- Industrial Communications
- AC Drives
- Vibration Monitoring
- PLC & I/O Cards
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Encoders
- Industrial Computers
- Safety Switches & Guard Locking
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Servo Drives
- Automation Software
- Robotics
- Machine Vision
Brand: EVAPCO
EVAPCO ATWB Induced Draft Closed Circuit Cooler
Description
A closed circuit cooler that keeps the process fluid out of the air
The EVAPCO ATWB is an induced draft, counterflow closed circuit cooler: the process fluid circulates inside the tubes of a coil and never touches the outside air, while spray water and air are used outside the coil to take the heat away. That is the difference from an open cooling tower, whose water is exposed to dust and debris and often has to be separated from the process by a plate heat exchanger that costs approach temperature. EVAPCO describes the ATWB as the original Advanced Technology closed circuit cooler and lists a very wide range, from 91 to 37,765 MBH, in many box sizes.
The process fluid enters the Thermal-Pak II coil at the top connection, and water from the sump is pumped over the tubes while an axial fan draws air up through the unit against the falling water. A small part of the spray water evaporates and carries heat away, and the cooled fluid leaves through the bottom connection. Because the coil sits in the air stream, the unit can also run dry when ambient conditions allow, stopping the spray pump and saving water and pump energy, and EVAPCO states inlet fluid temperatures up to 170 F are possible where an open tower is limited by its fill to 130 F.
Technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer | EVAPCO, Inc. |
| Type | Induced draft, counterflow, axial fan closed circuit cooler |
| Capacity range (EVAPCO page) | 91 to 37,765 MBH |
| Coil | Thermal-Pak II elliptical tube coil with CrossCool internal tube enhancement; galvanized, Type 304 or Type 316 stainless steel |
| Coil design pressure (guide specification) | 300 psi, ANSI/ASME B31.5, strength tested and air-under-water leak tested |
| Coil connections | Beveled for weld; flanged or grooved optional |
| Fan | Axial propeller, extruded aluminum blades, venturi cowl, galvanized guard |
| Fan motor | TEFC or TEAO, premium efficient, VFD duty |
| Fan drive | Power-Band multigroove solid back belt sized for 150% of motor power; aluminum sheaves |
| Fan shaft bearings | Self-aligning pillow block, minimum L10 life 100,000 hours |
| Drive system warranty (EVAPCO) | 5 years, standard on Power-Band drive systems |
| Spray nozzles | ZMII, 1-1/4 in orifice, mounted in Schedule 40 PVC piping |
| Drift eliminators | PVC, drift rate 0.001% |
| Louvers | Formed PVC, sight-tight design |
| Basin | Galvanized steel, sloped clean pan; Type 304 or 316 stainless optional; stainless steel strainer |
| Make-up | Brass mechanical valve with plastic float; electric water level control optional |
| Sound options | Low sound fan, super low sound fan (9 to 15 dB(A) reduction per EVAPCO), water silencers, discharge attenuation, attenuation walls |
| Certification statements | CTI certified, IBC compliant (upgraded structural design available), FM Approved construction available (EVAPCO page) |
Model range and engineering data
Models are written as, for example, ATWB 9-3I14: the first number appears to be the cabinet width series, the middle number and letter the coil and fan selection, and the final number the cabinet length in feet (derived reading from the drawings, confirm on certified prints). The printed tables give shipping weight, heaviest section weight, operating weight, fan hp, air flow, spray pump hp and gpm, coil volume, and the remote sump data. Selected rows:
| Model | Fan hp | Air flow cfm | Pump hp / gpm | Coil volume gal | Shipping lb | Operating lb |
|---|---|---|---|---|---|---|
| ATWB 9-3I14 | 10 | 55,780 | 3 / 600 | 250 | 11,240 | 17,550 |
| ATWB 9-7M14 | 30 | 68,930 | 3 / 600 | 565 | 19,330 | 28,270 |
| ATWB 9-3H18 | (2) 7.5 | 75,570 | 5 / 800 | 319 | 15,200 | 23,370 |
| ATWB 9-7K18 | (2) 20 | 89,630 | 5 / 800 | 725 | 25,650 | 37,200 |
| ATWB 9-3H21 | (2) 7.5 | 83,760 | 7.5 / 1,050 | 370 | 17,260 | 26,870 |
| ATWB 17-3I12 | (2) 10 | 100,630 | (2) 3 / 1,100 | 432 | 19,880 | 30,760 |
Notes in the tables state that the number of coil connections doubles when the flow rate exceeds 900 gpm on the 9 x 14, 9 x 18 and 9 x 21 models, and 1,800 gpm on the 17 x 12 models, as a required high-flow coil configuration. Series flow piping, stainless steel coils, low sound fans and non-certified options are marked by suffix letters on the model number.
