Role of the SYA8K16I in a power protection layout

The APC SYA8K16I gives the protected load a UPS from the Symmetra LX range sized at 8000 VA (5600 W) with 220 V AC 1 phase / 230 V AC 1 phase / 240 V AC 1 phase output.

It is fed from 220 V AC 1 phase / 400 V AC 3 phases / 230 V AC 1 phase / 240 V AC 1 phase / 380 V AC 3 phases / 415 V AC 3 phases and supplies 220 V AC 1 phase / 230 V AC 1 phase / 240 V AC 1 phase as a sine wave. The listed battery type is lead-acid battery, with a typical recharge time of 3 h. The recorded mounting mode is not rack-mountable.

The APC SYA8K16I is listed with on-line topology. In an online double-conversion design the load is fed from the inverter at all times, so connected equipment is isolated from mains disturbances and there is no transfer time when the mains supply fails. This approach is commonly chosen for servers, network cores and other sensitive loads.

The output waveform is listed as sine wave. A sine-wave output is the safer choice for equipment with active power factor correction and for sensitive electronics. The listed ratings of 8000 VA and 5600 W correspond to a power factor of 0.7. Size the load against the watt rating as well as the VA rating, and keep margin for future equipment.

Technical specifications

Parameter Specification
Part number SYA8K16I
Main input voltage 220 V AC 1 phase / 400 V AC 3 phases / 230 V AC 1 phase / 240 V AC 1 phase / 380 V AC 3 phases / 415 V AC 3 phases
Other input voltage 220 V / 240 V / 380 V / 415 V
Input harmonic distortion Less than 7 % for full load
Cos phi 0.98
Input connection 1 hard wire 3-wire (1P + N + E) / 1 hard wire 5-wire (3P + N + E)
Input frequency 45…65 Hz auto-sensing
Output voltage 220 V AC 1 phase / 230 V AC 1 phase / 240 V AC 1 phase
Other output voltage 220 V / 240 V
Rated power in W 5600 W
Rated power in VA 8000 VA
Output connection Hard wire 3-wire (H N + E) for 1 zone(s)
Bypass type Internal bypass (automatic and manual)
Crest factor Up to 5 : 1
Harmonic distortion Less than 5 % at full load
Maximum configurable power in VA 16000 VA
Maximum configurable power in W 11200 W
Maximum output current 36 A
UPS topology On-Line
Waveform type Sine wave
Output frequency 47…63 Hz sync to mains / 60 Hz +/- 0.1 % for 60 Hz nominal unsynchronised / 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
Battery type Lead-acid battery
Additional information Configurable for 220 : 230 or 240 nominal output voltage
Extendable runtime 1
Included battery module 2
Empty battery slot 2
Typical recharge time 3 h
Battery life 3…5 year(s)
Battery charging power 574 W rated
Battery type Lead-acid internal included
Control panel Multifunction LCD status and control console
Emergency power off Yes
Free slot 1
Preinstalled device Network management card 2 with environmental monitoring
Alarm Audible and visible alarms : prioritized by severity
UPS connectivity Serial port / Available expansion slot / Pre-installed network management card 3
Color Black / Silver
Height 937 mm
Width 483 mm
Depth 726 mm
Product weight 219.55 kg
Mounting location Front
Mounting preference No preference
Mounting mode Not rack-mountable
Two post mountable 0
USB compatible No
Mounting mode Tower
Provided equipment CD with software / Documentation CD / Installation guide / User manual / Web/SNMP management card
Number of power module filled slots 2
Number of power module free slots 3
Additional specification 4kVA power increments
Redundant Yes
Range of product Symmetra LX
Product or component type Uninterruptible power supply (UPS)
Performance multiplier 1
Value multiplier 1
Size UPS version Internetworking / Server / Telecom
Curve equation Efficiency
Curve fixed loss 0.0464
Curve load maximum 100 %
Curve load minimum 5 %
Curve proportional loss 0.0238
Curve square loss 0.02
Curve test cond ID Curve fit to measured efficiency data. All measurements taken in normal operating mode, at typical environmental conditions, with nominal electrical input and balanced resistive load (PF = 1.0) output.
Curve x-axis maximum 100 %
Curve x-axis minimum 0 %
Curve x-axis title Load
Curve x-axis unit Percentage
Curve y-axis maximum 100 %
Curve y-axis minimum 50 %
Curve y-axis title Efficiency
Curve y-axis unit Percentage
Graph display 1
Operating temperature note No
UPS size L
Product certification C-Tick / CE / GOST / VDE
Standard EN 50091-1 / EN 50091-2 / EN 55022 class A / EN 55024 / EN 60950 / IEC 60950
Ambient air temperature for operation 0…40 °C
Ambient air temperature for storage -15…45 °C
Storage altitude 0…4572 m
Relative humidity 0…95 %
Storage relative humidity 0…95 %
Acoustic level 62 dBA
Heat dissipation 3707 Btu/h
Operating altitude 0…10000 ft
Warranty (in months) 24

