Raychem HWAT-R2 Hot Water Temperature Maintenance Heating Cable

Description

HWAT-R2 is the Raychem self-regulating heating cable for the 208-277 V version of the hot water temperature maintenance system. Installed under the pipe insulation of hot water supply lines, it replaces heat loss where it occurs and keeps water at 105 to 140 F (40 to 60 C) without a recirculation loop.

Keeping hot water at temperature without recirculation pipework

The datasheet describes the cable as adjusting its power output to compensate for variations in water and ambient temperature. A single-pipe HWAT system therefore removes the pumps, return piping and balancing valves of a conventional recirculation design, and the maker lists lower installed and operating cost as the result. Retrofits and multiple pressure zones are described as simple to design.

The cable has a modified polyolefin inner and outer jacket, a tinned-copper braid, a polymer-coated aluminium wrap and a self-regulating core on 16 AWG nickel-plated copper bus wires. HWAT-R2 has a red jacket and is the version for 208-277 V; the 120 V version is HWAT-P1 with a plum jacket.

Features stated in the datasheet

  • Maintain temperature range 105 F (40 C) to 140 F (60 C) when designed with the HWAT System Product Selection and Design Guide.
  • Designed and approved for use with the Raychem HWAT-ECO-GF electronic controller; the ACS-30 controller supports HWAT-R2 for large systems.
  • Cut to length, spliced, tee-branched and terminated on site.
  • Listed c-UL-us when used with the appropriate agency-approved Raychem components and accessories.

Technical specification

Specification of HWAT-R2

Parameter Specification
Supply voltage 208-277 V (HWAT-P1 is 120 V)
Maintain temperature range 105 F (40 C) to 140 F (60 C)
Jacket and colour Modified polyolefin, red
Braid / bus wires Tinned copper braid; 16 AWG nickel-plated copper bus wires
Dimensions Width 0.72 in (18 mm), thickness 0.38 in (10 mm)
Weight 230 lb per 1000 ft (0.35 kg/m)
Minimum bend radius 0.5 in (12 mm)
Ground-fault protection 30 mA ground-fault equipment protection on each branch circuit
Maximum circuit length, 15 A breaker 250 ft (75 m)
Maximum circuit length, 20 A breaker 330 ft (110 m)
Maximum circuit length, 30 A breaker 500 ft (150 m)
Approval as printed c-UL-us Listed with appropriate agency-approved Raychem components and accessories

System parts that go with the cable

An HWAT system consists of the cable, a power connection kit, RayClic tees and splices at pipe branches, an end seal, and a controller. The installation manual names the RayClic, FTC-HST-PLUS or HWT-P connection kits and the HWAT-ECO-GF or ACS-30 controllers. The manual notes that a pipe temperature sensor must be used on the least-used pipe with HWAT-P1 cable.

Select the cable length per branch from the circuit-length table; the 208-277 V group allows longer runs than the 120 V cable, which the datasheet limits to 395 ft (120 m) on 30 A.

Installation and commissioning notes

Per manual H57548 the cable is attached to the pipe with glass tape under thermal insulation, and the insulation should follow immediately after tracing and testing so the cable is not damaged during construction. Fibreglass insulation must be a specific thickness per pipe size (Table 2 in the manual). Do not use metal straps or vinyl tape.

Read the scald warning: water above 130 F (55 C) is a significant risk of injury or death and requires scald protection. Extended 10 year warranty is available if the online warranty form is completed within 30 days of installation; it covers the cable and connection kits but not the controllers.

Where hot water maintenance cable is used

General engineering note: hotels, hospitals, accommodation camps and office towers in the Gulf have long hot water riser and branch pipework where recirculation systems waste energy. HWAT-R2 suits such building services, and not process piping, because the maintain range ends at 140 F (60 C).

In commercial buildings the manual flags trade coordination: heating cable must be installed, tested and insulated before walls are closed, because repairs afterwards may require opening them.

Information to send with an RFQ for the Raychem HWAT-R2 Hot Water Temperature Maintenance Heating Cable

Heat-tracing cable is quoted per metre or per reel, but the cable alone rarely completes a circuit. To get an accurate offer for the Raychem HWAT-R2 Hot Water Temperature Maintenance Heating Cable, list the pipe sizes and lengths to be traced, the maintain temperature, the lowest expected ambient temperature and the highest exposure temperature during steam-out or process upsets. State the supply voltage, the breaker rating you plan to use and whether the area is classified, with the gas group and temperature class required.

