Tokyo Keiso VC Series V-Cone Differential Pressure Flowmeter
Description
V-cone differential pressure meter for short straight runs
The Tokyo Keiso VC series V-Cone flowmeter is a differential pressure meter in which a V-shaped cone sits in the centre of the line. The fluid is forced around the cone, its speed increases at the edge, and the static pressure falls. The upstream pressure and the pressure taken from the centre of the cone, measured at two tapping points, give the differential pressure that is converted to flow by the usual Bernoulli-based relation with a discharge coefficient.
Tokyo Keiso lists several benefits: a self-straightening flow profile, stable low-flow signals, no liquid retention, and straight-run requirements it quotes as less than one fifth of those for traditional orifice plates and vortex meters. The meter has no moving part, handles liquids, slurries, gases and steam, and is made from stainless steel.
Technical specifications
Data from the Tokyo Keiso VC series catalogue TG-F821-4E (dated February 2007; an older edition, so confirm current availability).
| Parameter | Specification |
|---|---|
| Manufacturer / series | Tokyo Keiso VC series V-Cone flowmeter |
| Connection size | 15A (1/2 in) to 400A (16 in): 15, 20, 25, 40, 50, 65, 80, 100, 125, 150, 200, 250, 300, 350, 400A |
| Material | Stainless steel SS304 (standard), SS316L |
| Process connection | Flange: JIS 10K or 20K RF slip-on, ASME class 150 or 300 RF slip-on, others |
| DP tappings | Screw connection Rc1/2 or Rc1/4 |
| Beta (contraction) ratio | 0.45, 0.50, 0.55, 0.60, 0.65, 0.70, 0.75, 0.80 |
| Uncertainty of discharge coefficient | 2.0% (standard) |
| Turndown | 10:1 (standard) |
| Reynolds number | 8,000 or higher |
| Minimum differential pressure | 0.025 kPa (gas, liquid); 0.05 kPa (steam) |
| Rating reference | Fluid temperature and maximum pressure follow the flange rating and material; JIS 10K 1.4 MPa at 120 °C; JIS 20K 3.4 MPa at 120 °C (reference table) |
| Face-to-face length | 203 mm (15A to 25A) to 762 mm (300A to 400A); for example 40A 254 mm, 100A 406 mm, 200A 660 mm |
| Options | Differential pressure transmitters (FCX-A3 FKC type); SS316 three-way valve manifold |
Straight-run and sizing rules
The catalogue tabulates the upstream and downstream straight length required behind a single 90 degree bend, two bends, a tee, butterfly or gate valves, expanders and reducers, separately for liquids, gases or steam at Reynolds number up to 200,000 and for gases or steam above that. Several fittings can sit directly upstream with zero straight run, and one more diameter is added when the beta ratio is 0.70 or more. The run is measured from the flange face of the meter.
The flow formula uses the beta ratio, pipe inside diameter, discharge coefficient, differential pressure, density and, for gas, the expansion factor, so sizing needs the fluid density, line pressure and expected flow range.
Ordering notes
The model code selects connection type and rating, material, connection size and beta ratio (two-digit codes 45 to 80). Non-standard specifications are possible on request. Please give the fluid and its condition, flow range and flange standard so that the beta ratio and the differential pressure range can be matched to your transmitter.
How the VC-VCONE Tokyo Keiso VC series works
The VC series is a differential pressure meter with a cone in the middle of the pipe. The flow must pass around the cone, so the speed rises at the edge and the static pressure falls. The meter takes the pressure upstream and the pressure at the centre of the cone, and the difference gives the flow rate. The cone also flattens the velocity profile, so the meter needs short straight pipe runs. The VC-VCONE has no moving parts.
Where the VC-VCONE is used
- Liquid, gas and steam lines
- Slurries and dirty process fluids
- Sites with little straight pipe
- Low flow rates where stable signals are needed
- Fuel, utility and process plant piping
Selection checklist for the VC-VCONE
- Line size from 15A to 400A
- Beta ratio from 0.45 to 0.80
- Material SS304 or SS316L
- Flange: JIS 10K, JIS 20K, ASME class 150 or 300
- Tapping connection of Rc1/2 or Rc1/4
- Fluid, temperature and pressure
- Flow range and Reynolds number of 8,000 or higher
- Differential pressure transmitter and manifold options
Installation, commissioning and maintenance notes for the VC-VCONE
Fit the meter between flanges with the high pressure tapping upstream and keep to the straight lengths in the catalogue. Connect the impulse lines to a differential pressure transmitter through a manifold, and fill the lines for a liquid or drain them for a gas. Set the transmitter range from the sizing sheet. Check the zero and the lines at planned intervals.
