JUMO 902550 Surface RTD Temperature Probes for Pipes and Flat Surfaces
Description
Strap-on surface probes that measure without cutting into the pipe
The JUMO 902550 family of surface RTD temperature probes is the preferred choice for measuring temperatures on closed pipe systems and other round or flat surfaces between -50 and +260 degC. The probes install with tightening bands or cable ties, so the measuring location needs no mechanical modification. Only basic types 902550/10 and /11 have a hole for screw-fitting to a surface such as a heating plate. Because the indirect method does not disturb the flow, pressure and chemicals cannot shorten the probe life.
The low thermal mass of the probe has little influence on the measured object, and heat-conducting paste is available to improve transfer; JUMO cautions that large differences between medium and surroundings will influence the measurement and recommends additional insulation in such cases. The standard insert is a Pt100 to DIN EN 60751 class B in 2-wire circuit, with Pt500 and Pt1000 as options. The range is completed by the 902554 pipe contact probe with a cable socket housing, available with an analog transmitter.
Technical specifications
| Parameter | Specification |
|---|---|
| Basic types, cable | 902550/10 aluminium fitting, screw hole; /11 stainless 30 AL, screw hole; /20 stainless 40 AL; /30 and /31 aluminium |
| Basic types, housing | 902554/41 pipe, IP54, with kit; /42 flat surface, IP54; /44 pipe, IP65, with kit |
| Temperature range | -50 to +260 degC |
| Cable / operating temperature | PVC -5 to +105 degC (730); silicone -50 to +180 degC (378); PTFE -50 to +260 degC (386); stainless-sheathed PTFE (388) |
| Housing versions | 361: -50 to +90 degC; 365: -50 to +120 degC; 474: -40 to +80 degC (with transmitter); 573: -30 to +90 degC |
| Measuring insert | Pt100 (2-/3-wire), Pt500, Pt1000, Ni1000, KTY81-110, KTY81-122, LM235 Z, NTC 1 kOhm, depending on type |
| Tolerance class | B (standard), A, AA on 902554/44 |
| Protection fitting | Stainless steel 1.4571, aluminium or plastic |
| Cable ends | Tin-plated wires, ferrules to DIN 46228 part 4, plug-in sleeve 6.3 to DIN 46247, multi-pole connector |
| Cable length AL | 2500 mm standard; 500 to 500,000 mm in 500 mm steps |
| Housing material | PC, silver-gray/blue (/41, /42), white (/44) |
| Transmitter (902554/44) | 4 to 20 mA from 7.5 to 30 V DC, accuracy 0.1 %; 0 to 10 V from 15 to 30 V DC, accuracy 0.2 %; settling 10 ms or less |
| Installation kit | Tightening band and heat-conducting paste for pipes up to 100 mm diameter, part no. 00493675 |
| Options | SIL and PL compatible (058); strain relief spring (315) or hose (316); IP65 (404); spring-cage terminals (242) |
Which 902550 or 902554 type fits the surface?
Pick the cable-connected 902550 types for tight spaces and the housing-type 902554 probes for clean installation in building services. Order code for the cable types is basic type – cable code – measuring insert – tolerance class – cable end – cable length / extra codes, for example 902550/10 – 386 – 1003 – 1 – 11 – 2500 / 000. The housing types use basic type – operating temperature – insert – class / extra code, for example 902554/41 – 365 – 1003 – 1 / 000.
| Stock order code | Part no. |
|---|---|
| 902550/10-386-1003-1-11-2500/000 | 00306774 |
| 902550/20-386-1003-1-11-2500/000 | 00065547 |
| 902550/30-378-1003-1-11-2500/315 | 00065531 |
| 902550/31-378-1003-1-11-2500/000 | 00507000 |
| 902554/41-365-1003-1/000 | 00378669 |
| 902554/41-365-1003-1/404 (IP65) | 00376703 |
Operating range 474 (-40 to +80 degC) is valid only with extra codes 330 or 333, which add a 4 to 20 mA or 0 to 10 V analog transmitter to a Pt100 probe (data sheet 707030). Extra code 242 (spring-cage terminals) cannot be combined with a transmitter.
