TDK B84144A0050R000 50 A 4-Line EMC Filter with Neutral

Description

A four-line filter for three-phase supplies that carry a neutral

The TDK B84144A0050R000 is a 4-line power line EMC filter: three phases plus the neutral conductor are filtered, which distinguishes it from the three-line filters used on drives without a neutral connection. It is rated 50 A at 40 C on a 250/440 V AC supply, weighs about 4.0 kg, and has finger-safe terminals for a 10 mm2 cable, so it can be wired directly in a small machine or UPS cabinet.

TDK names UPS, wind farms and general applications for power electronics as typical uses, along with machine tools and textile and packaging machines. The threaded bushes on the end faces allow an RF-tight installation, which helps when the filter must be bonded to a cabinet wall.

Specification of the 50 A four-line filter

Parameter Specification
Ordering code B84144A0050R000
Series B84144A*R000, 4-line filters for converters and power electronics; power line filters for 3-phase systems with neutral conductor
Rated voltage VR 250/440 V AC, 50/60 Hz
Rated current IR 50 A, referred to 40 C rated temperature
Terminal cross section 10 mm2, finger-safe terminals
Leakage ILK 4.1 mA, VR, 50 Hz
Rtyp 1.3 mOhm, typical
Weight Approx. 4.0 kg
Voltage test (16 A to 50 A) 1770 V DC line/line and 2700 V DC lines/case, each applied 2 s
Thermal overload 1.5 x IR: 3 minutes per hour; 2.5 x IR: 30 seconds per hour
Climate rating 25/100/21 (IEC 60068-1)
Degree of protection IP20 (IEC 60529)
Construction Metal case with threaded bushes at the end faces for RF-tight installation
Approvals and standards UL 1283; design complies with IEC 60939; approval column marked for this code
Cost-optimised alternative Series B84144A*R120 per the datasheet

Where the 50 A rating sits in the series

The ladder runs 16, 25, 36, 50, 80, 120, 150 and 180 A, with terminals growing from 4 mm2 to 95 mm2. The 50 A step has its own insertion loss curve (SSB1678-Y in the datasheet), separate from the 16 to 36 A group, and its own circuit drawing: the 25 to 50 A filters use a different internal diagram from the 16 A and 80 to 180 A ones. Leakage current rises with size, from 1.11 mA at 16 A to 4.1 mA at 25 to 50 A and 8.8 mA from 80 A.

Typical resistance falls from 10 mOhm at 16 A to 1.3 mOhm at 50 A and 0.25 mOhm at 180 A, while weight rises from 2.2 kg at 16 A to 4.0 kg at 50 A and 13 kg at 180 A, so the 50 A step is a mid-weight unit for cabinet planning.

  • Choose the rating from the converter or machine input current, with allowance for the 40 C temperature reference.
  • Check cable length and drive pulse frequency against EMC limits; the series is not specified for long motor cables in this datasheet, unlike the 3-line A and D series.
  • Use the 80 A or larger types when terminals above 10 mm2 are needed.

Installation and safety instructions

The datasheet restricts work to qualified persons and warns that stored charge can leave dangerous voltage at the terminals for more than five minutes. Connect the protective earth first and remove it last, and tighten PE bolts to the table torques: 1.2 Nm for M4, 2.0 Nm for M5, 3.0 Nm for M6, 6.0 Nm for M8 and 10 Nm for M10. At 4.1 mA this filter sits in the 3.5 to 10 mA leakage band, which requires a fixed connection or an industrial IEC 60309 plug with at least 2.5 mm2, as set out in the cautions. The filter must be protected against exceeding its rated current by an overcurrent device, and it can stay hot for some time after the power is switched off. Do not let the filter carry mechanical loads, and note that galvanised case edges may show edge rust, which TDK states is not a quality defect.

Use in GCC installations

A neutral-carrying filter suits 400/230 V systems feeding UPS rectifiers, single-phase loads mixed with three-phase electronics, and machine control panels in packaging and textile plants. In dusty or humid coastal plants, remember that the stated climatic category is 25/100/21 and the filter is IP20, so it belongs inside a cabinet. Related drive-panel parts are in the electrical and power category.

