Kamstrup flowIQ 3100 Ultrasonic Water Meter Q3 2.5 to 63 m3/h
Description
An ultrasonic cold water meter for blocks, pump stations and meter pits
The Kamstrup flowIQ 3100 is an electronic ultrasonic meter for measuring the distribution and consumption of cold water in blocks of flats, commercial premises, small pump stations and distribution wells. Q3 ranges from 2.5 up to 63 m³/h and the meter is approved with a dynamic range up to R630. The measuring tube is brass or stainless steel with a moulded PPS composite housing on top, and the electronics sit in a hermetically vacuum-sealed chamber, so condensation behind the display glass is avoided. Kamstrup states that the meter fits into a network of MULTICAL 21 household meters, so one reading system can cover the whole building.
Technical specifications
| Parameter | Specification |
|---|---|
| Nominal flow Q3 | 2.5, 4.0, 6.3, 10, 16, 25, 40 and 63 m³/h |
| Dynamic range | 100:1 or 160:1 by type; cover states approval up to R630 |
| Approvals | MID DK-0200-MI001-017 (up to 63 m³/h); OIML R 49 accuracy class 2, sensitivity U0/D0 |
| Water temperature | 0.1 to 30 °C (T30, Sigfox) or 0.1 to 50 °C (T50, wired and wireless M-Bus) |
| Drinking water approvals | WRAS, ACS, Belgaqua, SCU, PZH, BWGL |
| Pressure stage | Threaded PN16; flanged PN25 to EN 1092-1 |
| Protection / ambient | IP68; ambient/meter temperature 2 to 55 °C |
| Housing materials | Threaded: DZR brass CW511L; flanged: stainless steel 1.4408; PPS 40 % glass-fibre measuring tube and housing; stainless steel reflectors; EPDM O-ring |
| Battery | 3.65 VDC, one C-cell lithium; up to 16 years (up to 8 years for M-Bus at battery temperature below 55 °C) |
| Communication | Wireless M-Bus 868 MHz (C1, T1 OMS), linkIQ (selected markets), Sigfox, wired M-Bus |
| Data | Daily registers for 460 days, 36 months and 10 years of monthly/yearly data; optical eye with USB configuration |
| ATEX | 2014/34/EU, zone 2 |
Meter sizes and connections
The datasheet lists 23 type numbers in the form 031-YY-xxx-8XX, where YY is the communication package and XX the country code. A selection with the standard 100:1 and the 160:1 range variants is shown below; type numbers marked for selected markets only are omitted. Check valves are ordered separately, and strainers are factory-fitted on threaded meters except type C03.
| Type number | Q3 (m³/h) | Connection | Dynamic range | Length (mm) |
|---|---|---|---|---|
| 031-YY-C5C-8XX | 2.5 | G1B (R3/4) | 100 | 190 |
| 031-YY-C03-8XX | 4.0 | G5/4B (R1) | 100 | 175 |
| 031-YY-C1T-8XX | 4.0 | G5/4B (R1) | 100 | 260 |
| 031-YY-C1U-8XX | 6.3 | G5/4B (R1) | 100 | 260 |
| 031-YY-C2U-8XX | 6.3 | G5/4B (R1) | 160 | 260 |
| 031-YY-C1K-8XX | 6.3 | G1½B (R5/4) | 160 | 260 |
| 031-YY-C1D-8XX | 10 | G5/4B (R1) | 160 | 260 |
| 031-YY-C5J-8XX | 10 | G2B (R1½) | 100 | 300 |
| 031-YY-C8V-8XX | 16 | G2B (R1½) | 160 | 300 |
| 031-YY-C0L-8XX | 16 | DN50 | 100 | 270 |
| 031-YY-C2W-8XX | 25 | DN50 | 160 | 270 |
| 031-YY-C0M-8XX | 25 | DN65 | 100 | 300 |
| 031-YY-C2Q-8XX | 40 | DN65 | 160 | 300 |
| 031-YY-C0N-8XX | 40 | DN80 | 100 | 300 |
| 031-YY-C2X-8XX | 63 | DN80 | 160 | 300 |
Installation and selection
The meter can be mounted vertically or horizontally independent of the existing piping. For a smaller household meter with the same communication family, see the Kamstrup flowIQ 2200; larger bulk sizes DN125 to DN300 are on the Kamstrup flowIQ 4200 page. The meter can only be opened by Kamstrup, and opening it voids billing validity. Browse the other meters in Flowmeters.
How the Kamstrup flowIQ 3100 works
The flowIQ 3100 measures flow by ultrasound. Two transducers send sound pulses through the water, one with the flow and one against it. The pulse that travels with the flow arrives sooner. The electronics measure the difference in transit time, calculate the flow speed and add up the volume. There are no moving parts in the measuring tube, so the meter holds its accuracy over a wide range of flows.
