- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Automation Software
- Machine Vision
- Robotics
Brand: Caprari
Caprari NC.E EN 733 End-Suction Pumps for Fire-Fighting Units
Description
EN 733 end-suction pumps built for fire-fighting units
The Caprari NC.E is a series of EN 733 end-suction centrifugal pumps. The catalogue cover states that they comply with UNI EN 12845 and UNI EN 12259-12, and describes them as ideal for building fire-fighting units driven by electric motors or internal combustion engines. The pump casing is a volute type with a flanged delivery port; the impeller is a high-efficiency closed type with balanced axial thrust, in AISI 316 stainless steel or bronze.
The catalogue (code 996935B/05-26, 44 pages) lists two types, NC.EC and NC.EK, in sizes from DN32 to DN150 on the delivery port, mostly at 2,900 rpm, with lower speeds on the largest sizes. Unlike the monobloc NMC, the NC.E is a separate-motor pump with a back pull-out arrangement.
Key features from the catalogue
- BACK PULL OUT design with an optional flexible coupling and spacer, so the wet end can be removed from the rear for inspection and repair without disconnecting the motor or the casing from the piping.
- Stainless steel shaft fully protected from contact with the pumped water, guided by two ball bearings in the connecting support with permanent high-quality grease lubrication.
- Mechanical seal housed in the connecting support, easily replaceable; seal faces silicon carbide against silicon carbide with AISI 316 spring and EPDM gaskets as standard, to DIN 24960 and ISO 3069.
- Couples to IP55 standard electric motors with B3 mounting, or to an internal combustion engine; the French text adds that high-efficiency motors can be fitted.
- Bronze impeller wear ring.
Technical specification
| Parameter | Specification |
|---|---|
| Series | NC.E, types NC.EC and NC.EK |
| Standard | EN 733 end-suction; cover states UNI EN 12845 and UNI EN 12259-12 |
| Delivery port | DN32 to DN150 in the performance list |
| Speeds in the list | 2,900 rpm for most; 2,640 rpm (NC125-315EC); 2,100 rpm (NC125-400EC); 1,480 rpm (NC150-315EC); 2,045 rpm (NC150-400EC) |
| Maximum liquid temperature | +90 C |
| Minimum liquid temperature | -10 C |
| Closed-discharge run time at 90 C | 30 seconds maximum |
| Rotation | Clockwise seen from the drive side |
| Ports | Axial suction; radial delivery pointing upwards |
| Performance tolerance | UNI/ISO 9906 Grade 2B (cold water 15 C, 1 bar; density 1 kg/dm3, viscosity 1 mm2/s or less) |
| Liquids | Any liquid chemically and mechanically compatible with the pump materials |
| Flanges | UNI EN 1092-2, PN10/16 from DN32 to DN200 (DN200 also PN10), PN16 at DN250 |
Materials
| Part | NC.EC | NC.EK |
|---|---|---|
| Pump casing | Cast iron or nodular cast iron | Cast iron |
| Impeller | Bronze or stainless steel | Bronze or stainless steel |
| Lantern bracket / support | Cast iron | Cast iron |
| Shaft, nut, spacer sleeve, feather key | Stainless steel | Stainless steel |
| Impeller wear ring | Bronze | Bronze |
| Seal rings, water retainer | – | Nitrile rubber |
| Mechanical seal (NC.EC list) | Carbon/ceramic/rubber | – |
| Duck foot pedestal | – | Steel |
Screws and nuts are stainless steel. The general-data page lists silicon carbide seal faces as standard, while the NC.EC materials page lists carbon/ceramic/rubber; confirm the seal for the ordered type.
Selected performance limits and weights
The operating-limits page lists, for every impeller diameter, maximum speed, maximum flow QR and maximum absorbed power P2. Selected rows with the pump weight from the dimensions pages:
| Model | Speed rpm | QR max l/s | P2 max kW | Weight kg |
|---|---|---|---|---|
| NC32-200EC/204-2900 | 2,900 | 5.8 | 6.9 | 40 |
| NC40-200EK/214-2900 | 2,900 | 8.7 | 10.0 | 45 |
| NC50-160EK/174-2900 | 2,900 | 17.6 | 11.4 | 38 |
| NC65-125EK/139-2900 | 2,900 | 27.8 | 9.6 | 39 |
| NC65-250EC/249-2900 | 2,900 | 26.7 | 36.2 | 89 |
| NC80-200EK/214-2900 | 2,900 | 47.3 | 38.7 | 75 |
| NC80-250EC/207-2900 | 2,900 | 33.3 | 19.5 | 91 |
| NC100-160EK/174-2900 | 2,900 | 60.3 | 26.6 | 72 |
| NC50-315EK/342-2900 | 2,900 | 23.2 | 67.2 | 87 |
| NC100-315EK/342-2900 | 2,900 | 80.6 | 174.9 | 135 |
| NC125-250EK/278-2900 | 2,900 | 87.1 | 146.8 | 140 |
The largest listed duties are NC150-315EC/322-1480 at 133.3 l/s and NC150-400EC/420-2045 at 125 l/s, with 229.6 kW absorbed on the latter. The weights are for the pump only, and the dimensions pages also give the duck foot pedestal and shaft projection dimensions for each model.
