Brand: VEGA
VEGA VEGACAP 65 Capacitive Cable Level Switch up to 32 m
Description
A cable electrode switch for tall silos with a transistor output
The VEGACAP 65 hangs a partly insulated capacitive cable electrode of up to 32 m into a tall vessel to give a point level signal for bulk solids and liquids. VEGA calls the construction proven with high functional safety, the probe can be shortened on site, and the whole probe length is available for switching because there is no blocking distance. The sheet covers the transistor (NPN/PNP) version: a 10…55 V DC supply, maximum 0.5 W, a load current below 400 mA, a switching voltage below 55 V DC, a blocking current below 10 µA and a 0.7 s switching delay.
Technical specifications
| Parameter | Specification |
|---|---|
| Type | VEGACAP 65, capacitive cable electrode for point level detection |
| Sensor length | Up to 32 m (105 ft) |
| Process fitting | Thread from G1 / 1 NPT; flanges |
| Process pressure | -1…+64 bar (-100…+6400 kPa) |
| Process temperature | -50…+200 °C (-58…+392 °F) |
| Ambient, storage, transport | -40…+80 °C (-40…+176 °F) |
| Operating voltage (transistor sheet) | 10…55 V DC; max. 0.5 W |
| Load current / switching voltage | < 400 mA / < 55 V DC; blocking current < 10 µA |
| Switching delay | 0.7 s on/off |
| Wetted parts | Stainless steel; PTFE probe insulation |
| Electronics | Transistor NPN/PNP, contactless electronic switch, relay, two-wire |
| Housing | Single-chamber housing in plastic, aluminium or stainless steel, up to IP67 |
Placing a point level far from the roof
A cable electrode lets one instrument sense a limit at any depth inside a tall silo or deep tank, from a nozzle in the roof; the switching point is then adjusted on the electronics. Because the cable carries a tensile load from the weight of the product, VEGA’s mounting instructions require the roof load and the tensile load of the suspension to be checked, and the probe to be mounted at a position where filling and emptying do not subject it to strong lateral forces.
Comparison and ordering
The VEGACAP 65 is the partly insulated cable for dry solids and non-conductive liquids; the fully insulated VEGACAP 66 serves liquids and solids to 150 °C, and the VEGACAP 67 reaches +400 °C. Quote the probe length, thread or flange, supply voltage and output type, and mention cone and wall distances in the silo so a suitable arrangement can be confirmed with the manufacturer.
Since the same family offers the relay and contactless electronic switch versions, the transistor version of this sheet is the one for PLC inputs. For hazardous areas, VEGA’s documentation lists Ex approvals as available by version and ship approvals for the family, so declare any requirement in your enquiry. The product information notes that the cable should be installed away from the filling stream, and that the permissible tensile load of the suspension is printed in the technical data of the operating instructions.
Documents and quotation
The official VEGA VEGACAP 65 (transistor NPN/PNP) specification sheet (34689-EN, version 160112) is attached to this page for download and covers the technical data, dimensions and wiring summarised above.
Share the application details with our sales desk in Muscat and we will match them to the right variant and prepare a quote. Seven Star LLC supplies these instruments as an independent company, not as the manufacturer’s agent; see our level instrumentation category for related products. Please confirm approvals, cable length and fitting against the manufacturer’s data before ordering.
Datasheets & Documents
- Datasheet VEGA VEGACAP 65 Specification Sheet (34689-EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
VEGA is a German maker of level and pressure instruments. Bruno Grieshaber founded the company in 1959 in Triberg in the Black Forest, and it has been based in Schiltach since 1975, still family owned as VEGA Grieshaber KG. VEGA is best known for radar level sensors: it introduced the first two-wire radar level sensor in 1997 and the first 80 GHz radar sensor for bulk solids, the VEGAPULS 69, in 2015.
Seven Star LLC is an independent supplier listing VEGA radar and guided wave radar transmitters, point level switches, pressure transmitters and signal conditioning instruments for buyers in Oman and the GCC. Sensors are matched from the product code on the type label.
VEGA at a glance
| Origin | Founded by Bruno Grieshaber in 1959 in Triberg, Germany |
|---|---|
| Headquarters | Schiltach, Black Forest, Germany (since 1975) |
| Ownership | Family-owned company: VEGA Grieshaber KG |
| Milestones | First two-wire radar level sensor (1997), first 80 GHz radar for bulk solids, VEGAPULS 69 (2015), VEGAPULS 6X single radar platform for liquids and solids |
| Product families | VEGAPULS radar, VEGAFLEX guided wave radar, VEGASWING and VEGAPOINT switches, VEGACAL capacitive probes, VEGABAR and VEGADIF pressure, VEGAMET and VEGADIS signal conditioning |
VEGA sensor and instrument series
| Series | Type | Typical use |
|---|---|---|
| VEGAPULS 6X, VEGAPULS 69, VEGAPULS 64 | Process radar level transmitters (80 GHz) | Storage and process tanks, reactors with agitators, silos and bulk solids |
| VEGAPULS 11, 21, 31, 42 | Compact radar sensors | Water and wastewater, simple storage tanks; VEGAPULS 42 with IO-Link for machine integration |
| VEGAPULS C 21, C 11, C 22, C 23 | Radar sensors with fixed cable, IP68 | Wet wells, pumping stations, open channels and river levels |
| VEGAFLEX 81, 82, 83, 86 | Guided wave radar (TDR) | Level and interface in liquids, bulk solids, hygienic and high-temperature or high-pressure service (VEGAFLEX 86) |
| VEGASWING 61, 63, VEGAPOINT 21 | Vibrating and capacitive point level switches | Overfill protection, dry-run protection and high or low level alarms |
| VEGACAL 62 to VEGACAL 67 | Capacitive rod and cable probes | Point and continuous level in solids and conductive or adhesive liquids |
| VEGABAR 82, 83, 28, 29, 38 | Pressure transmitters, ceramic or metallic cell | Process pressure and hydrostatic level; compact 18/19 and 28/29/38 versions for utilities |
| VEGADIF 85 | Differential pressure transmitter | DP flow, filter monitoring and level in pressurised vessels |
| VEGAMET 841, VEGADIS 176 | Controller and loop display | Level display, pump control and remote indication of 4-20 mA signals |
Where VEGA instruments are used
VEGA radar sensors measure level in crude oil and product tanks, separators, chemical reactors, cement and aggregate silos, grain stores and water reservoirs. Compact cable radars are widely used in wastewater pumping stations and flood monitoring. Because 80 GHz radar focuses a narrow beam, it can measure past internal structures in a tank, and it is not affected by the temperature, pressure or vapour above the product, which suits hot Gulf storage tanks.
Ordering VEGA instruments: what we need
The product code on the type label (for example PS64.XXXXXXX) fixes the measuring range, antenna or probe, process connection, electronics and approvals. Send it with the serial number. For a new measurement add the medium and its dielectric constant if known, tank or silo height and internals, process pressure and temperature, process connection, output (4-20 mA HART, PROFIBUS PA, Modbus or IO-Link), and any hazardous-area or overfill protection approval required.
Facts checked against VEGA company and product information, October 2026.
Browse VEGA products by category: Level Transmitter, Pressure Instrumentation, Controllers and Data Acquisition.
Related products
Frequently Asked Questions
Up to 32 m (105 ft).
Transistor NPN/PNP with 10…55 V DC supply.
-1…+64 bar and -50…+200 °C.
VEGA says measurement is over the entire probe length, so the vessel height can be fully used.
Tensile load on the cable and the roof load.