Power, battery and connection data

Output connections: Hard wire 3-wire (H N + E) for 1 zone(s). Input connection: 1 hard wire 3-wire (1P + N + E) / 1 hard wire 5-wire (3P + N + E). Input frequency: 45…65 Hz auto-sensing. Communication and expansion: Serial port / Available expansion slot / Pre-installed network management card 3.

Extendable runtime is listed as 1. Battery life is listed as 3…5 year(s).

Load sizing should be checked against both the VA and the watt rating, and runtime depends on the connected load, battery condition and ambient temperature. Confirm these points against the product documents before ordering.

Site requirements and approvals

Dimensions are 937 mm x 483 mm x 726 mm (H x W x D), and the unit weighs 219.55 kg. Colour: black / silver.

Listed operating limits: operating temperature 0…40 °C; relative humidity 0…95 %; operating altitude 0…10000 ft; acoustic level 62 dBA.

Certifications: C-Tick / CE / GOST / VDE. Standards: EN 50091-1 / EN 50091-2 / EN 55022 class A / EN 55024 / EN 60950 / IEC 60950. Warranty recorded by APC (months): 24.

Battery data listed for this model: type lead-acid battery. The typical recharge time is 3 h. Sealed lead-acid batteries need no topping up in normal use but wear with age and heat, so replacement should be planned in advance and the battery state checked during routine maintenance. Used batteries must be recycled according to local regulations. Extendable runtime is listed as 1. Actual runtime always depends on the connected load, battery age and ambient temperature.

Further electrical values recorded for the APC SYA8K16I include: bypass type: Internal bypass (automatic and manual); crest factor: Up to 5 : 1; maximum output current: 36 A. Use these figures when sizing upstream protection and cabling, and confirm them against the installation documents for the exact variant.

Communication and management details listed: UPS connectivity: Serial port / Available expansion slot / Pre-installed network management card 3; graph display: 1. Network cards, software and monitoring options should be matched to the facility monitoring system before ordering.

The mounting mode is listed as not rack-mountable. The unit measures 937 mm x 483 mm x 726 mm (H x W x D) and weighs 219.55 kg, so check the available space and the floor or rack loading before delivery. Listed environmental limits: operating temperature 0…40 °C; relative humidity 0…95 %; altitude 0…10000 ft. Equipment rooms in the Gulf region often run warm, so leave ventilation clearance and keep the unit away from direct heat sources.

Certifications listed: C-Tick / CE / GOST / VDE. The warranty period recorded in the product data is 24 months. If a project requires certificates or test reports, include that request with the quotation request.

How the SYA8K16I is used in APC Symmetra LX systems

Symmetra LX is a modular single-phase UPS built from hot-swappable power modules and battery modules in a rack or tower frame. With N+1 redundancy a failed module can be replaced while the load stays protected, and capacity or runtime can be raised by adding modules instead of replacing the whole UPS.

The APC SYA8K16I is a complete UPS rather than a spare part, so the selection starts from the load. Add up the real power of the connected equipment in watts, compare it with the watt rating of the UPS as well as the VA rating, and keep about 20 to 25 percent margin for growth and for inrush current when equipment restarts. Then define the runtime the site needs: a few minutes is enough to ride through short interruptions or to let a standby generator start and stabilise, while longer outages call for external battery capacity where the model supports it.

In the product data for the APC SYA8K16I, it is rated 8000 VA and 5600 W; it uses on-line topology; its battery technology is listed as lead-acid battery. These values are the starting point for matching it to the rest of the installation.

Site conditions in Oman and the GCC for the SYA8K16I

The output can be set to 240 V, which matches the nominal 240 V single-phase supply in Oman. The listed operating temperature tops out at 40 °C. Summer shade temperatures in Muscat, Sohar and the interior regularly pass 45 °C, so the equipment belongs in an air-conditioned room or cabinet rather than an open plant area. Battery temperature has the biggest effect on service life: as a rule of thumb, the life of a valve-regulated lead-acid battery roughly halves for every 10 °C above 25 °C, so a room held at 20 to 25 °C pays back in fewer battery replacements. The heat dissipation of 3707 Btu/h has to be included in the cooling budget of the room.

