Brand: Lumel
Lumel RE82 131100M0 PID Temperature Controller, 48 x 96 mm
Description
The Lumel RE82 131100M0 is a 48 x 96 mm panel temperature controller with a universal input for Pt100 and Pt1000 sensors, ten thermocouple types and 0/4 to 20 mA or 0 to 5/10 V signals. It runs on/off, PID, step-by-step valve control or heating-cooling PID control with a SMART PID algorithm and auto-tuning. This code has three relay outputs, one 0/4 to 20 mA analog output, a 24 V d.c. transmitter supply, two binary inputs and RS-485.
Control features for furnaces, ovens and heaters
The manual names plastics, food and dehydration industries, and any process where temperature must be stabilised. The set point can be a fixed value, a programmed profile or a value read from an additional input, and a soft-start function limits the heat-up rate. A timer function, eight alarm types with an alarm latch and up to four PID parameter sets with gain scheduling help on processes whose behaviour changes with temperature. The controller can measure heater current through a transformer input and flag an overheating or shorted control element such as a solid-state relay, so a failed SSR is seen before the load runs away.
Two 21-point red and green bargraphs on the front show the process value against the set point, which is useful for operators at a glance.
Key features from the data sheet
- Universal measuring input with binary input control.
- On/off, PID, PID step-by-step (valve) and PID heating-cooling control.
- Relay, OC or analog outputs depending on code, with alarm outputs of eight types and an alarm latch.
- Soft start, timer and password protection.
- Heater current measurement with a heater-fault check.
- RS-485 MODBUS RTU.
Technical specification
Input types and error
| Input | Range and error |
|---|---|
| Pt100 / Pt1000 | -200 to 850 degrees C; 0.2% |
| Thermocouple J (Fe-CuNi) | -100 to 1200 degrees C; 0.3% |
| Thermocouple T (Cu-CuNi) | -100 to 400 degrees C; 0.3% |
| Thermocouple K (NiCr-NiAl) | -100 to 1372 degrees C; 0.3% |
| Thermocouple E (NiCr-CuNi) / N (NiCrSi-NiSi) / L (Chromel-kopel) | -100 to 1000 / -100 to 1300 / -100 to 800 degrees C; 0.3% |
| Thermocouple S / R (Pt-Rh) | 0 to 1767 degrees C; 0.5% |
| Thermocouple B (PtRh30-PtRh6) | 200 to 1767 degrees C; 0.5% |
| Current channel | 0/4 to 20 mA; 0.2% plus or minus 1 digit |
| Voltage channel | 0 to 5 / 10 V; 0.2% plus or minus 1 digit |
Outputs, interface and construction
| Parameter | Specification |
|---|---|
| Relay outputs | Voltage-free NO contacts, 2 A / 230 V a.c. |
| Transistor voltage output | 0/5 V, up to 40 mA (to drive an SSR) |
| Continuous voltage / current output | 0 to 10 V at load 1 kohm or more; 0 to 20 mA or 4 to 20 mA at load up to 500 ohm |
| Transmitter supply | 24 V d.c., up to 30 mA |
| RS-485 | MODBUS RTU, 8N2, 8E1, 8O1, 8N1; 4.8 to 57.6 kbit/s |
| Display | Bargraph 2 x 21 points, red and green, with numeric display |
| Dimensions | 48 x 96 x 93 mm; cut-out 45 +0.6 x 92 +0.6 mm; panel up to 15 mm thick |
| Protection (EN 60529) | IP65 from the front, IP20 from the terminal side |
| Supply | 85 to 253 V a.c./d.c.; a 20 to 40 V a.c./d.c. supply is also listed |
| Ambient / storage temperature | 0 to 23 to 50 degrees C / -20 to 70 degrees C |
| Humidity | Below 85%, no condensation; any operating position |
| Standards named | Immunity EN 61000-6-2, emission EN 61000-6-4; installation category III, pollution level 2, altitude 2000 m |
| Isolation | 300 V phase-to-earth on supply and outputs; 50 V on input circuits |
Choosing the RE82 code
The data sheet prints three codes with the same universal input, 85 to 253 V a.c./d.c. supply, two binary inputs, 24 V transmitter supply and RS-485. RE82 431100M0 has two relays, one 10 V analog output and one 0/4 to 20 mA output. RE82 131100M0 (this page) has three relays and one 0/4 to 20 mA output. RE82 111100M0 has four relay outputs. All carry Polish and English documentation and a test certificate, and changing the last digit to 2 adds a paid calibration certificate. Pick the analog output for a valve or SCR driver, and the relay version for contactor or SSR on-off control.