Getting accurate readings from a surface probe
A surface probe measures the wall, not the fluid, so the reading lags the true medium temperature and is lower than it on a hot pipe if heat escapes to the room. Fit the probe on clean bare metal, apply heat-conducting paste, tighten the band, and insulate over the sensor and the adjacent pipe so the sensor sees the pipe and not the air. The installation kit is rated for pipes up to 100 mm diameter. Mount on the side of horizontal pipes rather than the bottom to avoid sediment or condensate effects (general practice).
The silicone, PTFE and stainless-sheathed cables cover different ambient exposures along the cable route, so pick the one matching the hottest point the cable passes. Applications include heating and chilled-water return lines, boiler flow lines, hot-water storage, heat meters, compressors and steam trace lines, as well as heating plates and platens through the screw-fitted types.
Choose the mounting style from the surface and temperature. Types 902550/10 and /11 have a fastening hole for plates, 902550/20 and /30 to /31 use fittings of stainless steel or aluminium for clamping, and the 902554 housing types are for building services pipes and flat walls. Housing temperature codes are 361 (-50 to +90 degC), 365 (-50 to +120 degC), 573 (-30 to +90 degC) and 474 (-40 to +80 degC, only with transmitter extra codes 330 or 333). Strain-relief spring or hose can be added to cable types, and spring-cage terminals to the 902554/44 housing. The installation kit is a separate sales item.
Documents and quotation
The JUMO data sheet 902550 is attached below. Seven Star LLC supplies JUMO sensors from Muscat; state the basic type, cable or housing option, element, cable length and any transmitter so we can quote. More probes are grouped under https://omansevenstar.com/product-category/sensors-transmitters/temperature/.
Datasheets & Documents
- Datasheet JUMO data sheet 902550 (surface RTD temperature probes) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Temperature measurement is the origin of JUMO, founded in 1948 in Fulda, Germany, as a maker of glass thermometers. Today the catalog covers sensors and transmitters for temperature, pressure, level and liquid analysis, plus controllers and recorders. Seven Star LLC lists JUMO RTD probes, pressure and differential pressure transmitters, pH, conductivity, turbidity and dissolved oxygen instruments, and sources them for plants in Oman.
JUMO product families listed
JUMO uses family names that recur across the catalog:
- dTRANS: transmitters, including dTRANS T01 and T100 for temperature, dTRANS p02 DELTA for differential pressure, and dTRANS pH 02 and CR 02 for liquid analysis
- Wtrans: wireless probes and transmitters, such as Wtrans T for RTD temperature and Wtrans p for pressure
- digiLine and ecoLine: digital and optical analysis sensors, for example the digiLine O-DO S10 dissolved oxygen sensor and the ecoLine NTU turbidity sensor
- NESOS: float-based level transmitters and switches
- RTD temperature probes: screw-in types such as 902030 and mineral-insulated designs
Where JUMO sensors are used
JUMO sensors and transmitters are typical of food and beverage lines, water and wastewater treatment, pharmaceutical utilities, heating and cooling systems, and packaged machinery supplied to the GCC by European builders. Many requests are for a like-for-like replacement of a probe fitted by the machine maker, where length, thread and connector have to match exactly.
Ordering JUMO parts: what we need
JUMO identifies each product group by a six-digit type number, such as 902030, followed by an order code that fixes the options. The label of the delivered item normally carries a part number as well. Send whichever you have, ideally both, or a photo of the label. For JUMO temperature probes add insertion length, diameter, process connection, sensor type and wiring. For JUMO pressure sensors state range, output, process connection and electrical connector. For analysis sensors name the transmitter they connect to and the cable length.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
With tightening bands or cable ties on pipes; types /10 and /11 have a hole for screwing to a flat surface.
Up to +260 degC with the PTFE cable versions.
Yes, the 902554/44 pipe probe can be fitted with a 4 to 20 mA or 0 to 10 V analog transmitter.
Heat-conducting paste, supplied in the installation kit, part no. 00493675.
Pt100, Pt500 and Pt1000 on the cable types, and Ni1000, KTY and NTC elements on the housing types.