Fine dust inland and humid, salty air on the coast are hard on electronics, so a sealed room, clean filters and periodic inspection of fans and terminals are part of a reliable installation. Many sites in the region run the UPS downstream of a standby diesel generator. The UPS carries the load during the start-up of the generator and smooths its voltage and frequency, so the generator should be sized with margin for the UPS input and battery charging current. At 219.55 kg the unit needs two people or lifting equipment for installation, and rails rather than a shelf if it goes into a rack.

What to send with an enquiry for the SYA8K16I

To confirm the right item and quote quickly, send the following with the part number:

  • The load to be protected in watts and VA, with the share of critical equipment
  • The runtime needed on battery, and whether a standby generator is installed
  • Input and output connection types required on site (1 hard wire 3-wire (1P + N + E) / 1 hard wire 5-wire (3P + N + E) / Hard wire 3-wire (H N + E) for 1 zone(s))
  • Rack or tower installation, and rack depth if rack-mounted
  • Whether a network management card or monitoring is required
  • The delivery location in Oman (for example Muscat, Sohar, Duqm or Salalah) or elsewhere in the GCC, and the required date

More APC power protection products are listed on the APC brand page, and the wider Schneider Electric range is available from the same supply channel.

Documents and quotation

The user guide for the SYA8K16I is hosted on this page under Documents so the wiring, installation and operating details can be reviewed before ordering.

The single-unit shipping package is listed as 118.1 cm (height) x 99.7 cm (width) x 59.9 cm (length) with a packed weight of 236.82 kg. Use these values when planning freight, lifting and receiving space.

To order, submit the part number SYA8K16I, the quantity and the delivery location. Related items are grouped under UPS and Batteries. Seven Star LLC is an independent supplier based in Muscat and answers with availability and a quotation.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

APC is Schneider Electric's brand for uninterruptible power supplies, power distribution units, cooling and racks for IT and control systems. American Power Conversion was founded in 1981 by three engineers from MIT's Lincoln Laboratory and grew into one of the largest UPS makers in the world. Schneider Electric completed its acquisition of APC on 14 February 2007, combined it with MGE UPS Systems, and since 2011 APC has been a product brand of Schneider Electric.
Seven Star LLC lists APC uninterruptible power supplies from desktop Back-UPS units to modular Symmetra systems, together with battery packs and network cards, and sources them for sites in Oman.

APC company profile
Founded1981, USA, as American Power ConversionFoundersThree engineers from MIT Lincoln LaboratoryOwnershipSchneider Electric since 14 February 2007; an APC by Schneider Electric product brand since 2011Product familiesBack-UPS, Easy UPS, Smart-UPS line-interactive, Smart-UPS On-Line SRT and SRV, Galaxy three-phase UPS, rack PDUs, NetShelter racks, network management cards and EcoStruxure IT software

Milestones
1981: American Power Conversion is founded by three MIT Lincoln Laboratory engineers.2006: Schneider Electric announces the acquisition of APC on 30 October.2007: The acquisition is completed on 14 February; APC is combined with MGE UPS Systems.2011: APC becomes a product brand within Schneider Electric.

APC UPS families on this page

APC names its UPS lines by topology and size:

Back-UPS and Back-UPS Pro: line-interactive units for workstations and small loads, such as BX1600MI-MS and BR1600MISmart-UPS: line-interactive models with sine wave output, including SMT750I, SMC1000IC and the Smart-UPS X SMX3000HV with its SMX120BP external battery packSmart-UPS SRT and Smart-UPS RT: online double-conversion units, for example SRT2200XLI, SRT3000XLI, SRT5KRMXLI and SURT8000XLIEasy UPS Online: SRV2KILSymmetra LX and Symmetra PX: modular, scalable systems for larger loads

The AP9641 Network Management Card 3 adds remote monitoring to UPS models with a SmartSlot.

Where APC UPS systems are used

In industrial plants across the GCC, APC UPS units back up DCS and PLC cabinets, operator stations, SCADA servers, telecom racks, fire and gas panels and analyzer shelters. Online double-conversion models are normally chosen for control systems because the load is always fed through the inverter. Line-interactive units suit office IT and less critical loads.