Requesting a quotation for the VC-VCONE
Please send the line size, the fluid, the flow range, the pressure, the temperature and the flange standard. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided. The catalogue on this page is an older edition, so availability is confirmed before an order.
VC-VCONE accuracy and turndown
The standard uncertainty of the discharge coefficient is 2.0 percent and the standard turndown is 10 to 1. The minimum differential pressure is 0.025 kPa for gas and liquid and 0.05 kPa for steam.
VC-VCONE face-to-face length
The length is 203 mm for 15A to 25A and rises to 762 mm for 300A to 400A. A 40A meter is 254 mm, a 100A meter is 406 mm and a 200A meter is 660 mm.
VC-VCONE pressure rating
Pressure and temperature follow the flange rating and the material. The reference table lists 1.4 MPa at 120 degrees C for JIS 10K and 3.4 MPa at 120 degrees C for JIS 20K.
VC-VCONE sizing records
Keep the sizing sheet, the beta ratio and the transmitter range with the instrument file.
Choosing the right VC-VCONE beta ratio
A smaller beta ratio gives a larger differential pressure at low flow, and a larger beta ratio keeps the pressure loss lower.
Documents and quotation
The Tokyo Keiso VC V-Cone catalogue is attached as a PDF. It is the 2007 edition, so we recommend confirming current availability and specification with the manufacturer through our RFQ process. Seven Star LLC is an independent supplier in Muscat; price and lead time are confirmed per enquiry. Related range: flowmeters and the ABB ProcessMaster FEP500 for liquid lines where a magnetic meter is preferred.
Datasheets & Documents
- Catalog Tokyo Keiso VC Series V-Cone Flowmeter catalogue (TG-F821-4E, Feb 2007) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Tokyo Keiso is a Japanese manufacturer of flow and level instruments, founded in Tokyo in 1954 as Japan's first maker of variable-area flowmeters. It now builds ultrasonic, Coriolis, electromagnetic and variable-area flowmeters plus level gauges, and set up a production subsidiary in Korea in 2012 for non-contact ultrasonic flowmeters.
Seven Star LLC is an independent supplier in Muscat. We list Tokyo Keiso models from the maker's published technical documents for water, oil and gas, power and chemical plants in Oman and the GCC.
Tokyo Keiso company profile
| Founded | 1954, Tokyo, Japan |
|---|---|
| First products | Variable-area flowmeters, a first for a Japanese manufacturer |
| Headquarters | Tokyo, Japan |
| Leadership | Ryoichi Sugi, President |
| Product families | SONICMAX inline and clamp-on ultrasonic flowmeters (UL3400, UL6300, UL350), MASSMAX Coriolis mass flowmeters, electromagnetic and variable-area flowmeters, float and magnetic level gauges |
Milestones
- 1954: Tokyo Keiso is founded as Japan's first variable-area flowmeter maker.
- 2012: TK Flow Engineering is set up in Korea for ultrasonic flowmeter production.
Tokyo Keiso product series
Ultrasonic flowmeters include the UL350 and SONICMAX UL6300 V2 clamp-on meters and the SONICMAX UL3400 three-beam inline meter. Other flowmeters include the MASSMAX 2400R Coriolis mass flowmeter, the VFM4200 SWIRLMAX vortex meter, the MAGMAX EGM2100C compact electromagnetic flowmeter, the TH series thermal gas flowmeters and the VC series V-Cone differential pressure flowmeter.
Level instruments include the TLR7500 80 GHz microwave level meter, the TGF7200 guided radar, the FM4000 MAG GAUGE magnetic metal tube level gauge and the FW-9000NN servo balance tank gauge for storage tanks.
Where Tokyo Keiso instruments are used
Water and wastewater networks, chemical and petrochemical plants, oil and gas facilities, power stations and tank terminals, with outputs such as 4-20 mA, pulse and digital communication for connection to control systems.
Tokyo Keiso products we list
Ordering Tokyo Keiso instruments: what we need
Send the fluid, line size, flow or level range, pressure and temperature, process connection and materials, output signals and any hazardous-area option. Where a catalogue is older or an option is still in preparation, we say so on the product page.
Facts checked against Tokyo Keiso company profiles and a 2022 interview with its president, October 2026.
Browse Tokyo Keiso products by category: Flowmeters, Level Instrumentation.
Related products
Frequently Asked Questions
A differential pressure meter with a V-shaped cone in the pipe centre; the pressure drop across it is converted to flow.
Tokyo Keiso quotes less than one fifth of the runs needed for orifice plates and vortex meters, and gives a table by fitting.
15A (1/2 in) to 400A (16 in) in SS304 or SS316L with flange connections.
10:1 as standard, with 2.0% uncertainty of the discharge coefficient.
Liquids, slurries, gases and steam, as listed in the catalogue.