- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- HMI Displays
- Motor Soft Starters
- Isolator & Barrier
- Pneumatic Cylinders
- Automation Software
- Machine Vision
- Robotics
Brand: Accuenergy
Accuenergy Acuvim II Advanced Power and Energy Meter
Description
Acuvim II is the Accuenergy multifunction power and energy meter for panels and switchgear, with class 0.1s active energy (IEC 62053-22) and ANSI C12.20 class 0.1. It is offered as the Acuvim IIR and as the Acuvim IIW, which adds IEC 61000-4-30 class S power quality event measurement, in a 96 mm panel meter or a DIN rail transducer form.
A modular meter that grows with the project
The base meter samples at 512 samples per cycle, measures harmonics up to the 63rd order, and offers a Fast Read mode with a 20 ms Modbus refresh rate and fast logging at 100 ms and 50 ms intervals. A custom moving-average frequency filter gives 0.001 Hz resolution, with a window of 1 to 50 cycles. The 4th CT input measures neutral current.
Up to three plug-in modules can be attached: a communication module (AXM-WEB2, WEB2-D, WEB2-FOLC, NET2 or RS485) and I/O modules adding digital, relay, analogue, residual-current (RCM) and RTD temperature channels. The WEB2 option expands logging memory from 8 MB to 8 GB and adds protocols from IEC 61850 2nd Edition to PROFINET.
Features stated in the datasheet
- Three assignable historical logs, real-time clock and four-tariff time-of-use energy.
- Up to 16 alarms chosen from 80 available parameters, triggering the alarm DO.
- Dual-source energy (grid and generator) in the function list; waveform capture on trigger, DI change, sag or swell.
- Acuvim IIW: class S readings at 10/12 cycles, 150/180 cycles, 10 minutes and 2 hours, plus class S PQ events with duration.
Technical specification
Metering (datasheet)
| Parameter | Specification |
|---|---|
| Voltage | 0.1 %; 0.1 V; 10 V – 1000 kV |
| Current | 0.1 %; 0.1 mA; 5 mA – 50000 A |
| Power, reactive, apparent | 0.1 %; 1 W; ± 9999 MW |
| Power factor | 0.1 %; -1.000 to 1.000 |
| Frequency | 0.001 %; 0.001 Hz; 45 – 65 Hz; 400 Hz on a dedicated model |
| Energy | 0.1 %; 0.1 kWh or 0.001 kWh resolution; up to 99999999.9 kWh |
| Harmonics, phase angle, unbalance | 1.0 %, 2.0 %, 2.0 %; harmonics resolved to the 63rd |
| Energy accuracy classes | Active class 0.1s IEC 62053-22 and 0.1 ANSI C12.20; reactive class 0.5s IEC 62053-24 |
Inputs, communication and environment
| Parameter | Specification |
|---|---|
| Current inputs | 5 A, 1 A, 333 mV, Rogowski coil, 80/100/200 mA; pickup 5 mA, 1 mA, 0.25 mV, 0.15 mA; accuracy 0.1 % at reading |
| Voltage inputs | 480 Vac L-N, 828 Vac L-L; 2 Mohm per phase; withstand 1500 Vac continuous |
| Control power | P1V3: 100 – 415 Vac 50/60 Hz or 100 – 300 Vdc, 5 W; P2V3: 20 – 60 Vdc |
| Communication | RS-485 Modbus RTU or BACnet MS/TP, 2400 – 115200 bps; optional second RS-485; Ethernet modules for Modbus TCP, DNP 3.0, IEC 61850, SNMP V3, BACnet/IP, MQTT, PROFINET |
| I/O module functions | Digital input (20 – 160 Vac/dc), photo-MOS digital output, Form A relay (5 A / 250 Vac), analogue in/out, 2 RCM inputs class 1, 2 RTD inputs PT100/PT1000/KTY83/KTY84 |
| Operating / storage temperature | -25 to 70 C / -40 to 85 C; humidity 5 – 95 % non-condensing |
| Dimensions (panel version) | 96 x 96 x 64.3 mm; opening 92 x 92 mm |
| Standards | IEC 62053-22, ANSI C12.20, IEC 61557-12, IEC 61010-1, UL 61010-1, EN55011; BTL listed for B-SA; IEC 61850 2nd Ed. conformance |
Order code and modules
The code is Meter Model – Mounting Option – Frequency – Current Input – Power Supply. Models: Acuvim IIR (data logging, TOU) and Acuvim IIW (IIR plus waveform capture and PQ event logging); mounting D (LCD panel meter) or M (DIN rail transducer without display); blank for standard frequency or 400 for 400 Hz; current 5A, mV or mA; power supply P1V3 or P2V3. Examples printed: Acuvim-IIR-M-mV-P2V3 and Acuvim-IIW-D-5A-P1V3.
