Brand:

Datakom DKG-605 Alarm Annunciator Unit

Description

An eight-channel annunciator for generating sets and diesel engines

The DKG-605 is a compact 8-channel programmable alarm annunciator used in generating sets and diesel engines. It can be used as an alarm extension module or as a stand-alone alarm annunciator and shutdown device, and several units can be connected in parallel to build a larger alarm system. Each input can be programmed as normally open or normally closed, switching positive or negative supply voltage, with delays of 0.5 to 4 seconds in four steps, latching or non-latching behaviour, and as a shutdown input, warning input, visual warning (no relay) or no connection. Easy alarm identification is provided by an insertable text label for each channel. It is part of our diesel generator spare parts range.

Technical specifications

Parameter Specification
Model DKG-605 alarm annunciator unit
Control 8-bit microcontroller
Input channels 8 programmable
Outputs 2 relay outputs (shutdown, warning) and 8 semiconductor outputs
Generator voltage input 50 to 277 VAC (Ph-N)
Generator frequency 20 to 100 Hz
DC supply range 9 to 18 V-DC (12 V models); 18 to 33 V-DC (24 V models)
Current consumption 60 mA-DC typical (no alarm); 150 mA-DC max. (outputs open)
Total DC current output rating 10 A-DC
Max. current per relay output 10 A (positive output, 10 A at 28 V-DC)
Max. current per alarm output 250 mA
Programmable parameters 44
Operating temperature -20 C to 70 C
Storage temperature -30 C to 80 C
Maximum humidity 95% non-condensing
Dimensions (W x H x D) 72 x 72 x 76 mm
Panel cut-out 68 x 68 mm minimum
Weight Approx. 200 g
Case material Flame-retardant, high-temperature ABS (UL94-V0, 110 C)
Hand terminal connector 6 pins
Conformity (as printed) Directives 73/23/EEC, 93/68/EEC, 89/336/EEC, 92/31/EEC; EN 61010 (safety), EN 50081-2 and EN 50082-2 (EMC)

How the alarms behave

In the initial state the unit watches the Safety On signal, with the Power On LED steady. The Safety On signal is taken from the AC generator voltage input or from input 8 (programmable), and the Safety On timer is programmable. When the signal arrives, alarm inputs are enabled after the timer, and the Power On LED flashes. If an alarm occurs, its LED flashes, its semiconductor output turns on and the warning and shutdown relays operate, supplying battery positive. A warning-type input does not operate the shutdown relay, and a visual warning also does not operate the warning relay.

The first press of the RESET button releases the relays and turns the flashing LEDs steady; a second press resets the LEDs and alarm outputs. Latching inputs stay on until reset and non-latching inputs clear when the fault signal is removed. A TEST button activates all alarm LEDs, alarm outputs and relays for a display test. Low and high frequency protections are provided on the AC generator input. The semiconductor outputs are open-collector types that sink current to negative supply, similar to an electronic relay contact, so they can drive distant visual warning lights.

Selection and installation notes

Select the 12 V or 24 V model to match the plant battery, because the unit has different models for 12 and 24 volt systems. Programming is done through the separate DKG-605-P hand terminal unit (six-pin connector); programs are held in non-volatile memory and survive power failures. The unit has a plug-in connection system for easy replacement, survives cranking dropouts and has standard 72 x 72 mm panel dimensions. Use input 8 as the Safety On signal in engine control applications where no generator voltage is available. Note that the datasheet gives older EU directive references; confirm current compliance requirements with your panel builder.

The user manual adds practical installation rules: the unit is not fused, so external 6 A fuses are required on the generator phase G and on battery positive BAT(+); wire with at least 0.75 mm2 cable; always remove the plug connectors when inserting wires with a screwdriver; observe battery polarity because reverse polarity will stop the unit from operating; and the building supply must have short-circuit back-up protection. To enter program mode connect the DKG-605-P hand terminal and press its button: the display shows the program number while the button is held and the value when released, values are changed with RESET (+) and TEST (-), and program mode is cancelled if no key is pressed for 15 seconds. Each input has five parameters (contact type, polarity, detection delay, priority level and latching) that are repeated for inputs 1 to 8, plus global values for the Safety On source and timer and for the frequency delay and limits.