Selection, ordering and installation
The code NC.E 100-200 E C 214-2900 reads series, nominal diameter and size, impeller reference, type (C or K), impeller diameter in mm and rotational speed. Choose the impeller diameter against the duty point on the model operating-data page, which carries the head, power, efficiency and NPSH curves. Keep the closed-discharge running time to the 30-second limit at 90 C.
Applications in GCC industries
The catalogue positions the NC.E for fire-fighting units with an electric or engine driver. The same EN 733 family also suits industrial and civil water duty. The catalogue states the two European standards but prints no UL, FM or other listing, and no certificate numbers, so none is claimed here. Standard seal and impeller materials are for fresh water; ask for the stainless steel impeller and a materials review for brackish or seawater service.
Selection and installation notes
Select a pump from the duty point: the flow, the head, the liquid and its temperature, the supply voltage and the expected operating hours. Check the electrical supply and cable size against the motor rating, install the pump as the manual shows on a firm base with pipework that does not strain the ports, protect the motor against overload and dry running, and fit non-return and isolation valves in the delivery line. Keep the installation and commissioning record, and plan routine inspection of seals, bearings and wear parts.
For fire-fighting service, confirm the standard, the duty point and the acceptance tests required by the local authority or the project specification before ordering.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Related items and documents
Other Caprari pumps are listed under pumps; the official catalogue is attached. Seven Star LLC is an independent supplier in Muscat: send the required flow, head, driver type and any project fire-water specification and we will check it against the Caprari catalogue before quoting.
Datasheets & Documents
- Datasheet Caprari NC.E end-suction pumps EN 733 catalogue (EN/FR/IT, 05-26) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Caprari is an Italian pump manufacturer, founded in 1945 by Amadio Caprari as Idromeccanica Caprari and headquartered in Modena. By 1950 it was building vertical lineshaft pumps, in 1968 it produced its first submersible deep-well pump, and from the 1970s it opened subsidiaries abroad. The Italian investment firm Ambienta acquired Caprari in February 2021.
Seven Star LLC is an independent supplier in Muscat. We list Caprari pumps for water utilities, farms, contractors and industry in Oman and the GCC.
Caprari company profile
| Founded | 1945, Italy, by Amadio Caprari |
|---|---|
| Headquarters | Modena, Italy |
| Ownership | Ambienta, since February 2021 |
| Production | Plants in Italy, China and Turkey |
| Product families | NMC and NC.E EN 733 end-suction pumps, MEC-MG flanged pumps for diesel drives, E6 and E8 stainless borehole pumps, Desert sand-resistant submersible pumps, D-M drainage and sewage pumps, CVD vertical multistage pumps |
Milestones
- 1945: Amadio Caprari founds Idromeccanica Caprari.
- 1965: The current Modena headquarters opens.
- 1968: Caprari builds its first submersible deep-well pump.
- 2021: Ambienta acquires Caprari.
Caprari product series
Borehole pumps include the E6NVX and E8NVX 6 and 8 inch stainless steel pumps and the Desert E4X and E6X sand-resistant pumps. Surface pumps include the NMC and NMCS monobloc EN 733 pumps from DN32 to DN150, the NC.E end-suction pumps for fire-fighting units, the PM high pressure horizontal multistage pumps, the CVD vertical multistage pumps and the SCC double-suction split case pumps from DN100 to DN700.
The P Series P6P and P8P are vertical lineshaft pumps, the MEC-MG, MEC-AG and BHG pumps are flanged for diesel engine drive, and the D-M Series covers submersible drainage and sewage pumps.
Where Caprari pumps are used
Well fields and water supply, farm irrigation, pressure boosting, fire-fighting pump sets, drainage of sites and basements, and sewage lifting.
Caprari products we list
Ordering Caprari pumps: what we need
Send the model or the required flow and head, the liquid, borehole diameter or installation type, power supply and motor or engine drive.
Facts checked against Caprari's own history page and Ambienta's 2021 announcement, October 2026.
Browse Caprari products by category: Pumps.
Related products
Frequently Asked Questions
EN 733 for the end-suction design, and the cover states compliance with UNI EN 12845 and UNI EN 12259-12 for fire-fighting units.
Liquid from -10 C to +90 C, with a closed-discharge running limit of 30 seconds at 90 C.
Yes. The catalogue says it suits fire-fighting units with electric motors or internal combustion engines, with B3 IP55 electric motors as the electric option.
A mechanical seal with silicon carbide faces, AISI 316 spring and EPDM gaskets, to DIN 24960 and ISO 3069.
The wet end can be removed from the rear for inspection or repair without disconnecting the motor or the casing from the piping, using the optional spacer coupling.

Reviews
There are no reviews yet.