APC products we list
FamilyExamplesUPS and BatteriesAP9641 Network Management Card 3, BR1600MI Back-UPS Pro 1600VA/960W, BX1600MI-MS Back-UPS 1600VA Tower UPS, SMC1000IC Line-Interactive UPS 1000VA 600W, SMC1500I Smart-UPS C 1500VA/900W, SMT750I Smart-UPS 750VA/500W Line-Interactive, SMX120BP Smart-UPS X 120V External Battery, SMX1500RMI2U Smart-UPS X 1500VA Rack/Tower and 9 more

Ordering APC UPS units and parts: what we need

Send the full SKU, for example SRT3000XLI, and not only the VA rating. The letters carry meaning: an I in the suffix marks a 230 V international model, XL an extended-run version that accepts external battery packs, and RM a rack-mount form. For a new requirement, give load in watts, input and output voltage, required runtime, tower or rack format, and the plug or hardwire arrangement. For batteries, send the UPS SKU and serial number so the correct replacement battery cartridge can be found in APC documentation.

Replacement batteries, battery packs and spares
Most APC service work is battery work. APC Replacement Battery Cartridges, sold under RBC and APCRBC numbers, are sets of sealed valve-regulated lead-acid blocks that arrive pre-wired with the connectors for the UPS models they are listed for, so a weak battery can be changed as one unit and, on hot-swap models, without switching the load off. Some newer cartridges carry an -LI suffix for lithium-ion versions. External battery packs extend runtime on XL and SRT models, and are chained to the UPS through the battery connector on the rear panel. To find the right cartridge, send the UPS SKU and serial number; the same UPS can use different cartridges across hardware revisions.
Modular and three-phase APC systems
Symmetra LX and Symmetra RM: single-phase modular UPS frames with hot-swappable power modules, battery modules and intelligence modules, so a failed module can be exchanged while the load stays on protected power.Symmetra PX: three-phase modular UPS for data rooms, built from power modules with N+1 redundancy and battery modules for runtime.Smart-UPS VT: three-phase double-conversion UPS for small data rooms and technical buildings.Silcon: large three-phase UPS based on delta conversion, still running in many plants and data centres; spare part kits are listed in levels (SPL1 to SPL4) so sites can hold the parts that match their service plan.Easy UPS On-Line (SRV): cost-focused double-conversion units, many with external battery pack support.
APC UPS in Oman and GCC conditions
Oman supplies 240 V single-phase and 415 V three-phase at 50 Hz, so international models with an I suffix (230 V nominal, adjustable to 240 V on most Smart-UPS units) are the usual choice. Heat is the main enemy: most APC UPS units are rated for operation up to 40 °C, while summer shade temperatures in Muscat and the interior pass 45 °C, and a lead-acid battery loses roughly half its service life for every 10 °C above 25 °C. Install UPS and batteries in a cooled room, keep filters clean in dusty inland sites, and size the standby generator with margin for UPS input and battery charging current.
All APC UPS systems, batteries and accessories on this site are grouped under UPS and Batteries, and the wider Schneider Electric range can be quoted together with them.

Facts checked against APC by Schneider Electric's published history, October 2026.

Browse APC products by category: UPS and Batteries.
Need a replacement battery for an APC UPS you already run? Use our APC UPS replacement battery finder to match the model to its official RBC cartridge.

FAQ

Questions about the APC SYA8K16I Symmetra LX 8kVA Scalable to 16kVA N+1

Answers from our engineering team on installation, compatibility and integration.

01What is the rated power of the APC SYA8K16I?
The APC SYA8K16I is rated at 8000 VA / 5600 W and uses on-line topology.
02What input and output voltage does the APC SYA8K16I use?
The input is 220 V AC 1 phase / 400 V AC 3 phases / 230 V AC 1 phase / 240 V AC 1 phase / 380 V AC 3 phases / 415 V AC 3 phases at 45...65 Hz auto-sensing and the output is 220 V AC 1 phase / 230 V AC 1 phase / 240 V AC 1 phase.
03What are the dimensions and weight of the APC SYA8K16I?
The listed dimensions are 937 mm x 483 mm x 726 mm (H x W x D) and the weight is 219.55 kg.
04What operating conditions apply to the APC SYA8K16I?
Listed limits: operating temperature 0…40 °C; relative humidity 0…95 %.
05How can I request a quotation for the APC SYA8K16I?
Send the part number SYA8K16I with quantity and delivery location through the RFQ form. Seven Star LLC is an independent supplier in Muscat and replies with availability and a quotation.