Selection and installation notes

An annunciator is selected from the number of alarm channels, the input type and the outputs it must drive. Set the input polarity, the alarm text and the horn logic at commissioning, test every channel from the field device and check that the acknowledge and test buttons behave as the site procedure requires.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Related Datakom products: Datakom DKG-309 Automatic Mains Failure Unit, Datakom AVR-8 Alternator Voltage Regulator, Datakom DKG-171 Automatic Transfer Switch Controller, Datakom D-500 MK3 Advanced Genset Controller, Datakom SBC-245 24V 5A Smart Battery Charger and Datakom D-300 MK3 Genset Controller.

Documents and quotation

The datasheet and user manual are provided as published by Datakom. Contact us with the supply voltage (12 V or 24 V) and quantity for a quotation, and ask about the DKG-605-P hand terminal if you need to program the unit.

Datasheets & Documents
  • PDF Datasheet DKG-605 datasheet (Datakom) Download
  • PDF User manual DKG-605 user manual (Datakom) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Datakom is a Turkish manufacturer of generator controllers and power measurement electronics, headquartered in Ümraniye, Istanbul. It was founded in 1988 as a three-person electronic design house, began manufacturing in 1990 and launched its own genset control products in 1994. Datakom now offers more than 400 products, including the Rainbow SCADA remote monitoring software.

Seven Star LLC is an independent supplier in Muscat. We list Datakom products with the manufacturer datasheets and manuals, for generator packagers and maintenance teams in Oman and the GCC.

Datakom company profile

Founded 1988, Istanbul, Turkey
Headquarters Ümraniye, Istanbul
Own products Genset controllers, from 1994
Range More than 400 products
Product families D-300 and D-500 MK3 genset controllers, DKG automatic mains failure and transfer switch controllers, AVR alternator voltage regulators, DKM network analysers, DFC reactive power controllers, Rainbow SCADA software

Milestones

  • 1988: Datakom is founded as a design house.
  • 1990: Manufacturing begins.
  • 1994: Datakom launches its own genset controllers.

Datakom product series

Genset controllers on this site include the D-300 MK3 and the advanced D-500 MK3, which support J1939 CANBUS engines, as well as the DKG-309 automatic mains failure unit and the DKG-171 transfer switch controller. The DKG-605 is an alarm annunciator.

Companion products include the AVR-8 alternator voltage regulator, the SBC-245 24 V 5 A smart battery charger, the DKM-409 network analyser with scopemeter function, the DPR-350 network analyser and protection relay and the DFC-0124 reactive power controller for capacitor banks.

Where Datakom products are used

Stand-by and prime power gensets for oil and gas camps, utilities, telecom sites, hospitals and commercial buildings, changeover panels, capacitor banks and energy monitoring in low-voltage switchboards.

Datakom products we list

Family Examples
Diesel Generator Spare Parts AVR-8 Alternator Voltage Regulator, D-300 MK3 Genset Controller, D-500 MK3 Advanced Genset Controller, DKG-171 Automatic Transfer Switch Contro…, DKG-309 Automatic Mains Failure Unit
Controllers & Data Acquisition DFC-0124 Reactive Power Controller, DKM-409 Network Analyser with Scopemeter

Ordering Datakom products: what we need

Send the model and variant, the engine make and ECU or magnetic pickup, the alternator, the number of phases and voltage, and the communication options needed. For replacements, send a photo of the label on the installed unit.

Facts checked against Datakom's own company profile (datakom.com.tr), October 2026.

FAQ

Questions about the Datakom DKG-605 Alarm Annunciator Unit

Answers from our engineering team on installation, compatibility and integration.

01How many alarm channels does the DKG-605 have?
Eight programmable input channels, each with its own semiconductor output.
02How is it programmed?
Through the DKG-605-P hand terminal unit via the 6-pin connector; programs are stored in non-volatile memory.
03Which supply voltages are available?
There are different models for 12 V (9-18 V-DC) and 24 V (18-33 V-DC) plants.
04Can several units be combined?
Yes, multiple DKG-605 units may be connected in parallel to form a larger alarm system.
05What are the relay outputs?
Two relays (shutdown and warning) supplying battery positive, rated 10 A at 28 V-DC.