusoidal AC residual current only | Simple resistive loads; restricted or no longer permitted in some countries |
| A | AC plus pulsating DC (with a small smooth DC component, typically up to 6 mA) | Single-phase electronics, washing machines, lighting with drivers, general use |
| F | Type A plus composite currents of mixed frequency from single-phase inverters, with higher DC tolerance | Single-phase variable speed drives, heat pumps, inverter air conditioners |
| B | Type F plus smooth DC residual current and higher frequencies (typically up to 1 kHz) | Three-phase VFDs, UPS, PV inverters, EV chargers without DC detection, medical equipment |
Type A, F and B devices are defined in IEC 61008, IEC 61009 and IEC 62423. Some manufacturers also offer B+ or B-SI versions with a wider frequency range or better immunity to nuisance tripping. For EV charging, the charger either includes a 6 mA DC detection device, in which case a Type A RCD is commonly used upstream, or a Type B device is needed; follow the charger manufacturer instructions and the local wiring rules.
Choosing the Sensitivity: 10, 30, 100, 300 mA and Above
| IΔn | Main purpose | Typical application |
|---|---|---|
| 10 mA | High-sensitivity personal protection | Bathrooms, laboratories, medical and special locations where required |
| 30 mA | Additional protection against electric shock | Socket outlet circuits, outdoor equipment, portable tools, final circuits |
| 100 mA | Fault protection and selectivity | Upstream of 30 mA devices, some equipment circuits |
| 300 mA | Protection against fire caused by earth faults | Incomers and sub-main feeders, agricultural and fire-risk locations |
| 500 mA and adjustable | Equipment and installation protection | Industrial feeders with earth leakage relays |
IEC 60364-4-41 requires additional protection by a residual current device of not more than 30 mA for socket outlets up to 32 A used by ordinary persons, and for mobile equipment used outdoors, with limited exceptions. Local regulations can add further requirements, so always check the rules that apply to the project.
Time-Delayed (S Type) RCDs and Selectivity
When two RCDs are in series, a fault on a final circuit can trip both, switching off the whole board. To keep the upstream device closed, use a selective (S type) device upstream. An S type has a built-in time delay; it must not trip in less than 130 ms at 2 × IΔn and must trip within 500 ms at IΔn.
- Use an S type device upstream and a general type downstream.
- Make the upstream IΔn at least three times the downstream value, for example 300 mA S upstream of 30 mA.
- Earth leakage relays allow adjustable sensitivity and delay for selectivity between larger feeders.
- S type devices are not used for 30 mA additional protection, because the delay defeats the purpose.
Nuisance Tripping: Causes and Fixes
An RCD that trips without an obvious fault is usually responding to real leakage that adds up from many loads, or to transients:
- Standing leakage from EMC filters in computers, drives, LED drivers and power supplies. A common design guideline is to keep the total standing leakage on one device below about 30% of IΔn, so split the loads across more devices or RCBOs.
- Long cables, which have capacitance to earth and leak current, especially with VFDs.
- Surges from lightning or switching; immune or super-immune versions (often marked SI or Hpi) resist this.
- Neutral-to-earth faults, or a neutral shared between two RCD-protected circuits.
- Moisture in outdoor fittings, junction boxes and heating elements.
- Wrong type: a Type A device next to a three-phase VFD can be blinded or trip erratically; use Type B where the drive manufacturer requires it.
Never bypass a tripping residual current device. Find the fault with an insulation resistance test and a leakage clamp meter, circuit by circuit.
Testing and Maintenance
- Press the test button at the interval stated by the manufacturer or local rules, often every three or six months. The button checks the mechanism, not the earth connection or the trip time.
- Use an RCD tester to measure the trip time at IΔn and 5 × IΔn during periodic inspection, and record the results.
- Check that the device type (AC, A, F, B) still suits the loads after equipment changes, such as new drives or chargers.
- Inspect the terminals for heat damage and tighten to the specified torque during shutdown.
Residual Current Devices From Our Catalog
Examples of RCD types in our catalog. Each link goes to the product page.
Browse more in our circuit breakers category. To get a quotation, send the number of poles, rated current, sensitivity, type (AC, A, F or B), breaking capacity for RCBOs, and the part number of any existing device through our quote request form or to [email protected].
Sourcing Residual Current Devices in Oman Through Seven Star LLC
Seven Star LLC is an independent supplier in Oman of low-voltage switchgear and protection devices for commercial buildings, industry, oil and gas and utilities. We quote RCCBs, RCBOs, add-on blocks, earth leakage relays and residual current monitors from manufacturers such as Schneider Electric, ABB, Hager, Eaton, CHINT, Lovato and Bender, and can match an installed device by part number. Specifications, approvals and lead time are confirmed against the manufacturer data at quotation.
Frequently asked questions
What is the difference between an RCCB and an RCBO?
An RCCB (IEC 61008) detects earth leakage only and must be used with a circuit breaker for overload and short-circuit protection. An RCBO (IEC 61009) combines earth leakage, overload and short-circuit protection in one device, so each final circuit can have its own protection.
Which residual current device type do I need for a VFD?
Single-phase drives usually need at least Type F. Three-phase drives can produce smooth DC leakage, so Type B is normally required. Always follow the drive manufacturer recommendation.
Is a 30 mA or 300 mA RCD better?
They do different jobs. A 30 mA device gives additional protection against electric shock on final circuits. A 300 mA device protects against fire caused by earth faults and is often used at the incomer, usually as an S type for selectivity.
Why does my RCD trip for no reason?
Common causes are accumulated standing leakage from electronic loads, long cables, surges, moisture, neutral-to-earth faults and the wrong device type. Split the loads, use immune versions and test each circuit for insulation and leakage.
How often should a residual current device be tested?
Press the test button at the interval stated by the manufacturer or local rules, often every three or six months, and measure the trip time with an RCD tester during periodic inspection.
Who supplies RCCBs and RCBOs in Oman?
Seven Star LLC is an independent supplier in Oman that quotes RCCBs, RCBOs, earth leakage relays and residual current monitors from Schneider Electric, ABB, Hager, Eaton, CHINT, Lovato and Bender. Send your requirements through the quote request form or to [email protected].