Brand: HOPPECKE
HOPPECKE grid | power V M 2-900 OSP.HC Cell 2 V 987 Ah
Description
grid | power V M 2-900 is a 2 V vented lead-acid cell of the HOPPECKE grid | power V M OSP.HC series, DIN designation 10 OSP.HC 850. The brochure type table gives 987 Ah at C10 to 1.80 V per cell, 69.9 kg and a maximum size of 215 x 193 x 710 mm.
An OSP.HC cell with strong high-current capability for UPS and signalling
The V M series is built for good high-current capability: an innovative electrode structure lowers the investment per ampere, and a low-antimony selenium alloy gives a very high expected service life. HOPPECKE system connectors give higher short-circuit safety while cells are installed.
The brochure splits the series into OSP.HC cells (2 V, 125 to 3880 in the type number) and OSP.HB monoblocs (6 V, 6-50 to 6-200). The HB blocs add the HOPPECKE SST terminal design for IEEE 450 testing and an external insulated inter-cell connector so single cell voltages can be read inside the block. The 2-900 is an HC cell in Figure B.
Selling points in the V M brochure
- Very good high-current capability and low investment cost from the electrode structure.
- Very high expected service life; design life up to 20 years for HC cells and HB blocs.
- Optional grid | AquaGen recombination system stretches water refill intervals up to maintenance-free.
- Typical uses printed: power supply systems, UPS, traffic signalling and lighting; HB also IT and telecom and emergency lighting.
Technical specification
Data for grid | power V M 2-900 (brochure type table)
| Parameter | Specification |
|---|---|
| Type / DIN designation | grid | power V M 2-900 / 10 OSP.HC 850 |
| Cell type | 2 V flooded lead-acid, OSP.HC |
| Discharge capacity C10 (1.80 V per cell) | 987 Ah |
| Discharge capacity C5 (1.77 V per cell) | 859 Ah |
| Discharge capacity C3 (1.75 V per cell) | 744 Ah |
| Discharge capacity C1 (1.67 V per cell) | 545 Ah |
| Weight | 69.9 kg |
| Maximum electrolyte weight | 17.4 kg, density 1.24 kg/l |
| Maximum L x W x H per DIN 40736-1 | 215 x 193 x 710 mm, figure B |
| Design life | up to 20 years |
| Float setting (manual) | 2.23 V per cell, tolerance 1 percent |
| Rest voltage when fully charged (manual) | 2.08 V per cell, tolerance 0.01 V |
Derived values (calculated here)
| Parameter | Specification |
|---|---|
| Stored energy at C10 | roughly 2.0 kWh per cell (2 V x 987 Ah) |
| Current for a 1 hour discharge | C1 = 545 Ah to 1.67 V per cell, so roughly 545 A |
Using the V M table to pick a cell
The OSP.HC list runs from 2-125 (3 OSP.HC 105, 142 Ah, 15.3 kg, 105 x 208 x 420 mm) to 2-3880 (36 OSP.HC 3780, 4113 Ah, 274.9 kg, 215 x 580 x 815 mm), with Figures A to D by size. The 2-810 to 2-1260 cells share the 215 mm length and 710 mm height with the 2-900.
Compare C1 and C3 for UPS or tripping duty and use C10 for long standby. Confirm the exact type code, plug option and terminal hardware before ordering.
Installation and charging notes from the manual
Rooms need ventilation that keeps hydrogen under 4 percent by volume, a load-bearing electrolyte-resistant floor and warning signs to IEC 62485-2. Insulation resistance of a new battery must exceed 1 megohm and must not fall below 100 ohm per volt of nominal voltage.
Float at 2.23 V per cell. Equalizing charge is only needed after deep discharge, long uneven warming or large cell-voltage scatter, at a constant 2.4 V per cell for up to 72 hours at no more than 20 A per 100 Ah, stopping if the temperature passes 55 °C. Check water levels at the regular service visits.
Switchgear, signalling and UPS batteries
The brochure lists power supply systems, UPS and traffic systems with signalling and lighting. General engineering note: in Gulf rail, metro and road-tunnel signalling a 2 V cell string gives a long-life, easily inspected DC source; the buyer still has to verify discharge duty against the load profile.
Related HOPPECKE items
The V H series uses OSP.XC plates with a higher electrolyte density, grid | power V L covers OPzS cells, and the AquaGen pro plug is the common recombination option.
Frequently asked questions
What does 10 OSP.HC 850 mean?
The DIN designation: ten positive plates, OSP.HC construction and a DIN class of 850 Ah, while the brochure C10 value is 987 Ah.
What is the design life of V M?
The brochure gives up to 20 years for both the OSP.HC and OSP.HB versions.
Which float voltage applies?
The manual lists 2.23 volts per cell, plus or minus 1 percent, for OSP.HB and OSP.HC.
How heavy is one cell?
69.9 kg including up to 17.4 kg of electrolyte at 1.24 kg per litre.
Does Seven Star LLC act as a HOPPECKE distributor?
No. Seven Star LLC is not a HOPPECKE distributor; it is an independent Muscat-based supplier that quotes HOPPECKE products on request.
Documents and quotation
The official HOPPECKE datasheet and user manual for grid power V M 2-900 are hosted on this page for download. Seven Star LLC is an independent supplier in Muscat; send your quantity and delivery location through the quotation form and we will quote this item. Please confirm the exact order code, supply voltage and output options against the documents before ordering. More related products: product category.
Datasheets & Documents
Reviews (0)
How would you rate this product? Cancel reply
About brand
HOPPECKE is a German family-owned manufacturer of industrial batteries and energy storage, based in Brilon, and describes itself as the largest privately owned European manufacturer of industrial batteries. Its website states more than 2,000 employees in 22 countries, 12 production locations and customers in 150 countries.
Stationary, solar and rail batteries
The company serves four application areas: trak for intralogistics, grid for stationary battery systems such as UPS and telecom, sun for the intermediate storage of renewable energies, and rail for rail and metro systems. The grid range covers grid | Xtreme VR pure lead AGM blocks, grid | XtremeStack racks, grid | power vented cells and FNC fibre nickel-cadmium cells, while sun | power adds cyclic AGM and gel batteries.
Supply through Seven Star LLC
Seven Star LLC is an independent supplier in Muscat that quotes HOPPECKE batteries for projects in Oman and the GCC, with the official data sheet or brochure and manual attached to each product page.
Related products
Frequently Asked Questions
The DIN designation: ten positive plates, OSP.HC construction and a DIN class of 850 Ah, while the brochure C10 value is 987 Ah.
The brochure gives up to 20 years for both the OSP.HC and OSP.HB versions.
The manual lists 2.23 volts per cell, plus or minus 1 percent, for OSP.HB and OSP.HC.
69.9 kg including up to 17.4 kg of electrolyte at 1.24 kg per litre.
No. Seven Star LLC is not a HOPPECKE distributor; it is an independent Muscat-based supplier that quotes HOPPECKE products on request.