Construction, access and water treatment
The basin is accessible from all four sides by lifting out the lightweight louver, the bottom of the fill section stands at least 4 ft above the basin floor, and the pan slopes completely to a depressed section so that dirt can be flushed through the drain. Optional equipment printed in the bulletin includes a sloped ladder, a working platform with davit, a basin level platform, a hinged louver access door, an all stainless steel option excluding fans and coils, and a vibration cutout switch.
EVAPCO offers factory mounted water treatment on the unit: the Smart Shield solid chemical system or the Pulse-Pure chemical-free system, plus the Pass-Protect passivation process for galvanized steel. A remote sump arrangement omits the spray pump and strainer and supplies an oversized outlet, and a bleed line is required to control concentration of impurities in the recirculating water.
Using the ATWB in Oman and the GCC
Closed circuit coolers are used in the region where the process fluid must stay clean, such as cooling for compressors, furnaces, induction heating, data centres, power generation equipment and water-cooled heat pumps. Because the fluid stays inside the coil, fouling of the process side is avoided, which is valuable where dust and sand would contaminate an open tower system. Selection must be made at the project’s design wet-bulb temperature, which can be high in coastal summer conditions.
The spray water outside the coil still needs a water treatment programme, blowdown control and a Legionella control plan, because scale on the coil reduces capacity quickly. Plan regular cleaning of the basin and strainers.
Information to send with an enquiry
- Process fluid, flow rate and temperatures
- Design wet-bulb temperature
- Make-up water quality
- Sound limits and quantity
Documents and quotation
The attached engineering data bulletin includes the full ATWB model tables, drawings, steel support layouts and the guide specification text. Seven Star LLC is an independent supplier in Muscat; to quote a closed circuit cooler we need the process fluid and flow, entering and leaving temperature, design wet bulb and dry bulb, allowable pressure drop and footprint limits. Related items are under cooling equipment.
Datasheets & Documents
- Datasheet EVAPCO ATWB closed circuit coolers engineering data and bulletin (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
EVAPCO is an employee-owned manufacturer of evaporative cooling and heat transfer equipment, founded in 1976 and headquartered in Taneytown, Maryland. Its cooling towers, closed circuit coolers, evaporative condensers and dry coolers serve commercial HVAC, industrial refrigeration, power generation and industrial process cooling.
EVAPCO product families
The range runs from factory-assembled cooling towers to larger field-erected equipment. Open cooling towers reject heat by evaporation, closed circuit coolers keep the process fluid inside a sealed coil, and evaporative condensers cool refrigerant directly for ammonia and other refrigeration plants. The eco-Air series adds dry and adiabatic coolers that use little or no water, and EVAPCO publishes engineering data bulletins for its model families.
EVAPCO equipment from Seven Star LLC
Seven Star LLC is an independent supplier in Muscat and supplies EVAPCO cooling equipment against project duties. Send the heat load, fluid, temperatures and site conditions with your request for quotation, and use the product pages for the datasheets of each EVAPCO series.
Related products
Frequently Asked Questions
The ATWB is a closed circuit cooler: the process fluid stays inside a sealed coil and is cooled by spray water and air outside it, so the process loop is not exposed to the environment.
EVAPCO states the coil in the air stream gives a higher dry bulb switchover temperature, so the unit can satisfy some loads in dry mode with the spray pump off.
It gives a coil design pressure of 300 psi in compliance with ANSI/ASME B31.5, strength tested and leak tested using air under water.
Galvanized steel is standard, and Type 304 or Type 316 stainless steel coils are available as options.
The bulletin states a standard 5-year warranty covering fan, fan motor, fan shaft, belts, sheaves and fan bearings on the Power-Band drive system.

Reviews
There are no reviews yet.