Selection and installation notes

An EMC filter or reactor is selected from the rated current at the actual ambient temperature, the supply voltage and the drive or load it serves. Fit it as close as possible to the drive input, keep the cable between filter and drive short, bond the housing to the panel back plate with a clean metal contact, separate input and output cables, and check the leakage current against the protective earth requirements of the installation.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Frequently asked questions

Why choose a 4-line filter rather than a 3-line one?

A 4-line filter also filters the neutral conductor, which is needed when the equipment draws neutral current in a 3-phase 4-wire supply.

What is the rated current and temperature?

50 A, referred to a rated temperature of 40 C.

What is the rated voltage?

250/440 V AC at 50/60 Hz.

Which terminals does it have?

Finger-safe terminals for 10 mm2 cable, plus a PE connection and threaded bushes at the end faces for RF-tight installation.

Who supplies this part in Oman?

Seven Star LLC is an independent supplier in Muscat and not the manufacturer. Confirm the rating and supply system before ordering.

Datasheets & Documents
  • PDF Datasheet TDK 4-line EMC filters B84144A*R000 datasheet (November 2025, 14 pages) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

TDK Electronics, formerly EPCOS, is a German maker of electronic components headquartered in Munich and owned by Japan's TDK Corporation. EPCOS AG was created in 1999 from Siemens Matsushita Components, a 1989 joint venture of Siemens and Matsushita, and TDK acquired the company fully in October 2009. The EPCOS name remains on many power capacitors, filters and inductors.

Seven Star LLC is an independent supplier in Muscat. We list selected TDK Electronics (EPCOS) items with the official data sheet attached to every product page, for panel builders and power quality projects in Oman and the GCC.

TDK Electronics (EPCOS) company profile

Origins Siemens Matsushita Components, 1989
EPCOS AG Formed 1999
Headquarters Munich, Germany
Ownership TDK Corporation, fully since October 2009
Product families PhaseCap and DeltaCap power factor correction capacitors, capacitor contactors, PFC controllers, EMC filters, output and dv/dt reactors, film capacitors, varistors and surge arresters

Milestones

  • 1989: Siemens and Matsushita form a components joint venture.
  • 1999: EPCOS AG is created.
  • 2009: TDK completes the acquisition of EPCOS.

TDK Electronics product series

Power factor correction components include the DeltaCap X Black 25 kvar 440 V capacitor, the B44066 capacitor contactor for switching capacitor steps and the FilterCap gas-filled AC capacitor for inverter filters.

Drive and EMC components include three-line EMC filters such as the 600 A B84143B0600S080 for converters, the 50 A four-line filter with neutral, the 40 A single-phase filter and the 10 A IEC inlet filter, as well as three-phase line reactors, the 180 A dv/dt output reactor that protects motor insulation and the 66 A LCL filter for active infeed converters.

Where TDK Electronics components are used

Capacitor banks and detuned filter panels, frequency converter and drive cabinets, UPS and inverter systems, and electronic equipment that must meet EMC limits.

TDK Electronics (EPCOS) products we list

Family Examples
Power Modules TDK B32305A4252B040 DeltaCap X Black 25…, TDK B32377G1426J000 FilterCap 3 x 42 uF…, TDK B84143B0600S080 600 A 3-Line EMC Fil…, TDK B84771A0010A000 10 A IEC Inlet EMC F…, TDK B86301U0180S000 180 A dv/dt Output R…
Contactors & Overload Relays TDK B44066S2410J230 Capacitor Contactor…

Ordering TDK Electronics components: what we need

Send the ordering code starting with B, such as B32305A4252B040, together with the quantity. If the code is not known, give the voltage, rated power in kvar or rated current, number of lines, mounting and the drive or system the part is used with.

Facts checked against TDK Electronics and EPCOS company histories, October 2026.

Frequently Asked Questions

Why choose a 4-line filter rather than a 3-line one?
A 4-line filter also filters the neutral conductor, which is needed when the equipment draws neutral current in a 3-phase 4-wire supply.
What is the rated current and temperature?
50 A, referred to a rated temperature of 40 C.
What is the rated voltage?
250/440 V AC at 50/60 Hz.
Which terminals does it have?
Finger-safe terminals for 10 mm2 cable, plus a PE connection and threaded bushes at the end faces for RF-tight installation.
Who supplies this part in Oman?
Seven Star LLC is an independent supplier in Muscat and not the manufacturer. Confirm the rating and supply system before ordering.