Installation and commissioning notes from the manual
Fix the controller with the four supplied screw clamps in a panel up to 15 mm thick with a 45 x 92 mm opening. The set also contains two 16-pole screw plugs for wires up to 2.5 mm2, and a seal. Select Pt100, thermocouple, current or voltage input with the terminal jumpers and the menu, then run the auto-tuning routine, which the manual describes together with Gain Scheduling for four PID sets. Verify the relay load against the 2 A / 230 V rating and use an SSR on the 0/5 V output for heavier heaters.
Where it is used
Typical GCC applications are plastics and packaging lines, food ovens and dryers, laboratory furnaces and process heaters, where a single 48 x 96 mm instrument replaces separate controller and indicator. Panel ambient is rated to 50 degrees C, so hot enclosures need checking.
Selection and installation notes
A temperature controller is selected from the input sensor, the control mode and the outputs it must drive. Match the sensor type and range, choose the output that suits the heater or valve (relay, analog or logic), run the auto-tuning with the process at normal load, set the alarm limits and keep a record of the final parameters. Use a separate protection device where overheating would be dangerous.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Frequently asked questions
Which sensors can the RE82 read?
Pt100, Pt1000, thermocouples J, T, K, S, R, B, E, N and L, and standard signals 0/4 to 20 mA or 0 to 5/10 V.
What control algorithms does it provide?
On/off, PID, PID step-by-step for valves and PID heating-cooling, using the SMART PID algorithm with auto-tuning.
How many relays does RE82 131100M0 have?
Three relay outputs, plus one 0/4 to 20 mA analog output.
Can it detect a failed heater element?
The data sheet lists heater current measurement with a check of heater overheating or shorting of the control element, for example an SSR.
What is the panel cut-out?
45 x 92 mm for a 48 x 96 mm front.
Documents and quotation
This catalogue entry for the RE82 131100M0 leads to an enquiry with Seven Star LLC, an independent supplier in Muscat. The Lumel RE82 user manual is attached; data sheet RE82-19I gives the three ordering codes and input table used here. Confirm the final selection against current Lumel documents. Find similar items under Controllers & Data Acquisition.
Datasheets & Documents
- Manual RE82 temperature controller user manual (Lumel) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lumel is a Polish manufacturer of measurement and industrial automation equipment, founded in the 1950s and headquartered in Zielona Góra, where it also runs an aluminium casting business through its subsidiary Lumel Alucast. It describes itself as the largest Polish manufacturer of measurement and automation equipment. Lumel's range covers panel meters, power network meters and analysers, power controllers and recorders.
Seven Star LLC is an independent supplier in Muscat. We list Lumel instruments, each with the manufacturer document, for switchboard builders and plant engineers in Oman and the GCC.
Lumel company profile
| Founded | 1950s, Zielona Góra, Poland |
|---|---|
| Headquarters | Zielona Góra, Poland |
| Group company | Lumel Alucast (aluminium die casting) |
| Product families | N-series digital panel meters, N14, N43 and ND20 power network meters, N100 network analysers, NF20 power factor controllers, RP3 thyristor power controllers, temperature controllers and recorders |
Lumel product series
Power measurement includes the N14 and ND20 three-phase power network meters with RS-485, the N43 DIN rail meter, the N100 network analyzer with Ethernet and the N32H digital DC circuit meter. The NF20 is a power factor controller for 4 to 12 capacitor steps.
Process instruments include the N31U universal digital panel meter, the RE82 PID temperature controller in 48 x 96 mm format, the RP3 three-phase thyristor power controller from 40 to 450 A and the HT20 Ethernet temperature and humidity monitor with PoE.
Where Lumel instruments are used
Switchboards and distribution panels, generator and capacitor bank panels, battery and rectifier circuits, industrial heating, plastics and food processing lines, and monitored storage and server rooms, wherever readings must reach a PLC, SCADA or building system.
Lumel products we list
Ordering Lumel instruments: what we need
Send the full ordering code, which defines inputs, supply voltage and communication, or give the measured quantities, CT and VT ratios, supply voltage, output and interface required.
Facts checked against Lumel's own company pages (lumel.com.pl), October 2026.
Browse Lumel products by category: Power Meters & Power Quality.
Related products
Frequently Asked Questions
Pt100, Pt1000, thermocouples J, T, K, S, R, B, E, N and L, and standard signals 0/4 to 20 mA or 0 to 5/10 V.
On/off, PID, PID step-by-step for valves and PID heating-cooling, using the SMART PID algorithm with auto-tuning.
Three relay outputs, plus one 0/4 to 20 mA analog output.
The data sheet lists heater current measurement with a check of heater overheating or shorting of the control element, for example an SSR.
45 x 92 mm for a 48 x 96 mm front.