Add -S after the power supply for the anti-tampering seal option. At most three modules may be attached; install a communication module first on the back, and use no more than two of the same I/O module.
Installation notes
Accuenergy suggests three CTs for each three-phase circuit and a USB-RS485 converter for set-up. The DIN-rail version uses the optional AXM-DIN adapter and can have a remote display (REM-DS2); an IP66/NEMA 4X cover is available for harsher locations.
Specification values on this page come from the datasheet; confirm wiring and module configuration against the current user manual before commissioning.
Applications
Listed uses include submetering, energy management, energy storage and microgrids, substations and distribution, power generation, transformer monitoring, load banks, building automation, measurement and verification, PDUs and data centres. General engineering note: the IIW suits plants that need to log sags and swells in oil and gas and petrochemical switchgear.
Related Accuenergy items
For class A power quality see the Acuvim 3; for a more economical range see the Acuvim L. More in the power meters category.
Commissioning and enquiry notes
Set the wiring mode, CT and PT ratios and communication settings at commissioning, and synchronise the clock so recorded events match other systems. Oman’s networks run at 50 Hz. Check panel temperature in summer.
Information to send with an enquiry
- IIR or IIW and the add-on modules needed
- Quantity
Frequently asked questions
What is the difference between Acuvim IIR and IIW?
The IIW adds IEC 61000-4-30 class S power quality measurement, waveform capture and PQ event logging on top of the IIR functions.
Which current sensors can be connected?
5 A, 1 A, 80/100/200 mA, 333 mV and Rogowski coil inputs, selected by the current-input ordering code.
How can communication be expanded?
With AXM modules such as WEB2, WEB2-D, WEB2-FOLC, NET2 and RS485, which add Ethernet, Wi-Fi, fibre and protocols including IEC 61850 and BACnet/IP.
How many modules fit on one meter?
A maximum of three modules, with the communication module installed first, and no more than two of the same I/O module.
Does Seven Star LLC act as an Accuenergy distributor?
No, we are an independent supplier in Muscat and supply Accuenergy items on request rather than acting for Accuenergy.
Documents and quotation
Need Acuvim II? The Accuenergy datasheet and user manual are attached to this listing. Seven Star LLC (independent supplier, Muscat) can quote the item and arrange supply on request; list quantity and site location in your enquiry. Verify the order code and electrical options in the documents before ordering. Other products are in the category page.
Datasheets & Documents
- Datasheet Accuenergy Acuvim II Advanced Power & Energy Meter datasheet, version 2.0.21 (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Accuenergy is a Canadian manufacturer of power and energy meters, founded in 1998 and headquartered in Toronto, with offices in Los Angeles, Beijing and Pretoria. Its first multifunction meter line, Acuvim, reached the global market in 2003. Accuenergy makes AC and DC power meters, multi-circuit submeters, current sensors and communication gateways.
Accuenergy company profile
| Founded | 1998, Toronto, Canada |
|---|---|
| Headquarters | Toronto, Canada |
| Offices | Los Angeles, Beijing and Pretoria |
| First product line | Acuvim multifunction meters, 2003 |
| Product families | Acuvim power meters, AcuRev DIN-rail and multi-circuit submeters, AcuDC DC power and energy meters, split-core and Rope CTs, AcuLink gateways |
Milestones
- 1998: Accuenergy is founded in Toronto.
- 2003: Acuvim meters reach the global market.
Power meters, DC meters and submeters
The Accuenergy range covers Acuvim multifunction and power quality meters, AcuRev DIN rail meters and multi-circuit submeters, AcuDC meters for DC systems and EV charging, plus current transformers, Rogowski coils and communication modules. Each datasheet lists accuracy classes, inputs, communication options and ordering codes. Accuenergy states that its operations hold ISO 9001, ISO 14001 and ISO 45001 certification and that its management systems are certified to ISO 27001 and ISO 50001.
Supply through Seven Star LLC
Seven Star LLC is an independent supplier in Muscat that quotes Accuenergy products for projects in Oman and the GCC, with the official Accuenergy datasheet attached to each product page.
Accuenergy products we list
Facts checked against Accuenergy's own about page (accuenergy.com), October 2026.
Related products
Frequently Asked Questions
The IIW adds IEC 61000-4-30 class S power quality measurement, waveform capture and PQ event logging on top of the IIR functions.
5 A, 1 A, 80/100/200 mA, 333 mV and Rogowski coil inputs, selected by the current-input ordering code.
With AXM modules such as WEB2, WEB2-D, WEB2-FOLC, NET2 and RS485, which add Ethernet, Wi-Fi, fibre and protocols including IEC 61850 and BACnet/IP.