  • Total cable length, with an allowance for valves, flanges, pumps and supports.
  • Connection kits: power connection, splice, tee and end seal, plus attachment tape and labels.
  • Thermal insulation type and thickness, because heat loss drives the watts per metre needed.
  • Control method: ambient sensing, line sensing or an electronic controller with monitoring.

With this data the circuit can be checked against the maximum circuit lengths in the manufacturer’s design tables before the order is placed, which avoids nuisance breaker trips during cold start-up.

Related Raychem items

The matching controllers are HWAT-ECO-GF, which provides programmable temperature control, a heat-up cycle, a BMS interface and nine predefined programs, and ACS-30 for large multi-circuit systems. Process-temperature cables such as BTV are separate products.

Frequently asked questions

What temperature range does HWAT-R2 maintain?

105 F (40 C) to 140 F (60 C) when the system is designed per the HWAT guide.

What is the difference between HWAT-R2 and HWAT-P1?

HWAT-R2 is for 208-277 V and has a red jacket; HWAT-P1 is for 120 V, plum jacket, with 105-130 F maintain range.

How long can one circuit be?

At 208-277 V: 250 ft on 15 A, 330 ft on 20 A and 500 ft on 30 A breakers, per the datasheet.

Is scald protection needed?

Yes, the datasheet warns that water above 130 F (55 C) requires scald protection measures.

Does Seven Star LLC act as a Raychem distributor?

No. Seven Star LLC is not a Raychem distributor; it is an independent Muscat-based supplier that quotes Raychem products on request.

Documents and quotation

The official Raychem datasheet and user manual for HWAT-R2 are hosted on this page for download. Seven Star LLC is an independent supplier in Muscat; send your quantity and delivery location through the quotation form and we will quote this item. Please confirm the exact order code, supply voltage and output options against the documents before ordering. More related products: product category.

Datasheets & Documents
  • PDF Datasheet Raychem HWAT heating cable datasheet RAYCHEM-DS-H57512-HWAT-EN-2504 (EN, PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Raychem is the electric heat-tracing brand of Chemelex, a company that describes itself as a global leader in electric thermal and sensing solutions with over 50 years of experience. Raychem systems cover industrial, commercial and residential applications, from frost protection of water pipes to maintaining high process temperatures.

Seven Star LLC is an independent supplier in Muscat. We list Raychem heating cables and controllers with the official datasheet attached to each product page, for oil and gas, petrochemical and building projects in Oman and the GCC.

Raychem product series

Self-regulating heating cables include the 5BTV2-CR for freeze protection, the 15QTVR2-CT for maintain temperatures up to 110 °C, the 10XTVR2-CT high power retention cable for 150 °C and the 15HTV2-CT for 205 °C. The 10VPL2-CT is a power-limiting cable for higher temperatures and longer circuits, HWAT-R2 maintains hot water temperature in building pipework and STS skin-effect tracing wire heats long pipelines from a single supply point.

Controllers include the Elexant 4010i heat-trace controller, the Elexant 3500i electronic thermostat and the RAYSTAT V5 controller for freeze protection.

Where Raychem heat tracing is used

Viscosity and temperature maintenance on fuel oil, sulphur, wax and bitumen lines, freeze protection of instrument lines and water pipes, tank heating, hot water systems in buildings and long transfer pipelines.

Ordering Raychem products: what we need

Send the cable catalogue number, or the pipe size and length, insulation type and thickness, maintain and exposure temperatures, minimum ambient, supply voltage and hazardous-area classification, so the cable and circuit lengths can be checked against the Raychem design data.

Frequently Asked Questions

What temperature range does HWAT-R2 maintain?
105 F (40 C) to 140 F (60 C) when the system is designed per the HWAT guide.
What is the difference between HWAT-R2 and HWAT-P1?
HWAT-R2 is for 208-277 V and has a red jacket; HWAT-P1 is for 120 V, plum jacket, with 105-130 F maintain range.
How long can one circuit be?
At 208-277 V: 250 ft on 15 A, 330 ft on 20 A and 500 ft on 30 A breakers, per the datasheet.
Is scald protection needed?
Yes, the datasheet warns that water above 130 F (55 C) requires scald protection measures.
Does Seven Star LLC act as a Raychem distributor?
No. Seven Star LLC is not a Raychem distributor; it is an independent Muscat-based supplier that quotes Raychem products on request.