Where the flowIQ 3100 is used
- Blocks of flats and commercial buildings
- Small pump stations
- Distribution wells and meter pits
- District water networks
- Sites that read meters by radio
Selection checklist for the flowIQ 3100
- Nominal flow Q3 from 2.5 to 63 cubic metres per hour
- Dynamic range of 100:1 or 160:1
- Threaded PN16 or flanged PN25 connection
- Water temperature of up to 30 or 50 degrees C
- Communication: wireless M-Bus, Sigfox or wired M-Bus
- Battery of one C-cell lithium
- IP68 rating for pits
- Type number with the right communication package
Installation, commissioning and maintenance notes
Fit the meter in the pipe with the flow arrow in the flow direction, and order a check valve separately where needed. Strainers are factory fitted on the threaded meters. Configure the meter with the optical eye and USB, and read the registers. The battery life is up to 16 years, so there is no routine work other than reading and checking the seals and the connections.
Requesting a quotation for the Kamstrup flowIQ 3100
Please send the Q3 size, the connection, the communication type and the quantity needed. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
flowIQ 3100 construction
The measuring tube is brass or stainless steel, with a moulded PPS housing, and the electronics sit in a vacuum-sealed chamber that avoids condensation behind the glass.
flowIQ 3100 data logging
The meter keeps daily registers for 460 days and monthly and yearly data for 36 months and 10 years.
flowIQ 3100 approvals
The data sheet lists MID and OIML R 49 accuracy class 2, and several drinking water approvals.
flowIQ 3100 radio communication
The wireless M-Bus version works at 868 MHz and can be read by a drive-by or a fixed network.
Water meter records for flowIQ 3100
Keep the type number, the serial number and the installation reading with the metering file.
Choosing the right flowIQ 3100 size
Pick the Q3 size from the normal flow of the building and the peak flow, not from the pipe size.
flowIQ 3100 drinking water approvals
The data sheet lists WRAS, ACS, Belgaqua, SCU, PZH and BWGL approvals for contact with drinking water.
flowIQ 3100 battery life
The 3.65 V lithium C-cell gives up to 16 years of life, and up to 8 years for the wired M-Bus version at a battery temperature below 55 degrees C.
Documents and quotation
The Kamstrup flowIQ 3100 data sheet is attached. When requesting a quotation, confirm Q3, thread or flange size, installation length, communication package, whether a check valve is required, and the destination country. We will compare your details against the Kamstrup documentation before quoting.
Datasheets & Documents
- Datasheet Kamstrup flowIQ 3100 Data Sheet (FILE100001568_B_EN_09.2024) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Ultrasonic measurement with no moving parts is the idea behind the flowIQ water meters and ultrasonic energy meters of Kamstrup. The Danish company, founded in 1946 in Skanderborg, makes meters for water, heat and cooling that are read remotely. Seven Star LLC lists the Kamstrup flowIQ water meters and the MULTICAL 403 energy meter, and supplies Kamstrup meters to utilities, district cooling operators and building owners in Oman and the GCC.
Kamstrup meter families on this page
The flowIQ 2200 is an ultrasonic smart water meter for residential, multi-unit and commercial connections. The flowIQ 4200 is the bulk water meter, made in five sizes from DN125 to DN300. The MULTICAL 403 is an ultrasonic thermal energy meter that can be supplied as a heat meter, a cooling meter or a combined heat and cooling meter, with a matched pair of temperature sensors and communication modules.
Ordering Kamstrup meters: what we need
Send the type number from the meter front if you are matching installed units. Otherwise give nominal flow and pipe size, connection type and meter length, heat or cooling service, where the flow sensor sits (supply or return pipe), the temperature sensor type and cable length, and the communication you need, for example wired M-Bus or a radio option.
Browse Kamstrup products by category: Flowmeters.
Related products
Frequently Asked Questions
Nominal flow Q3 runs from 2.5 to 63 m3/h (2.5, 4.0, 6.3, 10, 16, 25, 40 and 63), with threaded connections from G1B to G2B and flanged DN50, DN65 and DN80, and it is approved with a dynamic range up to R630 according to the cover.
No. The datasheet describes it for cold water: 0.1 to 30 °C (T30, Sigfox) or 0.1 to 50 °C (T50, wired and wireless M-Bus).
Integrated Wireless M-Bus 868 MHz (mode C1 and T1 OMS), linkIQ for selected markets, Sigfox and a wired M-Bus version. Consumption can also be read from the display or the optical eye.
It is IP68 type tested, hermetically vacuum sealed and described as suitable for meter pits and distribution wells. Direct prolonged sunlight must be avoided.
No. Seven Star LLC is an independent industrial supplier in Muscat and is not a distributor or agent of Kamstrup. We check the type number against Kamstrup documentation before quoting.